First Time Setup - Types of Control & KE2 Smart Access

Basic (Remote) Display KE2 Combo Display

 Description

Abbreviation

Scrolling Text

Ed

Ed

ELECTRIC DEFROST /TEV

Electric Defrost w/Mechanical valve

EdE

EdE

ELECTRIC DEFROST /EEV

Electric Defrost w/Electric Valve

Ad

Ad

AIR DEFROST /TEV

Air Defrost w/Mechanical Valve

AdE

AdE

AIR DEFROST /EEV

Air Defrost w/Electric Valve

SA

SA

SMART ACCESS MODE

KE2 SmartAccess (Enabled/Disabled)

Variables Menu

Basic (Remote) Display

KE2 Combo Display

Description

Abbreviation

Scrolling Text

rtP

rtP

ROOM TEMP

Room Temperature as measured by controller

CLt

CLt

COIL TEMP

Coil Temperature as measured by controller

SyS

SYS

SySTEM MODE

Current operating status

Sht

SHt

SUPERhEAT

Superheat as calculated by the controller

PrS

PrS

SUCTION PRESSURE

Suction Pressure as measured by controller

SUt

SUt

T1 SUCTION TEMP

Suction Temperature as measured by controller

SAt

SAt

SATURATION TEMP

Saturation Temperature as calculated by controller

oPn

oPn

VALVE % OPEN

Percentage EEV is open

Cor

Cor

COMPRESSOR RELAy Current status of LLS/compressor relay

dEr

dEr

DEFROST RELAy

Current Status of Defrost relay

FAr

FAr

FAN RELAy

Current Status of Fan relay

AU1

AU1

DIg 1 STATUS

Current Status/Temperature as measured by controller at Aux input 1

AU2

AU2

DIg 2 STATUS

Current Status/Temperature as measured by controller at Aux input 2

AU3

AU3

DIg 3 STATUS

Current Status/Temperature as measured by controller at Aux input 3

iP1

iP1

IP OCTET 1

First 3 digits of IP address

iP2

iP2

IP OCTET 2

Second 3 digits of IP address

iP3

iP3

IP OCTET 3

Third 3 digits of IP address

iP4

iP4

IP OCTET 4

Fourth 3 digits of IP address

Fir

Fir

FIRMWARE VERSION

Current Version of firmware on controller

System Modes

Basic (Remote) Display KE2 Combo Display

Abbreviation

Scrolling Text

rEF

rEF

REFRIgERATE

ddF

ddF

DEFROST DELAy FAN

dEF

dEF

DEFROST

drn

drn

DRAIN TIME

FdL

FdL

FAN DELAy

SoF

SoF

SySTEM OFF

oFF

oFF

OFF

Refrigerants

Abbreviation Full Name

R22

R-22

134

R-134a

42d

R-422D

42A

R-422A

40C

R-407C

40A

R-407A

507

R-507

404

R-404A

513

R-513A

450

R-450A

449

R-449A

448

R-448A

744

R-744

410

R-410A

407

R-407F

409

R-409A

408

R-408A

438

R-438A

717

R-717

452

R-452A

458

R-458A

Auxiliary Input Modes

Basic (Remote) Display

KE2 Combo Display

Description

Abbreviation

Scrolling Text

diS

diS

DISABLED

Not used

rtP

rtP

ROOM TEMP

Room temp as measured by TAIR Input

CLt

CLt

COIL TEMP

Coil Temp as measured by TCOIL Input

oni

oni

MONITOR

Monitoring Temp as measured by Aux Input

t2n

t2n

2ND (ROOM) TEMP

Inactive=2nd room temp SP off (t2F)/Active=2nd room temp SP on (t2n)

dor

dor 

DOOR SWITCh

Inactive=Door Closed (dCL)/Active=Door Open (don)

EA1/EA2/

EA3

EA1

  

EA2

  

EA3

EXTERNAL ALARM 1

EXTERNAL ALARM 2

EXTERNAL ALARM 3

Active=EAo / Inactive=EAF

SoF

SoF

SySTEM OFF

Inactive=System On (Son)/Active=System Off (SoF)

dFi

dFi

DEFROST INTERLOCK Inactive=Defrost Heaters normal (AUt)/Active=Defrost Heaters Off (oFF)

dFL

dFL

DEFROST LOCKOUT

Inactive=Defrost Normal (AUt)/Active=Defrost Not Allowed (dLo)

Valve Types

Basic (Remote) Display

KE2 Combo Display

Description

Abbreviation

Scrolling Text

thr

tHr

MEChANICAL

Traditional Thermostatic Expansion Valve

hS

HS

hSV

KE2 Therm’s Hybrid Stepper Valve

rS

rS

RSV

KE2 Therm’s Refrigeration Stepper Valve

SEi

SEi

SEI

Sporlan Valve with 1,600 steps

SEr

SEr

SER

Sporlan Valve with 2,500 steps

CrL

CrL

CAREL

Carel Valve with 500 steps

Содержание EvapOEM

Страница 1: ...t RSV 320 21167 1 2 x 1 2 10 ft RSV 320 21168 1 2 x 1 2 40 ft RSV 400 21529 5 8 x 7 8 15 ft RSV 400 21530 5 8 x 7 8 40 ft RSV 550 21594 5 8 x 7 8 15 ft RSV 550 21595 5 8 x 7 8 40 ft RSV 650 21779 5 8 x 7 8 15 ft RSV 650 21778 5 8 x 7 8 40 ft RSV C10 Stator 21149 For RSV 100 to 320 10 ft RSV C40 Stator 21150 For RSV 100 to 320 40 ft RSV LC15 Stator 21525 For RSV 400 to 650 15 ft RSV LC40 Stator 215...

Страница 2: ...nge Yellow Red Black Empty Red Green White Black EEV A B Shield RS 485 Line L1 Neutral L2 INCOMING POWER Red Black Green PSI NO COM NC NO COM GROUND EARTH GROUND FUSE NO COM L2 Supply Voltage FAN MOTOR FAN MOTOR FAN MOTOR EVAPORATOR FANS HEATER LIMIT SWITCH DEFROST HEATERS LIQUID LINE SOLENOID N C TSC1A250 1A 1A 250V slow blow 5mm x 20mm Q 1 45 May 2019 Page 2 KE2 EvapOEM Quick Start Guide Copyrig...

Страница 3: ...hout KE2 Terminal Board NO COM NO COM NC FAN RELAY COMPRESSOR RELAY DEFROST RELAY COM NO L1 N L2 VOUT MOTOR Aux3 Aux2 Aux1 TCoil TAir TSuc PSI RS 485 HS DEFROST HEATERS FANS S LLS NC N X BLK RED BLK FIELD SUPPLY 1 PHASE ETHERNET DISPLAY BLUE ORANGE YELLOW RED BLACK MOTOR RED GREEN WHITE BLACK EEV EMPTY RSV XDCR A B SHIELD G GRN ORG BLACK GREEN RED ...

Страница 4: ...fins Figure 3b shows the coil sensor properly secured NOTE On a small fraction of installations the sensor placement may require adjusting This is typically caused by product loading door openings air flow etc The sensor s should be placed where the frost disappears last on the coil Extending sensor wires After the sensors are mounted they are routed back to the controller If the wires must be ext...

Страница 5: ...n automatically enter Introduction Mode The Introduction Mode con sists of four Types of Control options Ed Electric Defrost with Mechanical TEV EdE Electric Defrost with Electric Expansion Valve Ad Air Defrost with Mechanical TEV AdE Air Defrost with Electric Expansion Valve Step 1 Using the and arrows moves the user through the avail able Types of Control options Once the preferred option is dis...

Страница 6: ...echanical valve is selected LPd LPd Press Diff for LPCO 1 0 psig 20 0 psig 15 0 psig Pressure Differential for LPCO Displays when LOW PRESSURE CUTOUT TIME LPt is greater than zero And only applies if non mechanical valve is selected rnt rnt comp Run time 0 hrs 24 hrs 6 hrs Compressor Run Time When rnt selected number of hours of cooling before starting defrost Htn Htn ELECTRIC DEFROST MODE N A N A...

Страница 7: ...mum amount of time between de energizing the liquid line solenoid compressor relay and energizing the defrost relay MULTI AIR TEMP CTRL Warmest or Average Warmest Air Warmest air use the warmest air temp from bonded controls Average air use the average air temp from bonded controls MULTI EVAP COOL Synchronized or Independent Synchronized Synchronized synchronize bonded controller in refrigeration ...

Страница 8: ...nd 3 digits of IP address iP3 iP3 IP OCTET 3 Third 3 digits of IP address iP4 iP4 IP OCTET 4 Fourth 3 digits of IP address Fir Fir FIRMWARE VERSION Current Version of firmware on controller System Modes Basic Remote Display KE2 Combo Display Abbreviation ScrollingText rEF rEF REFRIGERATE ddF ddF DEFROST DELAY FAN dEF dEF DEFROST drn drn DRAIN TIME FdL FdL FAN DELAY SoF SoF SYSTEM OFF oFF oFF OFF R...

Страница 9: ...tive if input is an open CLo active if input is shorted A2A a2a AU2 Temp sensor Alarm Alarms AU2 temperature sensor is shorted or open A3A A3A Aux Input 3 state Setpoint oPn active if input is an open CLo active if input is shorted A3A a3a AU3 Temp sensor Alarm Alarms AU3 temperature sensor is shorted or open Ad Ad Air Defrost w Mechanical valve Type of Control System operates with default values ...

Страница 10: ...m Switch Inactive Auxiliary Input External Alarm switch is not receiving external signal Ed Ed Electric Defrost w Mech valve Type of Control System operates with default values for Electric Defrost with Mechanical Valve EdE EdE Electric Defrost w EEV Type of Control System operates with default values for Electric Defrost with Electric Valve EdF EdF Extreme Temp Diff Setpoint ADVANCED TOPIC Call K...

Страница 11: ... Prn rEF rEF Refrigeration System Mode Indicates the system is currently in Refrigeration mode rFG rF Refrigerant Setpoint Type of refrigerant used see table below rFt rFt Refrigeration Fan Type Setpoint Select how fans will be run Manage Cycle Permanent On with Compressor Title 24 rnt rnt Compressor Run Time Setpoint Option for Defrost Initiation Mode ind when Compressor Run Time rnt selected num...

Страница 12: ...ccess akk for a nominal monthly fee No port forwarding No VPN KE2 Smart Access Online Access In 3 Easy Steps Preliminary Connect the KE2 Evap OEM to the customer s network NO NC COM EARTH CAT5 Ethernet Cable 1 2 3 6 5 4 7 Link ACT 100 1000Mbps POWER Customer Network youtube com ke2therm Visit our YouTube channel for videos on KE2 Smart Access Enter default information and click Log In button Site ...

Отзывы: