System operation
NOTE
Stage selection mode (switching mode):
The priority of switching criteria for compensation stages can be changed in the menu
Extra ==> Settings => System => Basic Parameters => Switching Performance => Switch-
ing Hysteresis => Switching Mode .
The aim of the switching criteria is to use the compensation stages as evenly as possible .
The following modes are available:
Priority 1: fewest operating hours (turn-on duration) of the compensation stage
Priority 2: fewest switching cycles of the compensation stage
Display example for Priority 1:
Switch mode
Priority
d
24h
7
t-on
On
¡
¯
Edit
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18
A A A A A A A A A A A A A A A A A A
An exchange of the connected compensation stages with equivalent stages can be
activated/deactivated after 24 hours of run-time in the Switching mode menu with the
parameter
d
24h
7
¶ (though only with priority 1 – operating hours optimization) .
The exchange takes place every 24 hours.