KE2 Evap
OEM
Quick Start Guide
dCL
dCL
Door Switch - Door Closed
Auxiliary Input
Door switch indicates door is closed
ddF
ddF
Defrost Delay Fan
System Mode
At defrost, fans will continue running for several minutes, using stored cooling in the coil. Once the
coil reaches room temp, the fans will stop, and the heaters will turn on and begin the electric defrost.
dEF
dEF
Defr Parameter
Setpoint
if DEFROST MODE = DEMAND: Coefficient to KE2 Defrost algorithm
dEF
dEF
Defrost
System Mode
Controller is performing a defrost cycle
dEr
dEr
Defrost Relay
Variables
Current state of the defrost relay
dFi
dFi
Defrost Interlock Switch
Auxiliary Input
Inactive=Defrost Heaters normal (AUT)/Active=Defrost Heaters Off (OFF)
dFL
dFL
Defrost Lockout Switch
Auxiliary Input
Inactive=Defrost Normal (AUT)/Active=Defrost Not Allowed (dLO)
dhC
dHC
DHCP
Setpoint
Turn DHCP mode on or off: EnA to enable DHCP mode / DiS to disable DHCP mode
diA
diA
Diagnostics Mode
Setpoint
Energizes each relay individually for 60 seconds: fan relay, defrost relay, compressor relay
diS
diS
Disabled
Auxiliary Input
Input is not used by the controller
dLo
dLo
Defrost Lockout
Auxiliary Input
Active = Defrost not allowed while signal is active
dnd
dnd
Demand Defrost
Setpoint
Option for Defrost Initiation Mode (ind) - when Demand Defrost (dnd) selected, system defrosts only
when dictated by decrease in evaporator efficiency; other options: Scheduled (SCH) or Compressor
Run Time (rnt)
don
don
Door Switch - Door Open
Auxiliary Input
Door switch indicates door is open
dor
dor
Door Switch
Auxiliary Input
Inactive=Door Closed (dCL)/Active=Door Open (don)
dor
dor
Door Open Alarm
Alarms
If door is open & room temp is 5 degrees above ROOM TEMP + AIR TEMP DIFF for DOOR ALARM DELAY
time
dPd
dPd
Defrosts per day
Setpoint
If DEFROST MODE = SCH: The number of evenly spaced defrosts per day the controller will initiate.
drn
drn
Drain Time
Setpoint
Time to be in drain mode (drip time)
drn
drn
Drain
System Mode
Time after defrost to allow moisture to drain from coil
dtL
dtL
Max Defrost Time
Setpoint
If DEFROST MODE = SCH: The maximum amount of time the defrost relay will be energized. (Not avail-
able if DEFROST MODE = DEMAND)
dtP
dtP
Defr Term Temp
Setpoint
Temp the coil sensor(s) must exceed to terminate defrost. Controller’s defrost mode is complete at
this point
dtt
dtt
Defr Term on Time Alarm
Alarms
Defrost terminated on time instead of temperature for two consecutive cycles
dty
dtY
Defrost Type
Setpoint
Type of Defrost: ELE - Electric; Ai - off time; HGn - hot gas w.comp on; HGF - hot gas w/comp off
EA1
EA1
External Alarm Switch
Auxiliary Input
Active=EAo / Inactive=EAF
EA1
EA1
External Alarm 1
Alarms
If AU1 IN MODE = EXT ALARM: The digital input is in an active state
EA2
EA2
External Alarm 2
Alarms
If AU2 IN MODE = EXT ALARM: The digital input is in an active state
EA3
EA3
External Alarm 3
Alarms
If AU3 IN MODE = EXT ALARM: The digital input is in an active state
EAo
EA3
External Alarm Switch Active
Auxiliary Input
External Alarm switch is receiving Active signal
EAF
EA3
External Alarm Switch Inactive
Auxiliary Input
External Alarm switch is not receiving external signal
Ed
Ed
Electric Defrost w/Mech. valve
Type of Control
System operates with default values for Electric Defrost with Mechanical Valve
EdE
EdE
Electric Defrost w/EEV
Type of Control
System operates with default values for Electric Defrost with Electric Valve
EdF
EdF
Extreme Temp Diff
Setpoint
ADVANCED TOPIC: Call KE2 Therm for assistance
EdF
EdF
Excess Defrost Alarm
Alarms
32 defrosts or more within 48 hours
Edt
Edt
Valve Type
Setpoint
Type of valve used on the system: mechanical, pre-configured electric, custom EEV configuration
EFL
EFL
Email Failure Alarm
Alarms
Email alert was not confirmed by email server provided after seven consecutive attempts
ELE
ELE
Electric Defrost
Setpoint
Option for evaporator Defrost Type (dtY) - Electric defrost heaters used; other options, Hot Gas w
Compressor Off (HGF), Hot Gas with Compressor On (HGn) or Air Off time Defrost (Ai)
EnA
EnA
Enabled
Setpoint
Enabled - Option to allow connection with KE2 Smart Access
FAC
FAC
Factory reset
Setpoint
Press and hold to reset the controller to the factory default setpoints
FAh
FAH
Fahrenheit
Setpoint
Option for units for the temperature display, in degrees - Fahrenheit or Celsius (CEL)
FAr
FAr
Fan Relay
Variables
Current state of the fan relay
FdL
FdL
Fan Delay
System Mode
Coming out of defrost, the LLS relay will be energized, and the coil will pulldown until it reaches 20ºF,
or 2 minutes, before the fans turn on. This allows any moisture on the coil to re-freeze, keeping it from
spraying and forming ice drops on the walk-in’s surfaces.
Fir
Fir
Firmware Version
Variables
Current version of the firmware on the controller
FoC
FoC
Fans on with Compressor
Setpoint
Option under Refrig Fan Type (rFt) to manage fans in OFF, then turn ON in refrigeration
hAd
HAd
High Temp Alarm Delay
Setpoint
Minutes the room temperature must remain above ROOM TEMP + HIGH TEMP ALARM OFFSET before
issuing a HIGH TEMP ALARM
hAo
HAo
High Temp Alarm Offset
Setpoint
The number of degrees above ROOM TEMP for a HIGH TEMP ALARM condition.
hgF
H F
Hot Gas Defrost w. Compressor
Off
Setpoint
Option for evaporator Defrost Type (dtY) - Hot Gas defrost used with the Compressor Off; other op-
tions Electric (ELE), Hot Gas w Compressor On (HGN), or Air Off time Defrost (Ai)
hgn
H n
Hot Gas Defrost w. Compressor
On
Setpoint
Option for evaporator Defrost Type (dtY) - Hot Gas defrost used with the Compressor On; other op-
tions Electric (ELE), Hot Gas w Compressor Off (HGF), or Air Off time Defrost (Ai)
hS
HS
HSV
Valve Type
KE2 Therm’s HSV, Hybrid Stepper Valve
hSh
HSH
High Superheat Alarm
Alarms
Superheat above upper limit
htA
HtA
High Temperature Alarm
Alarms
Room temperature is above ROOM TEMP + AIR TEMP DIFF + HIGH TEMP ALARM OFFSET for longer
than HIGH TEMP ALARM DELAY
htn
Htn
Electric Defrost Mode
Setpoint
If DEFROST TYPE = ELE: Whether to leave the defrost relay energized during the defrost cycle or to
utilize advanced defrost algorithm.
ind
ind
Defrost Ini Mode
Setpoint
Mode to initiate a defrost: dnd=demand / SCH=Schedule / rnt=comp run time
iP1
iP1
IP Address Part 1
Variables
The first three digits of the IP address
iP2
iP2
IP Address Part 2
Variables
The second three digits of the IP address