4.2.3.5 Motor temperature detection
Terminals T1, T2 at single axis module
Terminals T1A,T2A, T1B, T2B at double axis module
NOTICE
KTy or PTc cable
• Do not lay KTY or PTC cable of the motor (even shielded) together
with control cable !
• KTY or PTC cable inside the motor cable only permissible with
double shielding !
• The input is base insulated.
The KEB COMBIVERT H6 is delivered with switchable KTY84/PTC evaluation. The
desired function is set with dr33 and works in the following table:
dr33
function of T1, T2
Resistance
Display ru28
Error/
Warning
0
KTY84 (standard)
< 215 Ω
Error
2)
498 Ω
1°C
1) 2)
1 kΩ
100°C
1) 2)
1.722 kΩ
200°C
1) 2)
> 1811 Ω
Error
2)
1
PTC
< 750 Ω
T1-T2 closed
–
0.75…1.65 kΩ
(reset resistance)
undefined
–
1.65…4 kΩ
(tripping resistance)
undefined
–
> 4 kΩ
T1-T2 open
2)
Table 14:
Motor temperature detection
1)
The warning level is adjusted with pn11. The error level is adjusted with pn14.
2)
The behavior of the
drive converter
in error/warning case is set with parameter pn12.
4.2.3.6 Use of the temperature input in KTY mode
T1
T2
+
KTY84
M
KTY sensors are poled semiconductors and must be oper-
ated in forward direction ! Connect anode to T1 ! Non-ob-
servance leads incorrect measurement in the upper
temperature range. Protection of the motor winding is no
longer guaranteed.
Figure 24:
Connection of a KTY sensor
NOTICE
KTY sensors may not be combined with other devices. Otherwise
wrong measurements will be the consequence.
51
cONNEcTION Of THE POWER UNIT