7 Connection of the Control
7.1 Control board for F5 AIC devices
7.1.1 Assignment of the terminal block X2A
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
PIN Function
Name
Default assignment
Description
1
+ Setpoint input 1
AN1+
The input signal 0...±10V; 0...±20mA
and
4...20mA is determined with An.00
/ An.10. Resolution: 12 Bit, Ri =
30kΩ, scan time: 1ms/ at fast set
-
point setting: 250μs
2
- Setpoint input 1
AN1-
3
+ Setpoint input 2
AN2+
4
- Setpoint input 2
AN2-
5
Analog output 1
ANOUT1
The output at the analog output
is set with An.31 / An.36. Voltage
range: 0...±10V, Ri = 100Ω, res
-
olution: 10 Bit, PWM frequency:
3.4kHz, limiting frequency filter 1.
Order: 178Hz
6
Analog output 2
ANOUT2
7
+10 V output
CRF
Reference voltage 10V DC
+5% / max. 4mA for setpoint poten-
tiometer
8
Analog ground
COM
Ground for analog inputs and out-
puts
9
10 Progr. input 1
I1
2. Setpoint of the control
voltage
All digital inputs are freely program-
mable. The control release is firmly
linked with the input ST, but can be
assigned with additional functions.
Ri = 2.1kΩ
Scan time: 1ms
11 Progr. input 2
I2
Switch-on delay, control
release ST
12 Progr. input 3
I3
13 Progr. input 4
I4
14 Progr. input forward
F
15 Progr. input reverse
R
16 Progr. input control
release
ST
ST
17 Progr. input reset
RST
RST
18 Transistor output 1
O1
Control main contactor
(DC > level)
Max. 50mA DC for both outputs are
available.
19 Transistor output 2
O2
Ready for operation (Uic
loaded)
20 +24 V output
U
out
approx. 24V DC output (max.
100mA), voltage input for ext.
supply, reference potential 0V
X2A.22/23
21 20...30 V input
U
in
22
Digital ground
0V
Reference potential for digital in-
puts/outputs
23
continued on the next page
49
CONNECTION OF THE CONTROL
Содержание COMBIVERT F5 Series
Страница 2: ......