GB-16
Start-Up Instructions
3.3
Commissioning of a
G e a r l e s s
A s y n c h r o n o u s
Machine
The following procedure is recommended for the commissioning of
the KEB COMBIVERT F4-F lift version 3.0 with a gearless
asynchronous machine with SinCos-encoder:
Adjust the parameters in ascending sequence, as this initiates partial
presettings of the unit. Start with the selection of the resolution and
the adjustment of the lift data (LF-parameter). Save the adjusted data
by activating the „ENTER key.
LF.00: Enter password (440)
LF.02: Enter setpoint setting/rotation setting
1 = Binary coded setpoint setting
2 = Input coded setpoint setting
3 = Analog setpoint setting 0...+10V
4 = Analog setpoint setting -10...+10V
LF.04: Check, if value „0“ is adjusted
LF.06: Adjust value „1“
LF.20: Enter system speed in m/s
LF.21: Enter diameter of traction sheave in mm, if necessary,
remeasure
LF.22: Enter gear reduction 1
LF.23: Enter rope suspension (1 for 1:1, 2 for 2:1 etc.)
LF.24: Enter nominal load (lifting capacity) of the cabine in kg
LF.30: Select control procedure (0=without feedback, 2=with
feedback, 3=with torque pre-control)
LF.31 to LF.33: Enter speed controller data (use pracmatical values
or inquire about adjustment at KEB)
LF.40: Enter correction speed in m/s
LF.41: Enter crawl speed in m/s
LF.42: Enter rated speed in m/s
LF.43: Enter inspection speed in m/s
LF.54: Due to the high mass moment of inertia, adjust the stopping
jerk as small as possible
(ca. 0,3m/s
3
)
dr.00: Enter rated motor power in kW (1 kW = 1.36 PS)
dr.01: Enter rated motor speed in rpm (not synchronous speed)
dr.02: Enter rated motor current in A
dr.03: Enter rated motor frequency in Hz
dr.04: Enter cos phi of the motor
dr.12: Enter rated motor voltage in V (if the value to be adjusted is
already entered, it is essential to acknowledge the value with
ENTER)