owner's manual

 

4

 

 

The display contents as followings

:

 

Normal display:When standby, the high position displays the address of the 

outdoor nuit,and the low position displays the Qty.of indoor units that can communi

 

-cate with outdoor unit .When it is operating, it will display the rotation frequency of 
the compressor.

 

1)

 

Operation mode:0-OFF; 2-Cooling; 3-Heating; 4-Constraint  cooling;

 

2)

 

Fan speed:0-stop; 1~10: speed increase sequentially, 10 is the max. fan speed. 

3)EXV opening angle: Pulse count=display value*8;

 

4)Priority mode: 0-heating priority mode ; 1-cooling priority mode ; 2-open the

 

priority mode first ; 3-respond the heating mode only ; 4-respond the cooling mode only. 

5)Night noise control mode:0-Night noise control mode ; 1-silent mode ; 2-reserve;

 

3-no priority.

 

2.3  5-minute protection feature 

A protection feature prevents the air conditioner from being 
activated for approximately 5 minuites when it restarts 
immediately after operation.

 

2.4  Cooling, Heating, operation of DC speed regulation central 

A/C 

The indoor unit can be controlled separately, but indoor units in 
the same system can not simultaneously operate the cooling and 
heating.

 

If there is conflict between cooling mode and heating mode, the 
indoor unit under cooling operation will stop and the operating 
panel will display “Non-priority” or “Standing-by” code. The indoor 
unit under heating operation will operate normally.

 

If the administrator has fixed set the cooling or heating operation, 
it can not do the operations beyond the setting. When do the

 

 

2.9  Mishandling in operation

 

If mishandling happens because of lighting or mobile wireless, 
please shut off the manual power switch, and turn on again, 
then push the ON/OFF button.

 

2.10  About power cut

 

If power is cut during operation, stop all the operation 
immediately.

 

 

Power comes again. The lamp on the display panel of indoor 
unit flashes. And then unit will auto-restart.

 

 

3.  REINSTALLATION

 

 

 

                             

CAUTION

 

 

 

A/C installation should comply with the 
regulations in GB17790-2008 and the 
requirements in Installation manual.

 

 

When moving the A/C to another 
place, install the unit according to

 

Installation manual by a specialized person.

 

 

Improper installation could lead to electric shock or fire.

 

operations beyond the setting, the operating panel will display 

  

 

“Non-priority” or “Standing-by” code and the unit stops.

 

2.5  Features of heating operation

 

Warm air will not be blown out immediately at the beginning of 
the heating operation,3~5minutes later (depends on the indoor 
and outdoor temperature), until the indoor heat exchanger 
become hot, then blows out warm air.

 

During operation, the fan motor in the outdoor unit may stop 
running under high temperature.

 

2.6  Defrosting in heating operation

 

During heating operation, outdoor unit sometimes will frost. To 
increase efficiency, the unit will start defrosting automatically 
(about 2~10 minutes), and then water will be drained out from 
outdoor unit.

 

During defrosting, both the fan motors in the outdoor unit and 
indoor unit will stop running.

 

2.7  Heating capacity

 

The heating operation is a heat-pump process that heat will be 
absorbed from outdoor air and released in doors. Once the 
outdoor temperature is decreased, heating capacity decreased 
correspondingly.

 

Other heating equipment is suggested to be used together when 
outdoor temperature is too low.

 

In alpine region where the temperature is extremely low, heating 
effect wil be better if users can buy an additional E-heat device.

 

2.8  About protection equipment

 

This Protection Equipment will enable the Air Conditioner to 
stop when the Air Conditio ner is to be directed running 
compulsively. When the Protection Equipment is activated, 
the Operation Indicator still lights while the Air Conditioner is not 
running.

 

The protection equipment may be activated in following 
conditions:

 

Under cooling operation, the air inlet or air outlet of outdoor unit 
is blocked. Strong wind is continuously blowing to the air outlet 
of the outdoor unit.

 

Under heating operation, too much dust and rubbish adhere to 
the dust filter in the indoor unit. The air outlet of indoor unit is

 

3.1  Users’ instruction

 

1.  Users should use the certified power supply corresponding to 

the A/C nameplate, actual voltage should be within 90

%~

110

% 

of the rated voltage.

 

2.  RCCB and air switch should be installed in the power supply 

circuit, the capacity should be 1.5 times of A/C maximum current 
value. Be sure to use specialized circuit.

 

3.  Use specified fuse or RCCB under installation manual.

 

4.  Wiring operations should be applied by electricians, and must 

comply with electrical appliance safety regulations.

 

5.  Make sure the A/C has been grounded wiring properly. The main 

switch of A/C must reliably ground wiring.

 

6.  If the power supply cable needs to be change, please contact 

our A/C customer service center or special technology service 
department to operate by a specialized person.

 

 

3.2  Installation position

 

1. Do not install the unit in such places

 

1) 

Don’t install it in the place where TV, stereo phonographs and 
radio distance the unit less than 1m, noise made by A/C could 
affect those appliences.

 

2) 

Don’t install high frequency equipment near the unit,(e.g. 
commercial sewing machine or massager),or the A/C may fail.

 

3) 

Do not place items which might be damaged by moisture 
under the indoor unit.

 

4) 

Don’t install it in a salty place, such as nearby the sea.

 

5) 

Do not install the air conditioner at any place where flammable 
gas may leak out.

 

6) 

Don’t install it in the place where there’s strong wind, e.g. 
seashore, roof or high floor of a tall building.

 

7) 

Don’t install it nearby a hot spring where sulfur gas leaks. 

8)Don’t install it in the ship or a moving crane.

 

 

2.For the detailed requirements, please go over Installation 

Manual

 

For the detailed information, please refer to Installation manual.

 

 

CAUTION

 

choked. 

  

 

Please intall the unit securely or abmormal noise and vibration 
will be heard.

 

When the protection equipment starts, please shut down the 
manual power switch, and restart operation after problem is 
solved.

 

 

Install the outdoor unit where operation noise and discharged air 
couldn’t affect neighbours.

 

CAUTION

 

Содержание KMF-400 DN3

Страница 1: ... S MANUAL DC INVERTER FREE KMF 400 DN3 KMF 450 DN3 Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference ...

Страница 2: ......

Страница 3: ......

Страница 4: ...ll the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail Indoor unit Outdoor unit 1 Air outlet 2 Air inlet 3 Fixing support 4 Refrigerant pipe connector 5 Connection pipe ...

Страница 5: ...igerant leaks in the room contact with a fire of a burner a heater or a cooker may result in a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do not use the air conditioner until a service person confirms that the portion where the refrigerant leaks is repaired If the supply cord is damaged it must be replaced by the manu...

Страница 6: ...o not install the air conditioner at any place where flammable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out This appliance can be used by children age from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the a...

Страница 7: ... Total capacity of outdoor unit Reserve 6 5 Total requirement of indoor unit capacity Available for main unit 7 6 Total requirement of main unit corrected capacity Available for main unit 8 7 Operation mode 0 2 3 4 9 8 Thisoutdoorunitactualoperationcapacity Capacity requirement 10 9 Speed of fan A 0 1 9 10 11 10 Speed of fan B 0 1 9 10 12 11 T2B T2 average Temp Actual value 13 12 T3 T3A pipe Temp ...

Страница 8: ...tdoor unit and indoor unit will stop running 2 7 Heating capacity The heating operation is a heat pump process that heat will be absorbed from outdoor air and released in doors Once the outdoor temperature is decreased heating capacity decreased correspondingly Other heating equipment is suggested to be used together when outdoor temperature is too low In alpine region where the temperature is ext...

Страница 9: ...5 H7 Qty of indoor units decreases error Indoor unit lost for over 3 munites not recoverable until the unit qty recover 16 H9 3 times of P9 protection in 60 minutes Not recoverable until re power on 17 dF Defrosting 18 d0 Oil returning 19 P1 High pressure protection or discharge temperature switch protection 20 P2 Low pressure protection 21 xP3 Compressor current protection X represents in which s...

Страница 10: ...gularly to avoid super hot in the components 2 For detailed information about cleaning please refer to Indoor unit operation manual 4 5 Maintenance CAUTION After leaving unused for a long time inspect the air inlet and air outlet port of indoor and outdoor unit See if it has been blocked if it is blocked do cleaning immediately Before a long time idling please do the following work 1 Choose air su...