V2.00
19837_EDEBD
A0227-2620-1_EN
53
System operation
8.2
Measuring accuracy
Current
± 1 % / ± 1 digit
Voltage
± 1 % / ± 1 digit
Power
± 2 % / ± 1 digit
Power factor
± 2 % / ± 1 digit
Frequency
± 0 .1 Hz / ± 1 digit
8.3
Measuring principle
Sampling
128 readings per period
A/D converter
12 bit
Measurement of U and I
simultaneous recording of measured
values for U and I
Update speed
(complete measuring cycle)
20 ms
Harmonics calculation
FFT with 128 points over one period
Frequency measurement
Consumption: Voltage measurement
between phase Lx - N
8.4
Device memory
Memory
30 KB RAM (volatile)
Program and parameter memory
256 kB flash
Extreme value (max .)
Missing compensation power Qmax
Harmonic limit violation
Recording
time
approx . 100 ms
Overvoltage
switch-off
Recording
time
approx . 40 ms
Zero-voltage switch-off
Recording
time
approx . 40 ms (for measuring voltage)
8.5
Power supply
Power supply
100V - 240V +/-10% 50Hz/60 Hz/DC,
max . 15 VA, 9W