KE2 Efficiency Скачать руководство пользователя страница 19

Q.1.3 July 2015 

Page 19

Setpoints Menu - STPT

KE2 

Evaporator

Efficiency

Quick Start Guide

Parameter Name

Description

Range

Default

Current 

ROOM TEMP

Walk-in freezer or cooler room temperature to be maintained

-50°F to 90°F

-10°F

DEFROST TYPE

Method of defrost used on the evaporator coil: Electric, Air, Hot Gas with  Liquid Line Solenoid/Compressor relay off, Hot Gas with 

Liquid Line Solenoid/compressor relay on

ELEC, AIR, HOT GAS COMP ON, HOT GAS COMP OFF

ELEC

VALVE TYPE

Type of valve used on the system: mechanical, pre-configured electric, custom EEV configuration

MECHANICAL, KE2 RSV, KE2 HSV, SER/SEI 1 TO 20, SER B TO L, SEI 30, SEI 50, SEH, ETS12 TO 50, 

ETS100, ETS250/400, CAREL, CUSTOM;

MECHANICAL

Cust

om 

EE

V  onl

y

MOTOR TYPE

If VALVE TYPE = CUSTOM: The motor type used in the valve

BIPOLAR, UNIPOLAR

BIPOLAR

MOTOR STEP RATE

If VALVE TYPE = CUSTOM: The motor speed setting in number of steps per second

30 to 400 steps/second

200 steps

MAX VALVE STEPS

If VALVE TYPE = CUSTOM: The total number of steps required to move the valve from closed to fully open

200 to 6400 steps

1600 steps

SUPERHEAT

The superheat value that the controller will  maintain, (not applicable if VALVE TYPE = MECHANICAL)

5°F to 30°F

8°F

MAX OPERATING PRES

The maximum allowable suction pressure, (not applicable if VALVE TYPE = MECHANICAL)

10-500 psig if R-744 selected, 10-300psig if R-410A selected, 10-150 psig all other refrigerants

150 psig

REFRIGERANT

The type of refrigerant used in the refrigeration system

404A, R507, 407A, 407C, 422A, 422D, 134A, R22,  R717, 438A, 408A, 409A, 407F, 410A, R744

404A

AUX TEMP 4 MODE

Configuration  mode of the auxiliary temperature sensor

DISABLED, MONITOR, T4 ROOM TEMP, T4 COIL TEMP

DISABLED

AUX TEMP 1 MODE

Configuration  mode of the auxiliary temperature sensor (Not available if EEV is selected)

T1 SUCTION TEMP, MONITOR, T1 ROOM TEMP, 2ND COIL TEMP

T1 SUCTION

AUX RELAY MODE

Configuration mode of the auxiliary relay.  

ALARM RELAY, 2ND COMP RELAY, 2ND FAN RELAY, 2ND DEFR RELAY, 2 SPEED FAN CTL, LIGHT 

RELAY, PERM DEFROST RELAY

ALARM RELAY

FAN SPEED

Provides 0-10V DC signal to control variable speed

-100% to 100%

0.000 (Off)

MIN COMP RUN TIME

Minimum amount of time the liquid line solenoid/compressor relay must remain on after it is energized

0 to 15 minutes

2 minutes

MIN COMP OFF TIME

Minimum amount of time the liquid line solenoid/compressor relay must remain off before it can be energized again.

0 to 15 minutes

5 minutes

REFRIG FAN MODE

Fan operation while in refrigeration mode

ON WITH COMPRESSOR, PERMANENT, MANAGED, CONTROL FOR TITLE 24

ON WITH COMPRESSOR

DEFROST MODE

The method the controller uses to determine when to initiate a defrost.

DEMAND, SCHEDULED, RUN TIME

DEMAND

DEFROSTS / DAY

If DEFROST MODE = SCHEDULED: The number of evenly spaced defrosts per day the controller will initiate.

0 to 8

5

1ST DEFROST DELAY

If DEFROST MODE = SCHEDULED: The amount of time from controller power up until the first defrost is initiated. 

0 to 240 minutes

120 minutes

DEFROST FAN STATE

Whether or not to run the evaporator fans during defrost

ON/OFF

OFF if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF

ON if DEFROST TYPE = AIR

DEFROST TERM TEMP

The temperature the coil sensor(s) must exceed in order to terminate defrost.  The defrost relay is de-energized at this point.

35°F to 90°F

50°F if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF

40°F if DEFROST TYPE = AIR

DEFROST PARAMETER

if DEFROST MODE = DEMAND: Coefficient to KE2 Defrost algorithm

0 to 90

30 if DEFROST TYPE = ELEC

10 if DEFROST TYPE = HOT GAS COMP ON, HOT GAS COMP OFF

40 if DEFROST TYPE = AIR

MAX DEFROST TIME

If DEFROST MODE = SCHEDULE or RUNTIME: The maximum amount of time the defrost relay will be energized. (Not available if DEFROST MODE = DEMAND)

0 to 90 minutes

45 minutes if DEFROST TYPE = ELEC

10 minutes if DEFROST TYPE = HOT GAS COMP ON, HOT GAS COMP OFF

40 minutes if DEFROST TYPE = AIR

DRAIN TIME

Time to be in drain mode (drip time)

0 to 15 minutes

2 minutes

COMP RUN TIME

If DEFROST MODE = RUN TIME:  The amount of time liquid line solenoid/compressor relay is energized before the next defrost is initiated. 

0 to 24 hours

6 hours

ELEC DEFROST MODE

If DEFROST TYPE = ELEC:  Whether to leave the defrost relay energized during the defrost cycle or to utilize advanced defrost algorithm.

PULSE, PERMANENT

PULSE

FAN DELAY TEMP

After defrost, the coil sensor reading must fall below this temperature set point in order for the controller to resume normal fan operation. 

-40°F to 35°F

20°F

MAX FAN DELAY TIME

Maximum amount of time after defrost to resume normal fan operation.

0 to 20 minutes

2 minutes

PUMP DOWN TIME

Minimum amount of time between de-energizing the liquid line solenoid/compressor relay and energizing the defrost relay.

0 to 90 minutes

0 minutes if DEFROST TYPE = ELEC or AIR, 

2 minutes if DEFROST TYPE = HOT GAS ON/OFF

MULTI AIR TEMP CTRL

Select control method to use with multiple room temperature sensors

AVERAGE, WARMEST

WARMEST

Bonded  Contr

ol

-

lers O

nl

y MULTI EVAP COOL

Select type of multi evaporator control  - options are synchronous or independent

SYNC, INDEPENDENT

SYNC

MULTI EVAP DEFROST

Select whether to have all bonded controllers initiate defrost mode at the same time or independently.

SYNC, INDEPENDENT

SYNC

MULTI EVAP SENSOR

Select whether or not to share room temperature, coil temperature and suction pressure sensor data with bonded controllers.

SHARED, NOT SHARED

SHARED

HIGH TEMP ALARM OFFSET

The number of degrees above  ROOM TEMP  for a HIGH TEMP ALARM condition.

0°F to 99.9°F

10°F

HIGH TEMP ALARM DELAY

Minutes  the room temperature must remain above  ROOM TEMP + HIGH TEMP ALARM OFFSET before issuing a HIGH TEMP ALARM

0 to 120 minutes

60 minutes

LOW TEMP ALARM OFFSET

The number of degrees below  ROOM TEMP  for a LOW TEMP ALARM condition.

0°F to 20°F

4°F

LOW TEMP ALARM DELAY

Minutes the room temperature must remain below  ROOM TEMP - LOW TEMP ALARM OFFSET before issuing a LOW TEMP ALARM

0 to 30 minutes

10 minutes

DOOR ALARM DELAY

If DIG IN (1, 2 and/or 3MODE =  DOOR SWITCH: The amount of time, in minutes, before an alarm condition is initiated if door is open and room 

temperature is 5 degrees above ROOM TEMP + AIR TEMP DIFF

0 to 180 minutes

30 minutes

DIG IN 1 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH,  EXT ALARM, SYSTEM OFF

DOOR SWITCH

DIG IN 1 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

DIG IN 2 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH,  EXT ALARM, SYSTEM OFF, DEFR INTERLOCK, 

DEFR LOCKOUT

DISABLED

DIG IN 2 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

DIG IN 3 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH,  EXT ALARM, SYSTEM OFF, LIGHT SWITCH

SYSTEM OFF

DIG IN 3 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

2ND ROOM TEMP

If DIG IN (1, 2 and/or 3) MODE = 2ND ROOM TEMP: This value becomes the ROOM TEMP setpoint when the digital input is active

-50°F to 90°F

-50°F

SUCT PRES OFFSET

An offset added or subtracted from the suction line pressure transducer reading, if needed

-5.0 to 5.0 psig

0.0 psig

SUCT TEMP OFFSET

An offset added or subtracted from the suction temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

AIR TEMP OFFSET

An offset added or subtracted from the room temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

COIL TEMP OFFSET

An offset added or subtracted from the coil temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

AUX TEMP OFFSET

An offset added or subtracted from the auxiliary temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

TEMP UNITS

Units for temperature’s display in °F or °C

FAHRENHEIT/CELSIUS

FAHRENHEIT

AIR TEMP DIFF

The number of degrees above ROOM TEMP before the controller will go into REFRIGERATION mode

0.1°F to 5°F

1°F

EXTREME TEMP DIFF

ADVANCED TOPIC: Call KE2 Therm for assistance

PROPORTIONAL

A coefficient to the valve control algorithm that increases valve responsiveness

0 to 255

3

INTEGRAL

A coefficient to the valve control algorithm that increases valve responsiveness

0 to 255

5

DERIVATIVE

Should not be adjusted unless instructed by KE2 Therm technical support

0 to 255

3

Содержание Efficiency

Страница 1: ...es outside the space Silicone for sealing any box penetrations Accessories to Aid in Installation The following parts are available separately 10 Wire Harness pn 20736 25 Wire Harness pn 20670 40 Wire Harness pn 20737 KE2 Evap Mounting Box pn 20687 Further information on the Wire Harness and Mounting Box can be found in literature Q 1 21 L M N D E O P F B Left Arrow Right Arrow Use to move between...

Страница 2: ... a defrost Liquid Vapor Mix Restrictor TEV or EEV Warm Liquid ColdVapor HotVapor Warm Air Cold Air Evaporator Compressor Condenser SaturationTemp F from receiver pressure LiquidTemp atValve F Subcooling Suction Pressure PSI SuctionTemp F evaporator outlet SaturationTemp F calculated from Suct Pressure Superheat Temp Difference TD F return air minus coil temp Coldest point in evap F AMPS Trouble Sh...

Страница 3: ...row from these edges towards the center Therefore the sensor location is best situated approximately 1 to 1 1 2 from the outer edges and typically near the bottom 1 3rd portion of the evaporator The sensor needs to be as far away from the defrost heat sources as possible This is most easily located by viewing the current frost pattern The last place frost disappears during the defrost cycle is the...

Страница 4: ...roperly route conduit Determine the number of wires to go to the controller Controller power 3 wires Fan control 2 wires Defrost heater control 2 wires Liquid line solenoid 2 wires If the Aux Relay is used the installer will need to supply an ad ditional pair of wires to the controller Aux relay 2 wires Note Install in accordance with local wiring codes KE2 Therm does not accept responsibility for...

Страница 5: ...cted to the Power In location us ing a 3 position connector Controllerstillilluminatesdisplaywhen120Visappliedwith208 240V selected however controller will not function properly 6 Fan Relay Strip the end of the 2 wires used for fan control Locate 2 female spade connectors in the accessories kit Crimp on the female spade connectors Plug the connectors to the COM and NO positions of the Fan Relay Fa...

Страница 6: ...n ad ditional pair of wires to the controller Strip approx 1 4 wire insulation on end of the 2 wires for the alarm Locate a 3 position connector from the accessories kit Plug into the location as indicated in Wiring Schematic Max relay rating is 3A 11 11 Preparing the Evaporator The evaporator wiring will require access to the high voltage termi nal block on the coil Turn off power to the system V...

Страница 7: ...us power to the controller Attach ground wire Note Ground is required for the inter nal safeties to operate properly 16 Evaporator wiring Fans Strip the ends of the wires con nected to the KE2 Evap used to con trol the evaporator fans The fan wires can be attached to the terminal block using either screw down terminals or spade connectors Attach one of wires to the L1 Line This wire will be connec...

Страница 8: ...enoid Compressor relay to one of the solenoid leads Attach the wire from the COM on the L L Solenoid Compressor relay to the L1 Line Voltage Connect L2 Neutral to the remain ing L L Solenoid Compressor lead 20 Remove defrost termination Klixon from circuitry Attach one of wires to the L1 Line This wire will be connected to COM of defrost relay on the controller Attach the wire connected to the NO ...

Страница 9: ...y 2015 Page 9 KE2 EvaporatorEfficiency Quick Start Guide Copyright 2015 KE2 Therm Solutions Inc Washington Missouri 63090 Wiring Schematic Controller New Installation Wiring Schematic Controller New Installation ...

Страница 10: ...7 54 Amps 52 Amps 52 Amps 20218 68 Amps 65 Amps 62 Amps 20219 80 Amps 77 Amps 62 Amps L egend EFM Evaporator Fan Motor DH Defrost Header LLS Liquid Line Solenoid AUX Auxiliary PT Pressure Transducer T1 SUCTION Suction Temperature T2 AIR Return Air Temperature T3 COIL Evaporator Coil Temperature T4 AUX Auxiliary Temperature EEV Electric Expansion Valve ECM Electronically Commutated Motor D1 Digital...

Страница 11: ...e the best place to install the sensor The sensor should be located between 8 10 inches away from the face of the evaporator This distance prevents the sensor from sensing heat from the heating elements during the defrost cycle but close enough to accurately sense the return air temperature The sensor bracket may be bent as necessary to locate the sensor in the proper position WARNING Do not allow...

Страница 12: ... to the electric heating elements It should be about half the distance between the heat ers if possible In Figure 25B the probe is inserted into the fins ap proximately 1 16 deeper than the stainless shielding Pinch the fins gently together securing the sensor in place This provides thermal ballast to ensure a complete defrost 25 26 Connecting sensor wires to controller The temperature sensors are...

Страница 13: ... Range 0 to 150 psia Proof Pressure 450 psi Burst Pressure 1500 psi OperatingTemp 40 to 275 F Temperature Sensor Sensor Specs 60 to 150 F moisture resistant package 208 240 120 120 Temperature Sensors Pressure Transducer T1Suct T4Aux T2Air T3Coil line L1 ground neutral L2 NC NO NO NC NO NC COM COM NC Power In green red black NO Transformer 3A Relay 3A Relay COM COM COM NC NO COM NC NO 18V DI 1 DI ...

Страница 14: ...e generally correct for most applications 3 The Setpoint parameters shown in ITALIC are only displayed when a Custom EEV is used 4 Displayed when an EEV is used 5 Only available if mechanical valve is selected When using an electric valve the default suction temperature is required 6 The Setpoint parameters shown in BOLD ITALIC are used for bonded controllers only 7 Only displayed when Run Time De...

Страница 15: ...u the left and right arrows will move to the main screen or the adjacent menu The up and down arrows move the user through the available op tions for each group All users are allowed access to the variable alarms All other information is password protected to prevent unau thorized access to the controller s functionality The ENTER button is used to save an input option when it has been changed The...

Страница 16: ...b portal And Smart Access provides a customized dashboard of all the controllers on that network on one page Preliminary Connect the KE2 Evap to the customer s network CAT5 Ethernet Cable KE2 EvaporatorEfficiency TM thermsolutions ENTER BACK 2 2 1 2 3 6 5 4 7 Link ACT 100 1000Mbps POWER Customer Network Screen shot of a single KE2 Evap connected through Smart Access Screen shots of Smart Access da...

Страница 17: ...n the Introduction Mode menu After setting the Room Temp Defrost Type and Valve Type set Smart Access to Enabled Use the or arrow to change Smart Access to Enabled Press and hold the ENTER button for 3 seconds to save the change Note if using a Defined EEV Refrigerant must be selected too Note if using a Custom EEV Refrigerant Motor Type Motor Step Rate and Max Valve Steps must be selected Introdu...

Страница 18: ...ure set point in order for the controller to resume normal fan operation MAX FAN DELAY TIME Maximum amount of time after defrost to resume normal fan operation PUMP DOWN TIME Minimum amount of time between de energizing the liquid line solenoid compressor relay and energizing the defrost relay MULTI AIR TEMP CTRL Select control method to use with multiple room temperature sensors Bonded Control le...

Страница 19: ...f DEFROST TYPE AIR 35 F to 90 F 50 F if DEFROST TYPE ELEC HOT GAS COMP ON HOT GAS COMP OFF 40 F if DEFROST TYPE AIR 0 to 90 30 if DEFROST TYPE ELEC 10 if DEFROST TYPE HOT GAS COMP ON HOT GAS COMP OFF 40 if DEFROST TYPE AIR 0 to 90 minutes 45 minutes if DEFROST TYPE ELEC 10 minutes if DEFROST TYPE HOT GAS COMP ON HOT GAS COMP OFF 40 minutes if DEFROST TYPE AIR 0 to 15 minutes 2 minutes 0 to 24 hour...

Страница 20: ...ller to the factory default setpoints RESET WEB PASSWORD RESET Reset the web password to the factory default RESET SMART ACCESS Turn Smart Access on or off DISABLE ENABLE DISABLE DHCP Turn DHCP mode on or off DISABLE ENABLE DISABLE DOD INIT Re initialize KE2 defrost algorithm RESET CLEAR MD NO LONGER USED HOLD TO CLEAR MD Parameter Name Description ROOM TEMP Walk in freezer or cooler room temperat...

Отзывы: