KE2 21710 Скачать руководство пользователя страница 10

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.43 April 2018 

Page 10

KE2 Compressor 

Sequencer

Quick Start Guide

When applying the controller to a system consisting of fixed speed 

compressors with or without unloading capabilities, the controller 

requires the user to assign a relay output for each compressor stage 

available using the controller’s web pages. (Maximum Stages – 5)

Once the controller setup is completed through the controller’s Mas-

ter View web pages, it is ready to turn the System On, or allow Re-

frigeration, by either clicking the yellow System is Off button on the 

Setpoints web page, or using the Manual Menu -> Manual Control 

option.

When Fixed Suction Pressure and Fixed Speed Compressors are se-

lected the controller will use the compressor capacity in HP as defined 

on the Setpoints Page. Stages will be loaded and unloaded based on 

the smallest step available. If all available stages are equal the con-

troller will automatically select the option with the least amount of 

runtime. 

The Suction Pressure Setpoint will serve as the target pressure the 

controller works to achieve while in Refrigeration. The Suction Pres-

sure Differential determines the pressure above and below the Suc-

tion Pressure Setpoint the controller will allow the suction pressure 

to vary before it makes an adjustment to the compressor capacity. 

Once a stage has been loaded or unloaded that stage must remain on 

or off as determined by the Min Comp Runtime and Min Comp Off-

time. Stages of capacity will be made as necessary by the controller, 

however, it will not load or unload more often than the time defined 

in the Min Compressor Switch Time.

If the system is maintaining the suction pressure within the normal 

operating range, which is defined as the Suction Pressure Setpoint 

+/- the Suction Pressure Differential it will maintain the current 

capacity. 

Mode of Control:

Fixed Suction Pressure & Fixed 

Speed Compressors 

Determining Compressor ON / OFF Order

Mode of Control:

Fixed Suction Pressure with 

Digital Scroll Compressors 

When applying the controller to a system consisting of fixed speed 

compressors with or without unloading capabilities and one digital 

scroll, the controller requires the user to assign a relay output for each 

compressor stage available using the controller’s web pages.

Once the controller setup has been completed through the control-

ler’s Master View web pages, it is ready to turn the System On, or al-

low Refrigeration, by either clicking the yellow System is Off button 

on the Setpoints web page, or using the Manual Menu -> Manual 

Control option.

The Digital Scroll will serve as the primary stage to provide the most 

consistent suction pressure possible. Initially the compressor will be 

started unloaded. 

If the pressure rises above the Suction Pressure Setpoint plus the 

Suction Pressure Differential the Digital Scroll will be loaded by en-

ergizing the solenoid.

If the pressure falls below the Suction Pressure Setpoint minus the 

Suction Pressure Differential it will energize the solenoid to unload 

the compressor. If the low pressure is maintained the main digital 

scroll’s compressor relay will be de-energized if the Min Comp Run-

time has been met. *

If the Digital Scroll is fully loaded and the pressure exceeds the Suc-

tion Pressure Setpoint plus the Differential the next stage will be 

loaded based on the smallest step available. If all available stages are 

equal, the controller will automatically select the option with the least 

amount of runtime. The compressors will continue to be loaded until 

all compressors are running. 

If the pressure falls below Suction Pressure Setpoint minus the Suc-

tion Pressure Differential the controller will first unload the Digital 

Scroll. The pressure will primarily be controlled by loading and un-

loading the Digital Scroll. 

If that is not sufficient to bring the pressure within the normal operat-

ing range, the controller will de-energize the smallest stage, or if all 

available stages are equal, the controller will automatically select the 

option with the most amount of runtime.

*The Digital Scroll’s requirements for unloading follow its own ruleset 

that is not adjustable. It has been designed to be within the limits of the 

compressor manufacturer, and to ensure that specification is maintained 

the minimum times for transitioning are not adjustable. 

Содержание 21710

Страница 1: ...KE2 Compressor Se quencer can limit the amount of defrost load as dictated by the site s electrical requirements Part Numbers Controllers Accessories Part Number Description KE2 Compressor Sequencer 2...

Страница 2: ...SH 0 150 psia pressure transducer for suction header T1 Suction 50 to 150 F Tempera ture sensor for suction header T2 Air Optional 50 to 150 F tempera ture sensor for space temperature Allows floating...

Страница 3: ...ntroller wired and ready Superheat 0 0 F Suct Pressure 96 2 F Suct Temp 87 7 F Computer Tablet or Smart Phone Option A Option B Option C NOTE Computer requires Static IP See bulletin Q 5 11 This will...

Страница 4: ...Superheat Superheat as calculated by the controller T1 Suction Temp Suction temperature as measured by the controller Saturation temp Saturation temperature as calculated by the controller Only one of...

Страница 5: ...nloader for Cmp 3 Unloader for Cmp 4 Disabled Only one digital compressor Digital Comp ON OFF requires a solid state relay Comp HP per relay labels the HP of each compressor 0 1 to 50 HP None Defrost...

Страница 6: ...Max Disch Pres Turns system of when exceeded 100 to 500 psig 450 psig Min Suction SH The lowest acceptable superheat Turns system off when exceeded 5 to 50 F 2 8 to 27 8K 15 F 8 3K Max Suction SH The...

Страница 7: ...aximumDischarge Pressure Delay All stages will be turned off The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the Settings page...

Страница 8: ...luminated The controller will scroll High Superheat across the front panel High Discharge Pressure If the discharge pressure is above the Max Disch Pres Maximum Discharge Pressure for longer than the...

Страница 9: ...e superheat reading is main taining above the Min Safety Suction Superheat the alarm will be cleared The controller will send a notification to the email address or phone number provided in the Addres...

Страница 10: ...r to a system consisting of fixed speed compressors with or without unloading capabilities and one digital scroll the controller requires the user to assign a relay output for each compressor stage av...

Страница 11: ...be sent If multiple digital inputs are selected for compressor module any compressor module input will control in manner described above Compressor Module If the Digital Input receives an Inactive si...

Страница 12: ...ENTER for 3 seconds to save change To change settings To save setting changes To move through controller menus To return to Main Menu Indicator lights Red light critical alarm system is not running Am...

Страница 13: ...splays number of users currently viewing this specific controller s webpage System alarms and messages are displayed DESCRIPTION Displays real time system information and shows the interaction of mult...

Страница 14: ...tions Customer information is displayed Use to customize the User Name and Password from the default setting The KE2 Smart Access Settings are provided by KE2 Therm and are only needed when using KE2...

Страница 15: ...d must be provided The default User Name ke2admin The default Password ke2admin For security reasons the User Name and Password should be changed from the default Once you are logged in go to the Sett...

Страница 16: ...ld also be changed Network settings may be changed to match customer s environment IP address is Enabled or Disabled Enabled if selected IP is Dynamic Disabled if selected IP is Static Prevents unauth...

Страница 17: ...Comp 5 Relay 2 5 Dropdown Options All Relay Options the same as Relay 1 except the list of Unloaders for the compressor never includes the active compressor R 404A R 507 R 407A R 407C R 422A R 422D R...

Страница 18: ...p to 49 members All mem bers must be in the same network i e a router divides a network The SiteView may be organized by logging into the controller Air Electric Hot Gas DESCRIPTION SiteView provides...

Страница 19: ...le Date and Time are pulled from the connected computer 5 460 Day Capacity Load and Suction Pressure are displayed when moving the mouse over the data Days ago DESCRIPTION The Graphing Snapshot shows...

Страница 20: ...ile the KE2 Compressor Sequencer s free connectiv ity is still available KE2 Therm recognizes that some customers prefer the simplicity and convenience of KE2 Smart Access to enjoy the benefits of the...

Отзывы: