IODF INPUT/OUTPUT MULTI-FUNCTION EXPANSION MODULE KIT (PART NO. 9646) 

INSTALLATION AND OPERATION INSTRUCTIONS 

 

 

 KB 

Electronics, 

Inc. 

 

12095 NW 39th Street, Coral Springs, FL 33065-2516 

 (954) 346-4900 

 FAX (954) 346-3377 

 

Outside Florida Call Toll Free (800) 221-6570 

 [email protected] 

 www.kbelectronics.com 

Page 3 of 4  

(A40193) – Rev. A00 – 5/7/2013

 

Incremental Operation:

 For each activation of the Up Contact, the drive output frequency will increase incrementally, equal to the frequency 

set by Function 7.15 (factory set to 1.00 Hz). For each activation of the Down Contact, the drive output frequency will decrease incrementally, 
equal to the frequency set by Function 7.15 (factory set to 1.00 Hz). 
 

Note:

 In Incremental Operation, if the Up or Down Contact is maintained for longer than 2 seconds, the drive output frequency will "free run" 

up or down in increments set by Function 7.15, for the duration of the contact closure. The rate of change is equal to the Accel/Decel settings 
in Function Nos. 3.03 and 3.04. When the contact is opened, the drive output frequency will stop changing. 
 
 

TABLE 2 – IODF INPUT AND OUTPUT CONNECTIONS 

Terminal Block   No. 

Description 

Specifications 

13 

Open Collector 

Output 

NPN 

14 MFIT 

15 MFIT 

N.O. Contacts or NPN / PNP Transistors, 7 Preset Frequencies, Up Frequency Command, 

Down Frequency Command, Accel/Decel #2, Forward / Stop Command, Reverse / Stop Command,

External Fault (N.O. Contact), Reset, N.O. Start (2-Wire or 3-Wire Start/Stop), 

N.C. Stop (3-Wire Start/Stop), External Fault (N.C. Contact) 

16  

Common

1

 

──

 

17 

Power Supply 

+5 Volts DC at 1 mA Max. 

18  Analog Input #2 

0-2.5 thru 0-25 Volts DC 

(TB1 on IODF) 

16

14

13

15

17

19

18

 

19  

Common

1

 

──

 

N.O. Normally 

Open 

COM Relay Common

2

 

(TB3 on IODF) 

 

N.C. Normally Closed 

Run,

 

Fault, Target Frequency (5.03 ± 5.04), Frequency Threshold Level (> 5.03 – 5.04), 

Frequency Threshold Level (< 5.03 + 5.04), I

2

t or I•t Fault, Load Loss (See 5.05), External Fault 

Notes: 1.

 Common Terminals 16 and 19 are internally wired together. These terminals are also internally wired to Terminals 4 and 11 on the 

drive. 

2.

 Relay Common is not internally wired to Common Terminals 14 and 16 (or Common Terminals 4 and 11 on the drive). 

 
 

TABLE 3 – IODF MULTI-FUNCTION INPUT TERMINAL, FUNCTION, AND FACTORY CODE ASSIGNMENT 

Multi-Function Input Terminal* 

6 7 

Number On Terminal Block 

14 15 

Function 

7.05 7.06 

Factory Code Setting 

0003 0004 

Code Description 

Up Frequency Command 

Down Frequency Command 

*Each Multi-Function Input Terminal is controlled by a specific Function. Although factory set to a specific code, they can also be 
reprogrammed to any code "0000" – "0012" listed in Table 2, above.  Also see Function Group 7, on page 60, in the manual. 
 
 

3.2 MULTI-FUNCTION OUTPUT RELAY 

The connections for the Multi-Function Output Relay are located on Terminal Block TB3. The Multi-Function Output Relay is factory 
programmed to function as a "Run" Relay (Function 5.01 set to "0000"). When the drive is put into the Run Mode, the relay contacts will 
change state (the Normally Open (N.O.) contact will close and the Normally Closed (N.C.) contact will open). See Table 4. 
 

 

TABLE 4 – IODF MULTI-FUNCTION OUTPUT RELAY "RUN" AND "FAULT" OPERATING MODES 

"Run" Relay Mode 

(Function 5.00 Set to "0000") 

"Fault" Relay Mode 

(Function 5.00 Set to "0001") 

Drive Operating 

Condition 

N.O. Contact 

N.C. Contact 

N.O. Contact 

N.C. Contact 

Power 

Off  Open Closed Open Closed 

Power On (Stop Mode) 

Open 

Closed 

Closed 

Open 

Run Mode 

Closed 

Open 

closed 

Open 

All 

Faults  Open Closed Open Closed 

 
 
 
 

Содержание 9646

Страница 1: ...he responsibility of the equipment manufacturer and individual installer to supply this Safety Warning to the ultimate end user of this product SW 8 2012 The drive contains electronic Start Stop circuits which can be used to start and stop the drive However these circuits are never to be used as safety disconnects since they are not fail safe Use only the AC Line for this purpose Be sure to read a...

Страница 2: ...ore using the drive Disconnect the main power before making connections to the drive or the IODF To avoid electric shock be sure to properly ground the drive Application Note To avoid erratic operation do not bundle AC Line input and motor wires with each other Also do not bundle motor wires from multiple drives in the same conduit Use shielded cables on all signal wiring over 12 30 cm The shield ...

Страница 3: ... 14 13 15 17 19 18 19 Common 1 N O Normally Open COM Relay Common 2 TB3 on IODF N C Normally Closed Run Fault Target Frequency 5 03 5 04 Frequency Threshold Level 5 03 5 04 Frequency Threshold Level 5 03 5 04 I 2 t or I t Fault Load Loss See 5 05 External Fault Notes 1 Common Terminals 16 and 19 are internally wired together These terminals are also internally wired to Terminals 4 and 11 on the dr...

Страница 4: ...peed output and observe the display Rotate the SCALE Trimpot counter clockwise until the drive output frequency begins to drop Then rotate the SCALE Trimpot clockwise until the display returns to the maximum output frequency Set the signal Slope and Type and adjust the Gain Offset and Response Time as desired See Section 8 4 2 1 on page 30 of the manual 4 DIAGNOSTIC LEDs The two LEDs provide indic...

Отзывы: