Quick Start Guide

dCL

dCL

Door Switch - Door Closed

Auxiliary Input

Door switch indicates door is closed

ddF

ddF

Defrost Delay Fan

System Mode

At defrost, fans will continue running for several minutes, using stored cooling in the coil. Once the 

coil reaches room temp, the fans will stop, and the heaters will turn on and begin the electric defrost.

dEF

dEF

Defr Parameter

Setpoint

if DEFROST MODE = DEMAND: Coefficient to KE2 Defrost algorithm

dEF

dEF

Defrost

System Mode

Controller is performing a defrost cycle

dEr

dEr

Defrost Relay

Variables

Current state of the defrost relay

dFi

dFi

Defrost Interlock Switch

Auxiliary Input

Inactive=Defrost Heaters normal (AUT)/Active=Defrost Heaters Off (OFF)

dFL

dFL

Defrost Lockout Switch

Auxiliary Input

Inactive=Defrost Normal (AUT)/Active=Defrost Not Allowed (dLO)

dhC

dHC

DHCP

Setpoint

Turn DHCP mode on or off: EnA to enable DHCP mode / DiS to disable DHCP mode

diA

diA

Diagnostics Mode

Setpoint

Energizes each relay individually for 60 seconds: fan relay, defrost relay, compressor relay

diS

diS

Disabled

Auxiliary Input

Input is not used by the controller

dLo

dLo

Defrost Lockout 

Auxiliary Input

Active = Defrost not allowed while signal is active

dnd

dnd

Demand Defrost

Setpoint

Option for Defrost Initiation Mode (ind) - when Demand Defrost (dnd) selected, system defrosts only 

when dictated by decrease in evaporator efficiency; other options: Scheduled (SCH) or Compressor 

Run Time (rnt)

don

don

Door Switch - Door Open

Auxiliary Input

Door switch indicates door is open

dor

dor

Door Switch

Auxiliary Input

Inactive=Door Closed (dCL)/Active=Door Open (don)

dor

dor

Door Open Alarm

Alarms

If door is open & room temp is 5 degrees above ROOM TEMP + AIR TEMP DIFF for DOOR ALARM DELAY 

time

dPd

dPd

Defrosts per day

Setpoint

If DEFROST MODE = SCH: The number of evenly spaced defrosts per day the controller will initiate.

drn

drn

Drain Time

Setpoint

Time to be in drain mode (drip time)

drn

drn

Drain

System Mode

Time after defrost to allow moisture to drain from coil

dtL

dtL

Max Defrost Time

Setpoint

If DEFROST MODE = SCH: The maximum amount of time the defrost relay will be energized. (Not avail-

able if DEFROST MODE = DEMAND)

dtP

dtP

Defr Term Temp

Setpoint

Temp the coil sensor(s) must exceed to terminate defrost.  Controller’s defrost mode is complete at 

this point

dtt

dtt

Defr Term on Time Alarm

Alarms

Defrost terminated on time instead of temperature for two consecutive cycles

dty

dtY

Defrost Type

Setpoint

Type of Defrost: ELE - Electric; Ai - off time; HGn - hot gas w.comp on; HGF - hot gas w/comp off

EA1

EA1

External Alarm Switch

Auxiliary Input

Active=EAo / Inactive=EAF

EA1

EA1

External Alarm 1

Alarms

If AU1 IN MODE =  EXT ALARM: The digital input is in an active state

EA2

EA2

External Alarm 2

Alarms

If AU2 IN MODE =  EXT ALARM: The digital input is in an active state

EA3

EA3

External Alarm 3

Alarms

If AU3 IN MODE =  EXT ALARM: The digital input is in an active state

EAo

EA3

External Alarm Switch Active

Auxiliary Input

External Alarm switch is receiving Active signal

EAF

EA3

External Alarm Switch Inactive

Auxiliary Input

External Alarm switch is not receiving external signal

Ed

Ed

Electric Defrost w/Mech. valve

Type of Control

System operates with default values for Electric Defrost with Mechanical Valve

EdE

EdE

Electric Defrost w/EEV

Type of Control

System operates with default values for Electric Defrost with Electric Valve

EdF

EdF

Extreme Temp Diff

Setpoint

ADVANCED TOPIC: Call KE2 Therm for assistance 

EdF

EdF

Excess Defrost Alarm

Alarms

32 defrosts or more within 48 hours

Edt

Edt

Valve Type

Setpoint

Type of valve used on the system: mechanical, pre-configured electric, custom EEV configuration

EFL

EFL

Email Failure Alarm

Alarms

Email alert was not confirmed by email server provided after seven consecutive attempts

ELE

ELE

Electric Defrost  

Setpoint

Option for evaporator Defrost Type (dtY) - Electric defrost heaters used; other options, Hot Gas w 

Compressor Off (HGF), Hot Gas with Compressor On (HGn) or Air Off time Defrost (Ai)

EnA

EnA

Enabled

Setpoint

Enabled - Option to allow connection with KE2 Smart Access 

FAC

FAC

Factory reset

Setpoint

Press and hold to reset the controller to the factory default setpoints

FAh

FAH

Fahrenheit

Setpoint

Option for units for the temperature display, in degrees  -  Fahrenheit or Celsius (CEL)

FAr

FAr

Fan Relay

Variables

Current state of the fan relay

FdL

FdL

Fan Delay

System Mode

Coming out of defrost, the LLS relay will be energized, and the coil will pulldown until it reaches 20ºF, 

or 2 minutes, before the fans turn on. This allows any moisture on the coil to re-freeze, keeping it from 

spraying and forming ice drops on the walk-in’s surfaces.

Fir

Fir

Firmware Version

Variables

Current version of the firmware on the controller

FoC

FoC

Fans on with Compressor

Setpoint

Option under Refrig Fan Type (rFt) to manage fans in OFF, then turn ON in refrigeration

hAd

HAd

High Temp Alarm Delay

Setpoint

Minutes the room temperature must remain above ROOM TEMP + HIGH TEMP ALARM OFFSET before 

issuing a HIGH TEMP ALARM

hAo

HAo

High Temp Alarm Offset

Setpoint

The number of degrees above  ROOM TEMP  for a HIGH TEMP ALARM condition.

hgF

H F

Hot Gas Defrost w. Compressor 

Off  

Setpoint

Option for evaporator Defrost Type (dtY) - Hot Gas defrost used with the Compressor Off; other op-

tions Electric (ELE), Hot Gas w Compressor On (HGN), or Air Off time Defrost (Ai)

hgn

H n

Hot Gas Defrost w. Compressor 

On  

Setpoint

Option for evaporator Defrost Type (dtY) - Hot Gas defrost used with the Compressor On; other op-

tions Electric (ELE), Hot Gas w Compressor Off (HGF), or Air Off time Defrost (Ai)

hS

HS

HSV

Valve Type

KE2 Therm’s HSV, Hybrid Stepper Valve

hSh

HSH

High Superheat Alarm

Alarms

Superheat above upper limit

htA

HtA

High Temperature Alarm

Alarms

Room temperature is above ROOM TEMP  + AIR TEMP DIFF + HIGH TEMP ALARM OFFSET  for longer 

than HIGH TEMP ALARM DELAY

htn

Htn

Electric Defrost Mode

Setpoint

If DEFROST TYPE = ELE:  Whether to leave the defrost relay energized during the defrost cycle or to 

utilize advanced defrost algorithm.

ind

ind

Defrost Ini Mode

Setpoint

Mode to initiate a defrost: dnd=demand / SCH=Schedule / rnt=comp run time

iP1

iP1

IP Address Part 1

Variables

The first three digits of the IP address

iP2

iP2

IP Address Part 2

Variables

The second three digits of the IP address

Alphabetical List of Abbreviations (continued)

Abbreviation Full Name

Type

Description

Содержание EvapOEM

Страница 1: ...t RSV 320 21167 1 2 x 1 2 10 ft RSV 320 21168 1 2 x 1 2 40 ft RSV 400 21529 5 8 x 7 8 15 ft RSV 400 21530 5 8 x 7 8 40 ft RSV 550 21594 5 8 x 7 8 15 ft RSV 550 21595 5 8 x 7 8 40 ft RSV 650 21779 5 8 x 7 8 15 ft RSV 650 21778 5 8 x 7 8 40 ft RSV C10 Stator 21149 For RSV 100 to 320 10 ft RSV C40 Stator 21150 For RSV 100 to 320 40 ft RSV LC15 Stator 21525 For RSV 400 to 650 15 ft RSV LC40 Stator 215...

Страница 2: ...nge Yellow Red Black Empty Red Green White Black EEV A B Shield RS 485 Line L1 Neutral L2 INCOMING POWER Red Black Green PSI NO COM NC NO COM GROUND EARTH GROUND FUSE NO COM L2 Supply Voltage FAN MOTOR FAN MOTOR FAN MOTOR EVAPORATOR FANS HEATER LIMIT SWITCH DEFROST HEATERS LIQUID LINE SOLENOID N C TSC1A250 1A 1A 250V slow blow 5mm x 20mm Q 1 45 May 2019 Page 2 KE2 EvapOEM Quick Start Guide Copyrig...

Страница 3: ...hout KE2 Terminal Board NO COM NO COM NC FAN RELAY COMPRESSOR RELAY DEFROST RELAY COM NO L1 N L2 VOUT MOTOR Aux3 Aux2 Aux1 TCoil TAir TSuc PSI RS 485 HS DEFROST HEATERS FANS S LLS NC N X BLK RED BLK FIELD SUPPLY 1 PHASE ETHERNET DISPLAY BLUE ORANGE YELLOW RED BLACK MOTOR RED GREEN WHITE BLACK EEV EMPTY RSV XDCR A B SHIELD G GRN ORG BLACK GREEN RED ...

Страница 4: ...fins Figure 3b shows the coil sensor properly secured NOTE On a small fraction of installations the sensor placement may require adjusting This is typically caused by product loading door openings air flow etc The sensor s should be placed where the frost disappears last on the coil Extending sensor wires After the sensors are mounted they are routed back to the controller If the wires must be ext...

Страница 5: ...n automatically enter Introduction Mode The Introduction Mode con sists of four Types of Control options Ed Electric Defrost with Mechanical TEV EdE Electric Defrost with Electric Expansion Valve Ad Air Defrost with Mechanical TEV AdE Air Defrost with Electric Expansion Valve Step 1 Using the and arrows moves the user through the avail able Types of Control options Once the preferred option is dis...

Страница 6: ...echanical valve is selected LPd LPd Press Diff for LPCO 1 0 psig 20 0 psig 15 0 psig Pressure Differential for LPCO Displays when LOW PRESSURE CUTOUT TIME LPt is greater than zero And only applies if non mechanical valve is selected rnt rnt comp Run time 0 hrs 24 hrs 6 hrs Compressor Run Time When rnt selected number of hours of cooling before starting defrost Htn Htn ELECTRIC DEFROST MODE N A N A...

Страница 7: ...mum amount of time between de energizing the liquid line solenoid compressor relay and energizing the defrost relay MULTI AIR TEMP CTRL Warmest or Average Warmest Air Warmest air use the warmest air temp from bonded controls Average air use the average air temp from bonded controls MULTI EVAP COOL Synchronized or Independent Synchronized Synchronized synchronize bonded controller in refrigeration ...

Страница 8: ...nd 3 digits of IP address iP3 iP3 IP OCTET 3 Third 3 digits of IP address iP4 iP4 IP OCTET 4 Fourth 3 digits of IP address Fir Fir FIRMWARE VERSION Current Version of firmware on controller System Modes Basic Remote Display KE2 Combo Display Abbreviation ScrollingText rEF rEF REFRIGERATE ddF ddF DEFROST DELAY FAN dEF dEF DEFROST drn drn DRAIN TIME FdL FdL FAN DELAY SoF SoF SYSTEM OFF oFF oFF OFF R...

Страница 9: ...tive if input is an open CLo active if input is shorted A2A a2a AU2 Temp sensor Alarm Alarms AU2 temperature sensor is shorted or open A3A A3A Aux Input 3 state Setpoint oPn active if input is an open CLo active if input is shorted A3A a3a AU3 Temp sensor Alarm Alarms AU3 temperature sensor is shorted or open Ad Ad Air Defrost w Mechanical valve Type of Control System operates with default values ...

Страница 10: ...m Switch Inactive Auxiliary Input External Alarm switch is not receiving external signal Ed Ed Electric Defrost w Mech valve Type of Control System operates with default values for Electric Defrost with Mechanical Valve EdE EdE Electric Defrost w EEV Type of Control System operates with default values for Electric Defrost with Electric Valve EdF EdF Extreme Temp Diff Setpoint ADVANCED TOPIC Call K...

Страница 11: ... Prn rEF rEF Refrigeration System Mode Indicates the system is currently in Refrigeration mode rFG rF Refrigerant Setpoint Type of refrigerant used see table below rFt rFt Refrigeration Fan Type Setpoint Select how fans will be run Manage Cycle Permanent On with Compressor Title 24 rnt rnt Compressor Run Time Setpoint Option for Defrost Initiation Mode ind when Compressor Run Time rnt selected num...

Страница 12: ...ccess akk for a nominal monthly fee No port forwarding No VPN KE2 Smart Access Online Access In 3 Easy Steps Preliminary Connect the KE2 Evap OEM to the customer s network NO NC COM EARTH CAT5 Ethernet Cable 1 2 3 6 5 4 7 Link ACT 100 1000Mbps POWER Customer Network youtube com ke2therm Visit our YouTube channel for videos on KE2 Smart Access Enter default information and click Log In button Site ...

Отзывы: