KB Electronics 9646 Скачать руководство пользователя страница 2

IODF INPUT/OUTPUT MULTI-FUNCTION EXPANSION MODULE KIT (PART NO. 9646) 

INSTALLATION AND OPERATION INSTRUCTIONS 

 

 

 KB 

Electronics, 

Inc. 

 

12095 NW 39th Street, Coral Springs, FL 33065-2516 

 (954) 346-4900 

 FAX (954) 346-3377 

 

Outside Florida Call Toll Free (800) 221-6570 

 [email protected] 

 www.kbelectronics.com 

Page 2 of 4  

(A40193) – Rev. A00 – 5/7/2013

 

2.1  REMOVING THE DRIVE'S COVER: 

Press on the both finger grips on both side corners of the cover until the retaining clips disengage from the drive and lift it up. This cover must 
be replaced with the new cover (supplied), as described in Section 5, on page 4. 
 
 

2.2  REMOVING THE DRIVE'S INTERFACE HEADER COVERS: 

Both covers must be removed off of headers CON1 and CON2, on the drive. These covers are no longer needed and may be discarded. 
 

 
2.3  INSTALLING THE IODF 

Align the IODF CON1 and CON2 over the corresponding headers on the drive. The IODF should easily drop down into the headers 
approximately 1/8" (3 mm) and the IODF PC board should rest on all three clips. To complete the installation of the IODF, press down firmly 
on the PC board near the top two clips and then on the shorter Terminal Block TB2 until the IODF is secured onto the drive with all three clips. 
 
 
 

3 ELECTRICAL CONNECTIONS

 

Wire the control in accordance with the National Electrical 
Code requirements and other local codes that may apply 
to the application. See Figure 3, for connections to 
Terminal Blocks TB1 and TB3. See Table 1 for the 
terminal block wire and tightening torque specifications. 
 

 WARNING! HIGH VOLTAGE! Read Safety 

Warnings, on page 1, before using the drive. 
Disconnect the main power before making 
connections to the drive or the IODF. To avoid electric 
shock, be sure to properly ground the drive. 
 
Application Note: 

To avoid erratic operation, do not 

bundle AC Line input and motor wires with each other. 
Also, do not bundle motor wires from multiple drives in the 
same conduit. Use shielded cables on all signal wiring 
over 12" (30 cm). The shield should be earth grounded on 
the drive side only. 

 
 

TABLE 1 – TERMINAL BLOCK WIRE AND TIGHTENING TORQUE SPECIFICATIONS 

Maximum 

Wire Size (Cu) 

Recommended 

Tightening Torque 

Description Location 

AWG mm

2

 lbs-in kg-cm 

MFITs and Signals In/Out  

TB1 

16 

1.31 

1.7 

1.9 

Multi-Function  Output Relay 

TB3 

16 

1.31 

2.6 

2.9 

 
 

3.1 MULTI-FUNCTION INPUT TERMINALS 

 

MFIT 6 is factory programmed for Up Frequency Command (Function 7.05 set to "0003"). MFIT 7 is factory programmed for Down Frequency 
Command (Function 7.06 set to "0004"). When the MFIT 6 contact is closed, the drive's frequency will increase. When the MFIT 7 contact is 
closed the drive's frequency will decrease. Also see Section 8.4.2.3, on page 34 of the manual. MFIT 6 and MFIT 7 can be changed from their 
factory settings of Up Frequency Command and Down Frequency Command by reprogramming Functions 7.06 and 7.07, as shown in Table 
2, on page 3. Also see Tables 3 and 4, on page 3. 
 
 

Free-Running Operation:

 When the Up Contact is closed, the drive output frequency will increase for the duration of the contact closure. 

When the Up Contact is opened, the drive output frequency will stop increasing. When the Down Contact is closed, the drive output frequency 
will decrease for the duration of the contact closure. When the Down Contact is opened, the drive output frequency will stop decreasing.   

FIGURE 3 – CONNECTION DIAGRAM

 

 
 
 

Содержание 9646

Страница 1: ...he responsibility of the equipment manufacturer and individual installer to supply this Safety Warning to the ultimate end user of this product SW 8 2012 The drive contains electronic Start Stop circuits which can be used to start and stop the drive However these circuits are never to be used as safety disconnects since they are not fail safe Use only the AC Line for this purpose Be sure to read a...

Страница 2: ...ore using the drive Disconnect the main power before making connections to the drive or the IODF To avoid electric shock be sure to properly ground the drive Application Note To avoid erratic operation do not bundle AC Line input and motor wires with each other Also do not bundle motor wires from multiple drives in the same conduit Use shielded cables on all signal wiring over 12 30 cm The shield ...

Страница 3: ... 14 13 15 17 19 18 19 Common 1 N O Normally Open COM Relay Common 2 TB3 on IODF N C Normally Closed Run Fault Target Frequency 5 03 5 04 Frequency Threshold Level 5 03 5 04 Frequency Threshold Level 5 03 5 04 I 2 t or I t Fault Load Loss See 5 05 External Fault Notes 1 Common Terminals 16 and 19 are internally wired together These terminals are also internally wired to Terminals 4 and 11 on the dr...

Страница 4: ...peed output and observe the display Rotate the SCALE Trimpot counter clockwise until the drive output frequency begins to drop Then rotate the SCALE Trimpot clockwise until the display returns to the maximum output frequency Set the signal Slope and Type and adjust the Gain Offset and Response Time as desired See Section 8 4 2 1 on page 30 of the manual 4 DIAGNOSTIC LEDs The two LEDs provide indic...

Отзывы: