3 Technical Data
3.1 Operating conditions
3.1.1 climatic conditions
Storage
Standard
class
Note
Surrounding temperature
1K4
-25…55 °C
Relative humidity
1K3
5…95 % (without condensation)
Storage height
–
–
Max. 3000 m aboce sea level
Transport
Standard
class
Note
Surrounding temperature
2K3
-25…70 °C
Relative humidity
2K3
95 % bei 40 °C (without condition)
Operation
Standard
class
Note
Surrounding temperature
3K3
5…40 °C (extended to -10…45 °C)
With temperature over 45°C to max. 55°C a
derating of 5 % per 1 K must be taken into con-
sideration.
Coolant inlet tem-
perature
Air
–
–
5…40 °C (-10…45 °C)
Water
–
–
5…40 °C
Relative humidity
3K3
5…85 % (without condensation)
Version and degree of protec-
tion
IP54
Protection against dust in hazardous quanti-
ties
Protection against splash water on all sides
Non-conductive pollution, occasional conden-
sation when PDS is out of service.
The degree of protection is obtained if the
mounting in the final application is correctly
executed by the customer
Site altitude
–
–
max. 2000 m above sea level
• Ab 1000 m ist eine Leistungsreduzierung
von 1 % pro 100 m zu berücksichtigen.
• Ab 2000 m hat die Steuerkarte zum Netz
nur noch Basisisolation. Additional meas-
ures must be carried out when wiring the
control system.
Table 2:
Climatic conditions
23