Installation
©
2020 KEB America, Inc.
19
5.2 Electrical Installation
5.2.1 Terminals
Figure 3: Terminals
High Voltage Connection X1A
Terminal Function
Connection
Tightening Torque
BR+
Connection to
Brake Resistor
Stranded conductor with wire-end ferrule.
0.5 to 16 mm
2
UL stranded conductor. 20 to 4 AWG
2.0 Nm
18 in lbs
BR-
Earth/Ground Connection
Terminal Function
Connection
Tightening Torque
GND,
Connection to
Ground
M5 screw
Use UL listed ring style crimp connector.
Recommended wire gague 4.0mm
2
or 12 AWG
2.0 Nm
18 in lbs
Control Connection X2A
Terminal Function
Connection
Tightening Torque
0V
DC Power
Supply
Stranded conductor with wire-end ferrule.
0.13 to 4 mm
2
UL stranded conductor. 26 to 10 AWG
0.8 Nm
7.0 in lbs
24V
K1
Normally-Closed
Contact
Pilot Duty Rated
K2
Table 6: Terminal Connections