background image

Q.1.3 November 2017 

Page 19

Setpoints Menu

KE2 

Evaporator

Efficiency

Quick Start Guide

Parameter Name

Description

Range

Default

Parameter Name

ROOM TEMP

Walk-in freezer or cooler room temperature to be maintained

-50°F to 90°F

-10°F

ROOM TEMP

DEFROST TYPE

Method of defrost used on the evaporator coil: Electric, Air, Hot Gas with  Liquid Line Solenoid/Compressor relay off, Hot Gas with 

Liquid Line Solenoid/compressor relay on

ELEC, AIR, HOT GAS COMP ON, HOT GAS COMP OFF

ELEC

DEFROST TYPE

VALVE TYPE

Type of valve used on the system: mechanical, pre-configured electric, custom EEV configuration

MECHANICAL, KE2 RSV, KE2 HSV, SER/SEI 1 TO 20, SER B TO L, SEI 30, SEI 50, SEH, ETS12 TO 50, 

ETS100, ETS250/400, CAREL, CUSTOM;

MECHANICAL

VALVE TYPE

Cust

om 

EE

V  onl

y

MOTOR TYPE

If VALVE TYPE = CUSTOM: The motor type used in the valve

BIPOLAR, UNIPOLAR

BIPOLAR

MOTOR TYPE

MOTOR STEP RATE

If VALVE TYPE = CUSTOM: The motor speed setting in number of steps per second

30 to 400 steps/second

200 steps

MOTOR STEP RATE

MAX VALVE STEPS

If VALVE TYPE = CUSTOM: The total number of steps required to move the valve from closed to fully open

200 to 6400 steps

1600 steps

MAX VALVE STEPS

SUPERHEAT

The superheat value that the controller will  maintain, (not applicable if VALVE TYPE = MECHANICAL)

5°F to 30°F

8°F

SUPERHEAT

MAX OPERATING PRES

The maximum allowable suction pressure, (not applicable if VALVE TYPE = MECHANICAL)

10-500 psig if R-744 selected, 10-300psig if R-410A selected, 10-150 psig all other refrigerants

150 psig

MAX OPERATING PRES

REFRIGERANT

The type of refrigerant used in the refrigeration system

404A, R507, 407A, 407C, 422A, 422D, 134A, R22,  R717, 438A, 408A, 409A, 407F, 410A, 448A, 

449A, 450A, 513A, R744

404A

REFRIGERANT

AUX TEMP 4 MODE

Configuration  mode of the auxiliary temperature sensor

DISABLED, MONITOR, T4 ROOM TEMP, T4 COIL TEMP

T4 COIL TEMP

AUX TEMP 4 MODE

AUX TEMP 1 MODE

Configuration  mode of the auxiliary temperature sensor (Not available if EEV is selected)

T1 SUCTION TEMP, MONITOR, T1 ROOM TEMP, 2ND COIL TEMP

T1 SUCTION

AUX TEMP 1 MODE

AUX RELAY MODE

Configuration mode of the auxiliary relay.  

ALARM RELAY, 2ND COMP RELAY, 2ND FAN RELAY, 2ND DEFR RELAY, 2 SPEED FAN CTL, LIGHT 

RELAY, PERM DEFROST RELAY

ALARM RELAY

AUX RELAY MODE

FAN SPEED

Provides 0-10V DC signal to control variable speed

-100% to 100%

0.000 (Off)

FAN SPEED

MIN COMP RUN TIME

Minimum amount of time the liquid line solenoid/compressor relay must remain on after it is energized

0 to 15 minutes

2 minutes

MIN COMP RUN TIME

MIN COMP OFF TIME

Minimum amount of time the liquid line solenoid/compressor relay must remain off before it can be energized again.

0 to 15 minutes

5 minutes

MIN COMP OFF TIME

REFRIG FAN MODE

Fan operation while in refrigeration mode

ON WITH COMPRESSOR, PERMANENT, MANAGED, CONTROL FOR TITLE 24

ON WITH COMPRESSOR

REFRIG FAN MODE

DEFROST MODE

The method the controller uses to determine when to initiate a defrost.

DEMAND, SCHEDULED, RUN TIME

DEMAND

DEFROST MODE

DEFROSTS / DAY

If DEFROST MODE = SCHEDULED: The number of evenly spaced defrosts per day the controller will initiate.

0 to 8

5

DEFROSTS / DAY

1ST DEFROST DELAY

If DEFROST MODE = SCHEDULED: The amount of time from controller power up until the first defrost is initiated. 

0 to 240 minutes

120 minutes

1ST DEFROST DELAY

DEFROST FAN STATE

Whether or not to run the evaporator fans during defrost

ON/OFF

OFF if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS 

COMP OFF

ON if DEFROST TYPE = AIR

DEFROST FAN STATE

DEFROST TERM TEMP

The temperature the coil sensor(s) must exceed in order to terminate defrost.  The controller’s defrost mode is complete at this point.

35°F to 90°F

50°F if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS 

COMP OFF

40°F if DEFROST TYPE = AIR

DEFROST TERM TEMP

DEFROST PARAMETER

if DEFROST MODE = DEMAND: Coefficient to KE2 Defrost algorithm

0 to 90

30 if DEFROST TYPE = ELEC

10 if DEFROST TYPE = HOT GAS COMP ON, HOT GAS COMP OFF

40 if DEFROST TYPE = AIR

DEFROST PARAMETER

MAX DEFROST TIME

If DEFROST MODE = SCHEDULE or RUNTIME: The maximum amount of time the defrost relay will be energized. (Not available if DEFROST MODE = DEMAND)

0 to 90 minutes

45 minutes if DEFROST TYPE = ELEC

10 minutes if DEFROST TYPE = HOT GAS COMP ON, HOT GAS 

COMP OFF

40 minutes if DEFROST TYPE = AIR

MAX DEFROST TIME

DRAIN TIME

Time to be in drain mode (drip time)

0 to 15 minutes

2 minutes

DRAIN TIME

COMP RUN TIME

If DEFROST MODE = RUN TIME:  The amount of time liquid line solenoid/compressor relay is energized before the next defrost is initiated. 

0 to 24 hours

6 hours

COMP RUN TIME

ELEC DEFROST MODE

If DEFROST TYPE = ELEC:  Whether to leave the defrost relay energized during the defrost cycle or to utilize advanced defrost algorithm.

PULSE, PERMANENT

PULSE

ELEC DEFROST MODE

FAN DELAY TEMP

After defrost, the coil sensor reading must fall below this temperature set point in order for the controller to resume normal fan operation. 

-40°F to 35°F

20°F

FAN DELAY TEMP

MAX FAN DELAY TIME

Maximum amount of time after defrost to resume normal fan operation.

0 to 20 minutes

2 minutes

MAX FAN DELAY TIME

PUMP DOWN TIME

Minimum amount of time between de-energizing the liquid line solenoid/compressor relay and energizing the defrost relay.

0 to 90 minutes

0 minutes if DEFROST TYPE = ELEC or AIR, 

2 minutes if DEFROST TYPE = HOT GAS ON/OFF

PUMP DOWN TIME

MULTI AIR TEMP CTRL

Select control method to use with multiple room temperature sensors

AVERAGE, WARMEST

WARMEST

MULTI AIR TEMP CTRL

Bonded  Contr

ol

-

lers O

nl

y MULTI EVAP COOL

Select type of multi evaporator control  - options are synchronous or independent

SYNC, INDEPENDENT

SYNC

MULTI EVAP COOL

MULTI EVAP DEFROST

Select whether to have all bonded controllers initiate defrost mode at the same time or independently.

SYNC, INDEPENDENT

SYNC

MULTI EVAP DEFROST

MULTI EVAP SENSOR

Select whether or not to share room temperature, coil temperature and suction pressure sensor data with bonded controllers.

SHARED, NOT SHARED

SHARED

MULTI EVAP SENSOR

HIGH TEMP ALARM OFFSET The number of degrees above  ROOM TEMP  for a HIGH TEMP ALARM condition.

0°F to 99.9°F

10°F

HIGH TEMP ALARM OFFSET

HIGH TEMP ALARM DELAY

Minutes  the room temperature must remain above  ROOM TEMP + HIGH TEMP ALARM OFFSET before issuing a HIGH TEMP ALARM

0 to 120 minutes

60 minutes

HIGH TEMP ALARM DELAY

LOW TEMP ALARM OFFSET The number of degrees below  ROOM TEMP  for a LOW TEMP ALARM condition.

0°F to 20°F

4°F

LOW TEMP ALARM OFFSET

LOW TEMP ALARM DELAY

Minutes the room temperature must remain below  ROOM TEMP - LOW TEMP ALARM OFFSET before issuing a LOW TEMP ALARM

0 to 30 minutes

10 minutes

LOW TEMP ALARM DELAY

DOOR ALARM DELAY

If DIG IN (1, 2 and/or 3MODE =  DOOR SWITCH: The amount of time, in minutes, before an alarm condition is initiated if door is open and room 

temperature is 5 degrees above ROOM TEMP + AIR TEMP DIFF

0 to 180 minutes

30 minutes

DOOR ALARM DELAY

DIG IN 1 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH,  EXT ALARM, SYSTEM OFF

DOOR SWITCH

DIG IN 1 MODE

DIG IN 1 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

DIG IN 1 STATE

DIG IN 2 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH,  EXT ALARM, SYSTEM OFF, DEFR INTERLOCK, 

DEFR LOCKOUT

DISABLED

DIG IN 2 MODE

DIG IN 2 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

DIG IN 2 STATE

DIG IN 3 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH,  EXT ALARM, SYSTEM OFF, LIGHT SWITCH

SYSTEM OFF

DIG IN 3 MODE

DIG IN 3 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

DIG IN 3 STATE

2ND ROOM TEMP

If DIG IN (1, 2 and/or 3) MODE = 2ND ROOM TEMP: This value becomes the ROOM TEMP setpoint when the digital input is active

-50°F to 90°F

-50°F

2ND ROOM TEMP

SUCT PRES OFFSET

An offset added or subtracted from the suction line pressure transducer reading, if needed

-5.0 to 5.0 psig

0.0 psig

SUCT PRES OFFSET

SUCT TEMP OFFSET

An offset added or subtracted from the suction temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

SUCT TEMP OFFSET

AIR TEMP OFFSET

An offset added or subtracted from the room temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

AIR TEMP OFFSET

COIL TEMP OFFSET

An offset added or subtracted from the coil temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

COIL TEMP OFFSET

AUX TEMP OFFSET

An offset added or subtracted from the auxiliary temperature sensor reading, if needed

-5.0°F to 5.0°F

0.0°F

AUX TEMP OFFSET

TEMP UNITS

Units for temperature’s display in °F or °C

FAHRENHEIT/CELSIUS

FAHRENHEIT

TEMP UNITS

AIR TEMP DIFF

The number of degrees above ROOM TEMP before the controller will go into REFRIGERATION mode

0.1°F to 5°F

1°F

AIR TEMP DIFF

EXTREME TEMP DIFF

ADVANCED TOPIC: Call KE2 Therm for assistance

EXTREME TEMP DIFF

PROPORTIONAL

A coefficient to the valve control algorithm that increases valve responsiveness

0 to 255

3

PROPORTIONAL

INTEGRAL

A coefficient to the valve control algorithm that increases valve responsiveness

0 to 255

5

INTEGRAL

DERIVATIVE

Should not be adjusted unless instructed by KE2 Therm technical support

0 to 255

3

DERIVATIVE

Содержание 20844

Страница 1: ...KE2 Condensed Catalog 411 This reference should remain on site with the installed KE2 Evaporator Efficiency controller A C D E F G H I J K L M N B O P 20844 KE2 Ultimate Install kit includes KE2 Mount...

Страница 2: ...not recently performed a defrost look for the heaviest area of frost This will be used to locate the coil sensor Installers should account for a full system diagnostic in the installation esti mate f...

Страница 3: ...should be labeled with a matching number This will save time when wiring the evaporator 3 Determine the current draw of the unit Use the nameplate to determine the Amp rating of the unit and select th...

Страница 4: ...GE wires are used for the HEATER control Locate the orange wire with black stripe and black wire with orange stripe Plug the black wire with orange stripe into the COM terminal Plug the orange wire wi...

Страница 5: ...ay USING KE2 Wire Harness The YELLOW wires are used for Liquid Line Solenoid control Locate a 3 position pluggable connector from the parts kit Fasten the black wire with yellow stripe into the COM po...

Страница 6: ...otection for controller components The instructions below are based on the use of this board Determine the location of the following incoming power fan leads heater leads defrost termination leads and...

Страница 7: ...ct L2 NEUTRAL to the remain ing HEATERS terminal as shown using the HEATER LIMIT SWITCH or jumper The defrost safety should not be removed from the circuit Its purpose is to prevent the heaters from o...

Страница 8: ...2 COM NC NO COM NC N0 Auxiliary Relay Yellow with black stripe 16 AWG Black with yellow stripe L1 16 AWG Blue with black stripe 12 AWG Black with blue stripe L1 12 AWG LLS Compressor Fans Black with w...

Страница 9: ...4 Amps 52 Amps 52 Amps 20218 68 Amps 65 Amps 62 Amps 20219 80 Amps 77 Amps 62 Amps L egend EFM Evaporator Fan Motor DH Defrost Header LLS Liquid Line Solenoid AUX Auxiliary PT Pressure Transducer T1 S...

Страница 10: ...active coil surface The ice tends to grow from these edges towards the center Therefore the sensor location is best situated approximately 1 to 1 1 2 from the outer edges and typically near the bottom...

Страница 11: ...the evaporator WARNING Do not allow the metal portion of the air sensor to touch any thing other than air It should not touch the bracket nylon cable tie or any other solid surface 26 Evaporator wirin...

Страница 12: ...T function in the SETPOINTS menu Page 18 When running the wires back to the controller take care to avoid introduc ing electrical noise into the sensor wires Electrical noise can be introduced when se...

Страница 13: ...0 to 275 F 40 C to 135 C Temperature Sensor 3 pack pn 21151 15 ft leads or pn 21066 40 ft leads Sensor Specs 60 to 150 F 51 C to 65 C moisture resistant package 208 240 120 120 Temperature Sensors Pre...

Страница 14: ...displayed only when a Custom EEV is used 4 Displayed when an EEV is used 5 Only available if mechanical valve is selected When using an electric valve the default suction temperature is required 6 Th...

Страница 15: ...d alarms menu columns All other information is password protected to prevent unauthor ized access to the controller s functionality The ENTER button is used to save an input option when it has been ch...

Страница 16: ...onnect the KE2 Evap to the customer s network CAT5 Ethernet Cable 1 2 3 6 5 4 7 Link ACT 100 1000Mbps POWER Customer Network thermsolutions ENTER BACK Efficiency Evaporator Press and hold for manual d...

Страница 17: ...tion Mode menu After setting the Room Temp Defrost Type and Valve Type set KE2 Smart Access to Enabled Use the or arrow to change KE2 Smart Access to Enabled Press and hold the ENTER button for 3 sec...

Страница 18: ...ature set point in order for the controller to resume normal fan operation MAX FAN DELAY TIME Maximum amount of time after defrost to resume normal fan operation PUMP DOWN TIME Minimum amount of time...

Страница 19: ...EMP 0 to 90 30 if DEFROST TYPE ELEC 10 if DEFROST TYPE HOT GAS COMP ON HOT GAS COMP OFF 40 if DEFROST TYPE AIR Defrost parameter 0 to 90 minutes 45 minutes if DEFROST TYPE ELEC 10 minutes if DEFROST T...

Страница 20: ...AUTO FACTORY RESET Reset the controller to the factory default setpoints RESET WEB PASSWORD RESET Reset the web password to the factory default RESET KE2 Smart Access Turn KE2 Smart Access on or off D...

Отзывы: