GB - 27
KEB COMBICONTROL
Fl. 04
deleted bytes
Address 0904h
Displays the cleared bytes in the flash. The flash must be formatted or cleared in order to
make this place available again (not at COMPACT II).
Fl. 05
deleted files
Address 0905h
Displays the cleared files in the flash.
Fl. 06
free bytes
Address 0906h
Displays the free bytes in the flash.
Fl. 07
flash function
Address 0907h
Displays the flash status and enables the following functions by writing of a special value:
Formatting = -359074020 clearing = 597981618. Formatting only possible with supervisor
password!
3.3.5 Debugging
Parameters 06xxh are only used for the diagnosis during the production process.
3.3.6 System parameter
sy.01
Software date
Address 0001h
This parameter displays the date of the installed firmware.
sy.02
device identifier
Address 0002h
This parameter displays the software identification number (CFG-ID).
SY.07
baud rate 66019II
Address 0007h
The baud rate for the KEB DIN 66019II protocol is adjusted with this parameter. If the serial
interface X6A is used by the IEC control program, this adjustment is no longer valid.
SY.8
response delay 66019II
Address 0008h
The response delay for the KEB DIN 66019II protocol is adjusted with this parameter. If the
serial interface X6A of the IEC control program is used, this adjustment is no longer valid.