CP 503/A, CP 505/A,D,K, CP 507/
A,C
Mounting and installation instructions
Project engineering manual V1.06
31
© KEBA 2021
Fig. 5-15: Example module package
1
... Expansion modules
2
... CP 50x/x
3
... Input / output modules
Information
For adding and removing input/output modules and expansion modules, the
module package may already be mounted on the mounting rail, see
In order to ensure the stable function of the module package, the total power
requirement of the connected modules when added together must not ex-
ceed the performance values of the CP 50x/x specified in the technical data,
see "Technical data".
Information
●
In order to calculate the number of input/output modules that can be
connected on the right, the respective performance values specified in
the technical data under "Power input KeBus 5 V" and "Power con-
sumption KeBus 24 V" must be used in the respective configuration
manuals.
●
In order to calculate the number of expansion modules that can be
mounted in a row on the left, the power values specified in the technical
data under "Power consumption expansion bus 3.3 V" and "Power con-
sumption expansion bus 24 V" must be used in the respective project
engineering manuals.
●
The project engineering manuals of the respective modules must be
taken into account with regard to the order of the expansion modules.