background image

Refrigerant piping

Connection

Page 31

5. Clamp flare form on the end of the pipe.

The end of the pipe must extend beyond

the flare form.

Flare form

Pipe

6.

Place flaring tool onto the form.

7.

Turn the handle of the flaring tool

clockwise until the pipe is fully flared. Flare

the pipe in accordance with the dimensions.

PIPING EXTENSION BEYOND FLARE FORM

8. Remove the flaring tool and flare form,

then inspect the end of the pipe for cracks

and even flaring.

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, 

then connect it to the outdoor unit. You should 

first connect the low-pressure pipe, then the high-

pressure pipe.  

1.

 

When connecting the flare nuts, apply a

thin coat of refrigeration oil to the flared

ends of the pipes.

2.

 

Align the center of the two pipes that you

will connect.

Indoor unit tubing

Flare nut

Pipe

3.

 

Tighten the flare nut as tightly as possible

by hand.

4.

 

Using a spanner, grip the nut on the unit

tubing.

5. While firmly gripping the nut, use a torque

wrench to tighten the flare nut according

to the torque values in above table.

NOTE: 

Use both a spanner and a torque wrench 

when connecting or disconnecting pipes to/from 

the unit.

 

  Pipe 
gauge 

Tightening 

torque

Flare dimension (A) 

(Unit: mm/Inch)

Flare shape

Min.

Max.

Ø 6.35

R0.4~0.8

45

°±

2

90

°      

±

4

A

Ø 9.52

Ø 12.7

Ø 16

Ø 19

Ø 22

65-67 N.m 

(663-683 kgf.cm)

23.2/0.91

23.7/0.93

75-85N.m 

(765-867 kgf.cm)

26.4/1.04

26.9/1.06

18-20 N.m 

(183-204 kgf.cm)

8.4/0.33

8.7/0.34

25-26 N.m 

(255-265 kgf.cm)

13.2/0.52

13.5/0.53

35-36 N.m 

(357-367 kgf.cm)

16.2/0.64

16.5/0.65

45-47 N.m 

(459-480 kgf.cm)

19.2/0.76

19.7/0.78

 CAUTION

Ensure to wrap insulation around the piping.

Direct contact with the bare piping may

result in burns or frostbite.

Make sure the pipe is properly connected.

Over tightening may damage the bell mouth

and under tightening may lead to leakage.

Содержание KPDA-35 DVR14

Страница 1: ...4 Duct OWNER S INSTALLATION MANUAL IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please che...

Страница 2: ...Unit Specifications and Features 08 Owner s Manual Table of Contents Safety Precautions 04 Care and Maintenance 11 Troubleshooting 13 1 Indoor unit 08 2 Operating temperature 09 3 Other features 10...

Страница 3: ...g 34 2 Indoor Uint Wiring 34 3 Power Specifications 35 3 Anchor outdoor unit 27 Refrigerant Piping Connection 29 A Note on Pipe Length 29 B Connection Instructions Refrigerant Piping 30 1 Cut pipe 30...

Страница 4: ...must be supervised around the unit at all times operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circui...

Страница 5: ...residual current device RCD having a rated residual operating current not exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules For all electric...

Страница 6: ...stall the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause fire Do not turn on the power until all work has been completed Wh...

Страница 7: ...14903 Amount of refrigerant to be charged kg Minimum room area m 1 11 1 1 65 2 2 58 5 3 08 7 3 84 10 4 24 Model Btu h 12000 18000 24000 30000 36000 42000 48000 12 4 39 60000 13 Safety Precautions Pag...

Страница 8: ...control has been misplaced or is out of batteries Air outlet Air inlet Air filter on some models Drain hose Electric control cabinet Refrigerant connecting pipe A For the unit which the filter is remo...

Страница 9: ...owing temperature ranges certain safety protection features may activate and cause the unit to disable COOL mode HEAT mode DRY mode Room Temperature 17 C 32 C 0 C 30 C 10 C 32 C Outdoor Temperature 0...

Страница 10: ...will automatically return to the previous position The angle of the horizontal louver should not be set too small as condensation may form and drip into the machine To reset the louver press the manu...

Страница 11: ...conditioner can reduce the cooling efficiency of your unit and can also be bad for your health Make sure to clean the filter once every two weeks WARNING DO NOT REMOVE OR CLEAN THE FILTER BY YOURSELF...

Страница 12: ...outlets If using a vacuum cleaner the inlet side should face the vacuum If using water the inlet side should face down and away from the water stream CAUTION Before changing the filter or cleaning tur...

Страница 13: ...ion of the unit s plastic parts Both the indoor unit and outdoor unit make noises Low hissing sound during operation This is normal and is caused by refrigerant gas flowing through both indoor and out...

Страница 14: ...description of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Causes Solut...

Страница 15: ...Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for leaks re...

Страница 16: ...ctor 12 7 15 9 some models Transfer connector 6 35 9 52 some models Transfer connector 9 52 12 7 some models Connecting wire for display 2m some models Cord protection rubber ring some models Display...

Страница 17: ...ation Summary Install the outdoor unit Install the drainpipe 1 2 3 4 5 MC MC 6 Install the indoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes 7 Installation...

Страница 18: ...ent The actual shape shall prevail NOTE The installation must be performed in accordance with the requirement of local and national standards The installation may be slightly different in different ar...

Страница 19: ...es such as cabinets Kitchens that use natural gas Areas with strong electromagnetic waves Areas that store flammable materials or gas Rooms with high humidity such as bathrooms or laundry rooms Enough...

Страница 20: ...A B C 18K 210 8 3 674 26 5 880 34 6 24K 36K 249 9 8 774 30 5 1100 43 3 30K 36K 249 9 8 774 30 5 1360 53 5 36K 60K 300 11 8 874 34 4 1200 47 2 air outlet opening size D E F 136 5 4 706 27 8 600 23 6 1...

Страница 21: ...and fit pipes and wires after you have finished installing the main body When choosing where to start determine the direction of the pipes to be drawn out Especially in cases where there is a ceiling...

Страница 22: ...xternal duct static pressure 2 Install the canvas tie in between the body and duct 3 The air inlet and air outlet duct should be far enough apart enough to a avoid air passage short circuit 4 Connect...

Страница 23: ...e and will help seal it when you finish the installation process CAUTION When drilling the wall hole make sure to avoid wires plumbing and other sensitive components Wall Indoor Outdoor 12mm 0 5 inch...

Страница 24: ...h of the drain hose to the unit s outlet pipe Sheath the mouth of the hose and clip it firmly with a pipe clasp 39 59 1 1 5m 1 1 Lean over 1 50 Ceiling 39 59 7 9 20cm 21 7 55cm Lean over 1 50 1 1 5m 1...

Страница 25: ...leaks from the joints 3 Turn off the air conditioner and put the cap back on 3 Pass the drain hose through the wall hole Make sure the water drains to a safe location where it will not cause water dam...

Страница 26: ...build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or snow Build a shel...

Страница 27: ...ee Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to red...

Страница 28: ...403 15 87 946x810x410 37 24x31 9x16 14 673 26 5 403 15 87 952x1333x410 37 5x52 5x16 14 634 24 96 404 15 9 952x1333x415 37 5x52 5x16 34 634 24 96 404 15 9 845x702x363 33 27x27 6x14 3 540 21 26 350 13 8...

Страница 29: ...Type of model Capacity Btu h Length of piping Maximum drop height EU frequency conversion Split Type 15K 25 82 10 32 8 15K 24K 30 98 4 20 65 6 24K 36K 50 164 25 82 36K 60K 65 213 30 98 4 Other Split...

Страница 30: ...and flare them properly This will ensure efficient operation and minimize the need for future maintenance 1 Measure the distance between the indoor and outdoor units 2 Using a pipe cutter cut the pip...

Страница 31: ...door unit tubing Flare nut Pipe 3 Tighten the flare nut as tightly as possible by hand 4 Using a spanner grip the nut on the unit tubing 5 While firmly gripping the nut use a torque wrench to tighten...

Страница 32: ...Every wire must be firmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire 10 Do not let wires touch or rest against refrigerant tubing the...

Страница 33: ...less than 16A the power cord of air conditioner shall be equipped with plug purchased seperately 12 To avoid getting an electric shock never touch the electrical components soon after the power supply...

Страница 34: ...or metal parts 6 Reinstall the cover of the electric control box 1 Prepare the cable for connection a Using wire strippers strip the rubber jacket from both ends of the signal cable to reveal about 15...

Страница 35: ...IRCUIT BREAKER FUSE A 25 20 32 25 50 40 70 55 70 60 MODEL Btu h 36K 37K 60K 36K 37K 60K POWER PHASE 3 Phase 3 Phase 3 Phase 3 Phase 380 420V 380 420V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 32...

Страница 36: ...10 15 10 15 10 15 10 15 10 POWER outdoor PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase 208 240V 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 25 20 40 30 50 40 50 40 MODEL Btu h 36...

Страница 37: ...nutes or until the Compound Meter reads 76cmHG 105 Pa 2 3 4 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no ch...

Страница 38: ...16 The refrigerant should be charged from the service port on the outdoor unit s low pressure valve The additional refrigerant to be charged can be calculated using the following formula Liquid Side D...

Страница 39: ...ered correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that th...

Страница 40: ...and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the servic...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Отзывы: