Rev. 1.00
22062_EDEBD
A0236-1218-1_EN
11
KBR MWV measuring transducer adapter
5
Technical data
Type 400 / 100 V – IEC
Primary voltage:
400 V Ph-Ph
Secondary voltage:
100 V Ph-Ph or 57.7 V Ph-Mp
Power
Max. 1 VA
Housing
DIN rail installation
Weight
Approx. 650 g
Dimensions
Approx. 87 x 72 mm
Voltage input fuse
Max. 1 A slow-blow or C2 automatic
Type 600 / 85.7 V – UL (NRTL)
Primary voltage:
600 V Ph-Ph
Secondary voltage:
85.7 V Ph-Ph or 49.5 V Ph-Mp
Power
Max. 1 VA
Housing
DIN rail installation
Weight
Approx. 650 g
Dimensions
Approx. 87 x 72 mm
Voltage input fuse
Max. 1 A slow-blow or C2 automatic
Type 700 / 100 V – IEC
Primary voltage:
700 V Ph-Ph
Secondary voltage:
100 V Ph-Ph or 57.7 V Ph-Mp
Power
Max. 1 VA
Housing
DIN rail installation
Weight
Approx. 650 g
Dimensions
Approx. 87 x 72 mm
Voltage input fuse
Max. 1 A slow-blow or C2 automatic