29
Service settings manual
Basic settings
:
Parameter
Function
Parameter description
Setting range Default
value
P1.1
AUT. SWITCHOVER
SUMMER/WINTER
Automatic switch-off of heating in accordance to average
one-day outdoor temperature.
0- NO
1- YES
0
P1.2
AVERAGE OUTDOOR
TEMP. FOR SUMMER/
WINTER SWITCHOVER
Setting of average one-day outdoor temperature at which
the heating should switch-off.
10 ÷ 30 °C
18
P1.4
REQUESTED ROOM
TEMPERAT. BY FROST
PROTECTION
Setting of room temperature when heating is switched off.
2 ÷ 12
6
P1.5
TEMPERATURE ROUND
UP
You set the accuracy of displayed temperatures.
0- 0.1 °C
1- 0.2 °C
2- 0.5 °C
3- 1 °C
2
P1.6
AUT. SHIFT OF CLOCK
TO SUMMER/WINTER
TIME
With the help of a calendar, the controller carries out the
automatic changeover between summer and winter time. 0- NO
1- YES
1
P1.7
PERIOD OF TEMPERAT.
LOGGING (MINUTES)
By setting this field you define how often the measured
temperatures are saved.
1 ÷ 30 min
5
P1.8
TONES
By setting this field you define sound signals of the con-
troller.
0- OFF
1- KEYPAD
1
P1.9 ADVANCED
TEMPERATURE SCREEN
Advanced screen means that while checking temperatu-
res you can see measured and required or calculated
temperature.
0- NO
1- YES
1
Settings for heating circuit
:
Parameter
Function
Parameter description
Setting range Default
value
P2.1
HEAT CURVE
STEEPNESS
Heating curve steepness tells us, what temperature is
required for the heating bodies by a determined outdoor
temperature. The steepness setting depends on the type
of heating system (floor, wall, radiator, convector heating)
and insulation of the building.
0,2 ÷ 2,2
0,7
- floor
1,0
- radia-
tors