background image

Operating instructions 

multisio 1D4-4RO ISO

Page 5 of 5

Version 2.00

E

D

EBD

A0
18
7 /
 15

11-

1

 GB

6

Technical data

Power supply:

Via module bus

24VDC / ca. 1.3W

Connection

Modular connector RJ-12:6P6C

Hardware outputs:

4 plug terminal, each 2 pole

4 relay outputs

Terminals 40 to 47

potential free

Contact capacity

500VA each, 2A, 250V and 50/60Hz

Overvoltage category

CAT II

Module bus interface:

Serial interface

RS-485

Module bus connection

RJ-12 for ready-made 
KBR system cable, max. length 30 m 
when placed accordingly

Transmission speed

38400 Bps

Bus protocol

KBR module bus

Display:

LED

4x message
1x operation display

Control unit

DIP switch

1x 8-fold, for manual operation

Button

Scan button (module bus)

Mechanical data:

Top hat rail device

Housing measurements

90 x 70 x 61 mm (H x W x D)

Mounting type

Wall mounting on DIN rail 
7.5 mm deep, in accordance with 
DIN EN 50022.

Weight

approx. 130g

Standards and 
miscellaneous:

Ambient conditions

Standards

DIN EN 60721-3-3/A2: 1997-07; 
3K5+3Z11; (IEC721-3-3; 3K5+3Z11)

Operating temperature

-5°C ... +55°C

Humidity

5% ... 95%, non-condensing

Storage temperature

-25°C ... +70°C

Electrical safety

 

Standards

DIN EN 61010-1/A2: 2001 + B1: 
2002-11 + B2: 2004-1;
(IEC1010-1/A2)

Mode of protection

IP20 in accordance with DIN EN 
40050
part 9:1993-05

Electromagnetic
compatibility

DIN EN 61000-6-3: 2001 + A11: 
2004; (IEC61000-6-3)
DIN EN 61000-6-2: 2001
(IEC61000-6-2)

Содержание multisio 1D4-4RO ISO

Страница 1: ...Operating Instructions Technical Parameters Potential free 4 relay output module 1D4 4RO ISO multisio...

Страница 2: ...le of Contents 1 Function description relay output module multisio 1D4 4RO ISO 2 2 Connection diagram for relay output module 2 3 Relay output module LED display 3 4 Function of scan button 3 5 Functi...

Страница 3: ...or a computer with VE via multisys 3D2 ESBS using the module bus interface The master device has to configure the module The operating voltage is supplied via the module bus interface The module cann...

Страница 4: ...detection mode the output LEDs generate a running light The displays are 4 Function of scan button LED1 for Output relay 1 A1 switched LED2 for Output relay 2 A2 switched LED3 for Output relay 3 A3 sw...

Страница 5: ...determines the state of output 1 DIP switch 2 determines the state of output 2 DIP switch 3 determines the state of output 3 DIP switch 4 determines the state of output 4 If the DIP switch is set to O...

Страница 6: ...4x message 1x operation display Control unit DIP switch 1x 8 fold for manual operation Button Scan button module bus Mechanical data Top hat rail device Housing measurements 90 x 70 x 61 mm H x W x D...

Страница 7: ...der Norm en This is documented by the accordance with the following standard s Justifi par le respect de la des norme s suivante s DIN EN 61010 1 2001 DIN EN 61010 1 B1 2002 DIN EN 61010 1 B2 2004 DIN...

Страница 8: ...gsvor schl ge Bitte geben Sie die betreffende Anleitung oder Druck schrift mit Versionsnummer und oder Ausgabestand an If you come across misprints in this user manual or prin ted material please take...

Отзывы: