Ke Kelit SELTRON PROMATIC CMP25-2 Скачать руководство пользователя страница 31

34

 

Service settings manual 

Para-

meter

 

Function 

Parameter description 

Setting 

range 

Default value 

S2.4 PUMP 

OPERATION 

MODE 

Setting of pump operation mode. Settings have the following 

meaning: 

1 - STAND. (circulation pump of mixing circuit - regular) 

2 - P1 (operation according to time program P1= OFF)  

3 - P2 (operation according to time program P2= OFF) 

4 - P3 (operation according to time program P3= OFF)  

5 - P4 (operation according to time program P4= OFF) 

6 - SEL. PROG. (operation according to selected time program) 

1 - STAND. 

2- P1=OFF 

3- P2=OFF 

4- P3=OFF 

5- P4=OFF 

6 - SEL.

     PROG. 

S2.5 MINIMUM 

STAND-PIPE 

TEMPERATURE 

Setting of minimum stand-pipe temperature limitation. 

10 ÷ 90 °C 

20 

S2.6 MAXIMUM 

STAND-PIPE 

TEMPERATURE 

Setting of maximum stand-pipe temperature limitation. 

20 ÷ 150 °C 

45 - 

floor

 

85 - 

radiator

 

S2.7  DEAD ZONE OF MIXING 

VALVE CONTROL 

Setting of stand-pipe temperature span in which mixing valve 

control is in stand-by. 

0,4 ÷ 3,0 K 

S2.8  MIXING VALVE P - CON-

STANT 

Setting of mixing valve position correction intensity.  Smaller 

value means shorter movements, higher value means longer 

movements,  

0,5 ÷ 2,0 

S2.9 MIXING 

VALVE 

 

I - CONSTANT 

Setting of mixing valve control frequency - how often mixing 

valve position is being controlled. Smaller value means low 

frequency, higher value means higher frequency. 

0,4 ÷ 2,5 

S2.10 MIXING 

VALVE 

 

D - CONSTANT  

Sensitivity of mixing valve for stand-pipe temperature changes.  

Smaller value means low sensitivity, higher value means high 

sensitivity.  

0,4 ÷ 2,5 

S2.11 MINIMUM 

STAND-PIPE 

TEMPERATURE FOR 

COOLING 

Setting of minimum stand-pipe temperature in cooling mode. 

CAUTION! Too low stand-pipe temperature can cause dewing 

of heating bodies and pipelines. 

10  ÷ 20 °C 

15 

S2.12 HEATING-OFF 

TEMPE-

RATURE SHIFT 

Shift of calculated stand-pipe temperature for heating switch-off.  -10 ÷ 10 K 

S2.13 LIMITATION 

OF 

TEMP. 

DIFFERENCE BETWEEN 

STAND AND RETURN 

PIPE 

Setting of maximal difference between stand-pipe and return-

pipe temperature. Limiting the highest power of heating 

system . 

3 ÷ 30  K 

10 

S2.14 CONSTANT 

STAND-PIPE 

TEMPERATURE 

Selection of operation with constant stand-pipe temperature. 

Setting range is 10 ÷ 140 °C. 

This function deactivates weather compensated control of 

mixing valve.  

0 - NO 

1 - YES 

S2.15 CIRCULATION 

PUMP 

SWITCH-OFF DELAY 

(MINUTES) 

Setting of delayed circulation pump switch-off when there is no 

requirement for heating. 

0 ÷ 10 min 

S2.3  INFLUENCE OF DD2+ 

ROOM SENSOR 

Set whether the room unit influences  the controller operation. 

# 1 only the sensor from the first room unit has influence 

# 2 only the sensor from the second room unit has influence 

# 1 & 2  sensor from the both room units have influence 

AUTO sensors from the room unit which controll the heating  

   circuit have influence 

1- AUTO 

2- #1

3- #2 

4- #1&2 

5- NO

Содержание SELTRON PROMATIC CMP25-2

Страница 1: ...PROMATIC CMP25 2 Weather compensated controller for mixing heating circuits...

Страница 2: ...g circuit with radiator or surface heating systems CMP25 2 features multi chanel program timer for time dependent room heating CMP25 2 controllers can be connected to network and operate as uniform co...

Страница 3: ...rview 12 Symbols for protection functions 13 Symbols for communication of controllers in network 13 Symbols for notice and warnings 13 Basic screen navigation 14 Locking unlocking the screen 14 Displa...

Страница 4: ...ors room units and BUS 39 Connection of digital room unit DD2 40 Connection of room sensor 40 Marking and installation of temperature sensors 41 Operation mode by sensor failure 42 Expanding the syste...

Страница 5: ...MANUAL CONTROLLER DESCRIPTION OPERATION MODE INDICATION CONTROLLER APPEARANCE 1 2 Graphic display with touch panel Button Esc Help Illuminated button green closing of mixing valve red opening of mixin...

Страница 6: ...own Next the setup wizard runs PROCEDURE OF INITAL SETUP On screen appears picture for selecting the display orientation Press icon where letter A is normally readable After selecting proper display o...

Страница 7: ...LANGUAGE SELECTION Select scheme for controller operation Confirm your selection with button STEP 4 HYDRAULIC SCHEME Selected hydraulic scheme screen orientation direction rotation direction and langu...

Страница 8: ...unit Temperature overview Screen unlocking Key Esc Time and date Screen unlocking Indication of mixing valve and pump operation Notifications and warnings SYMBOLS FOR OPERATION MODE DESCRIPTION OF SY...

Страница 9: ...culated or set point temperature Indoor Room temperature Outdoor temperature Stand pipe temperature Return pipe temperature Boiler temperature Mixing valve closing flashing indicates trend for closing...

Страница 10: ...AND WARNINGS Symbol Description Notice In case of exceeding the maximum temperature or activation of protection function the controller indicates the event with flashing symbol on the display If the...

Страница 11: ...sing decreasing the data value Confirmation Confirmation and return to the previous menu or selection If you want to change the controller settings or overview the operation data Press the button to u...

Страница 12: ...for help notices and warnings is opened Short manual Short manual for use of the controller Controller version Overview of controller type and software version Notices List of exceeding the maximum t...

Страница 13: ...of selections press button to move on the next screen or button to move to the previous screen To unlock the screen press button To enter the menu press button ENTRY AND NAVIGATION THROUGH THE MENU To...

Страница 14: ...NCTIONS Party Eco Holiday Deactivation of function OPERATION MODE Time program operation mode Day temperature operation mode Night temperature operation mode Switch OFF Heating or cooling operation mo...

Страница 15: ...nation Intensity of inactive display illumination Contrast DATA OVERVIEW Diagrams of measured temperatures for last week Diagrams of measured temperatures for last day Special service data CONTROLLER...

Страница 16: ...manual PRAMETERS FOR FLOOR DRYING FACTORY SETTINGS Reset of all controller parameters Reset of time programs Reset of all controller settings and restart of initial setup Save user settings Load user...

Страница 17: ...Day temperature Night temperature Use buttons and to set the temperature Confirm and return to the previous screen by pressing button Use buttons and to set the temperature Confirm and return to the...

Страница 18: ...ll finish Temperature setting ECO Press icon ECO to activate economic temperature operation mode To adjust function press the ECO icon once again A new screen opens Use buttons and to set the temperat...

Страница 19: ...valve Circulation pump switch on Press button to confirm and exit to the previous screen Heating or cooling operation mode selector For cooling operation mode it is necessary to connect a room sensor...

Страница 20: ...ay whose program course you want to edit or copy it to other days TIME PROGRAMS Four independent time programs are available If we press on already selected time program icon a new screen opens Time p...

Страница 21: ...rval Move to left Move to right Save time program changes and return to the previous screen With the help of above listed icons we draw requested course of time program The time program copying Icons...

Страница 22: ...N FRI 06 00 22 00 SAT SUN 07 00 22 00 Day Day temperature period MON FRI 05 00 7 30 13 30 22 00 SAT SUN 07 00 22 00 Day Day temperature period MON FRI 06 00 08 30 11 00 13 30 16 00 22 00 SAT SUN 07 00...

Страница 23: ...ish to use by pressing the icon Confirm your selection and exit to the previous screen by pressing button Time and date Screen for time and date setting is opened Confirm your setting and exit to the...

Страница 24: ...L SERVICE DATA Diagnostic data for service department DIAGRAMS OF MEASURED TEMPERATURES FOR LAST WEEK Graphical representation of temperatures for each sensor by days Temperatures are recorded for the...

Страница 25: ...rs Service parameters Floor drying parameters CONTROLLER PARAMETERS BASIC PARAMETERS SERVICE SETTINGS MANUAL Only those parameters that are used in the selected hydraulic scheme are visible From the s...

Страница 26: ...he controller carries out the automatic changeover between summer and winter time 0 NO 1 YES 1 P1 7 PERIOD OF TEMPERAT LOGGING MINUTES By setting this field you define how often the measured temperatu...

Страница 27: ...he object by low outdoor temperatures gets warmer the heat curve steepness needs to be decreased The maximum steepness increase decrease should not be greater than 0 1 to 0 2 units at one observation...

Страница 28: ...1 4 With adjusting the heat curve steepness the controller is tuned with the building For optimal controller operation the right setting of the heat curve steepness is very important Preferred settin...

Страница 29: ...before editing Parameter index Default parameter value Parameter is locked Current parameter value Navigation buttons Parameter description Decrease value Previous position Increase value Next positio...

Страница 30: ...the operation mode for sensor T1 If return pipe sensor is selected a limitation of temprature difference between stand and return pipe needs to be set with parameter S2 13 0 ROOM SENSOR 1 RETURN PIPE...

Страница 31: ...igher frequency 0 4 2 5 1 S2 10 MIXING VALVE D CONSTANT Sensitivity of mixing valve for stand pipe temperature changes Smaller value means low sensitivity higher value means high sensitivity 0 4 2 5 1...

Страница 32: ...R DRYING 0 NO 1 YES 0 F1 2 INTERVAL 1 DURATION 1 15 days 10 F1 3 INTERVAL 1 START TEMPERATURE 10 60 C 20 F1 4 INTERVAL 1 END TEMPERATURE 10 60 C 20 F1 5 INTERVAL 2 DURATION 1 15 days 5 F1 6 INTERVAL 2...

Страница 33: ...S Load previously saved user settings RESET OF ALL CONTROLLER PARAMETERS Restores all settings of parameters P1 P2 P3 S1 except S1 1 S2 S3 and F1 to default values RESET OF TIME PROGRAMS Restores defa...

Страница 34: ...ng or opening of the controller is not needed and not allowed INSTALLATION ONTO MIXING VALVE Installation example shown on the picture bellow is valid for mixing valves of the following manufacturers...

Страница 35: ...38 Installation manual Installation onto 4 way mixing valve Installation onto 3 way mixing valve...

Страница 36: ...ibility of publisher for unprofessional wrong and false information and con secutive damage are explicitly excluded We retain the right for technical errors mistakes changes and corrections without pr...

Страница 37: ...ry to set the coding switches on the back side of the room unit REQUIRED SETTING Room unit controls the heating circuit Room unit does not control the heating circuit First room unit 1 Second room uni...

Страница 38: ...lip Room sensor or room unit Room sensor or room unit is mounted on the inner wall of the living room which is not exposed to the sun and away from heat sources and drafts First take off the lid then...

Страница 39: ...by manual operation mode Room temperature sensor or room unit isn t connected or has a malfunction Room heating operates normally with respect of outdoor temperature Return pipe temperature sensor is...

Страница 40: ...connection of controllers CMP25 2 and WDC10B WDC10 or WDC20 By Bus connection you can connect with each other any number of controllers WDC and CMP25 2 The first controller WDC controls the heat sour...

Страница 41: ...o not contain all auxiliary and safety elements When installing you have to follow valid rules IMPORTANT For controller operation room unit or room sensor is not needed Room unit or room sensor connec...

Страница 42: ...45 Hydraulic and electric schemes Scheme 360b Expanding mixing circuit BUS connection of controllers is described on pages 42 and 43...

Страница 43: ...60730 1 Temperature control class III without room temp sensor VII with room temp sensor Type of operation Tip 1B by EN 60730 1 Ambient temperature 0 to 40 C Storing temperature 20 to 70 C Technical s...

Страница 44: ...for hazardous substances in electric and electronic appliances 2011 65 EC Rohs II PRODUCT DESCRIPTION Weather compensated controller for central heating systems MODEL NAME CMP25 2 APPLIED STANDARDS E...

Отзывы: