Kaysun KHPA2 300S Скачать руководство пользователя страница 45

About Running 

1 System Structure Figure 

Unit has two kinds of heat sources: Heat pump(compressor) 

and electric heater. 

Unit will automatically select heat sources to heat water to the 
target temperature. 

2  Water Temperature Display 

The temperature shown on the display depends on the upper 

sensor. So it is normal that the display temperature has 

reached to target temperature but compressor still running, 

because the lower water temperature does not get to target 

temperature. 

Modes will be automatically selected by unit. manually mode 
selection is unavailable. 

3  Heat source will be automatically selected by unit. But manually 

E-Heater operation is available.

4  Heat Source Shift 

The default heating source is heat pump.If externalis range out 

of heat pump, heat pump will stop running, the unit will shift 

automatically to activate E-heater and show the icon LA  on 

the display, then if the externaltemperature goes into the 

running range of heat pump again, it will stop E-heater and 

shift automatically to heat pump again, and the icon LA  will be 

extinguished. 

If the target setting water temperature is higher than Max. temp

(Heat pump), the unit will activate heat pump firstly to the Max. 

temperature, then stop heat pump, activate E-heater to 

continually heat water to the target temperature. 

If manually activate the E-heater running mode when heat pump 

running, E-heater and heat pump will work together until the 

water temperature gets to target temperature.  
So if want to heat quickly, please manually activate E-heater. 

Note

 

 

E-heater will be activated once for the current heating progress, 

if 

want 

to 

apply 

E-heater 

again 

please 

push  

E-HEATER. 

If system occurs some malfunctions, error code "E7" and 

 , e 

will be shown on the display, then heat pump will stop running, 

and the unit will activate automatically E-heater as the backup heat 

source, but the code "E7" and 

will be shown until power off. 

If only use E-heater, about only 75 liters water (unit 

190S

) will be

 

heated or about only 150 liters water (unit 

300S

), so must set

 

higher target water temperature if externaltemperature is out of 

heat pump running range. 

Defrosting During Water-heating 

In heat pump running period, if the evaporator frosted in lower 

ambient temperature, the system will defrost automatically to keep 

effective performance(about 3~10min). At defrosting time, the fan 

motor will stop, but compressor will still run. 
TCO and ATCO 
The power of compressor and E-heater will be automatically shut-
off or turn on by TCO and ATCO. 
If the water temperature is higher than 78°C, the ATCO will 
automatically shut off the power of compressor and E-heater, and 
reconnect it if the temperature falls down below 68°C. 
the water temperature is higher than 85°C, the TCO will 
automatically shut off the power of compressor and E-heater. 

Storage tank 

Water outlet 

Temperature probe 
(T5U) 

Electric heater 

Water inlet 

Temperature probe 
(T5L) 

9

 

START-UP 

Содержание KHPA2 300S

Страница 1: ...ch for purchasing our product Before using your unit please read this manual carefully and keep it for future reference INSTALLATION TECHNICAL OWNER S MANUAL Domestic Hot Water Heat Pumps COMPAK KHPA2...

Страница 2: ......

Страница 3: ...installation site 23 6 Water connections 26 7 Aeraulic connections 32 8 Electrical connections 37 9 Start up 41 10 Control 47 11 Maintenance 60 12 Residual risks Decommissioning 65 13 Technical data...

Страница 4: ...de by children without supervision Before cleaning be sure to stop the operation and turn the breaker off or pull out the power plug Otherwise an electric shock and injury may be caused DANGER Do not...

Страница 5: ...idden to trample on the device and or to put on it any type of object It is forbidden to throw or spray water directly on the device It is forbidden to insert sharpened objects by the air return and s...

Страница 6: ...king it easier to suitably note the various interventions and aids the search for any breakdowns Water temperature over 50 C can cause severe burns instantly Children disabled and elderly are at highe...

Страница 7: ...down or malfunction voids the warranty may compromise the safety of the unit may increase time and repair costs Follow local safety regulations Keep packing material out of children s reach it may be...

Страница 8: ...symptom increase Risk of freeze If the unit or the relative water connections can be subject to temperatures close to 0 C adopt measures for prevent risk of freeze The appliance is intended to be perm...

Страница 9: ...protection devices gloves glasses ecc The power cables and the protection cable section must be defined in accordance with the characteristics of the protections adopted The serial number label report...

Страница 10: ...le to emit electromagnetic disturbances Do not lay the cable near devices which can generate electromagnetic interferences Do not lay the cables parallel to other cables cable crossings are possible o...

Страница 11: ...y mode maintenance what to do what not to do in case of breakdown Data update Continual product improvements may imply manual data changes Visit manufacturer web site for updated data 1 SAFETY CONSIDE...

Страница 12: ...number It identifies uniquely each unit Must be quoted when ordering spare parts Assistance request Note data from the serial number label and write them in the chart on side so you will find them eas...

Страница 13: ...ve the following information Model serial and product number Parts name Picture All the picture in this manual are for explanation purpose only They may be slightly different from the unit you purchas...

Страница 14: ...Parts unit 190S Code Description The codes are subject to being updated contact the authorised service centre for the updated code 2 INTRODUCTION...

Страница 15: ...Code Description The codes are subject to being updated contact the authorised service centre for the updated code Parts unit 190S 2 INTRODUCTION...

Страница 16: ...Code Description The codes are subject to being updated contact the authorised service centre for the updated code Parts unit 190S 2 INTRODUCTION...

Страница 17: ...Parts unit 300S Code Description El ectr ical heate r The codes are subject to being updated contact the authorised service centre for the updated code 2 INTRODUCTION...

Страница 18: ...Code Description The codes are subject to being updated contact the authorised service centre for the updated code Parts unit 300S 2 INTRODUCTION...

Страница 19: ...Code Description The codes are subject to being updated contact the authorised service centre for the updated code Parts unit 300S 2 INTRODUCTION...

Страница 20: ...he packaging In case of damage or anomaly Write down on the transport document the damage you found and quote this sentence Conditional acceptance clear evidence of deficiencies damages during transpo...

Страница 21: ...dling equipment lifting capacity B Identify critical points during handling disconnected routes flights steps doors C Stair climbing trolley Handle the packed unit D Minimum passage height E During tr...

Страница 22: ...he unit Keep packing material out of children s reach it may be dangerous Recycle and dispose of the packaging material in conformity with local regulations Front Rear Cut the hoops Cut along the join...

Страница 23: ...s to be installed on a metal part of building make sure the well electric insulation which should meet the relevant local electric standard use of air from heated rooms could penalise the heating perf...

Страница 24: ...tic waves exist Place where flammable gases or materials exist Place where acid or alkali gases evaporate Consider sound emission Noise levels could represent an inconvenience if installed in areas th...

Страница 25: ...g physical danger Check that the floor can support the weight of the unit in operation dimensional see Unit in bubble level Electrical outlet The installation height of power supply should be over 1 5...

Страница 26: ...d to avoid the presence of particles sludge and waste The system must be drained before installing the new unit Dirt can be removed only with a suitable water flow Each section must then be washed sep...

Страница 27: ...ned when the water temperature varies Safety valve Provided by the customer Install all safety devices required by the local laws in force in the countries where the unit is installed The manufacturer...

Страница 28: ...Solar outlet E Solar inlet Electrical connections page 76 Unit with solar 1 Upper condensate outlet 10 2 Condensate drain 10 3 Domestic hot water safety valve 4 Storage tank discharge 5 Drain accumula...

Страница 29: ...drainage work may cause wetting of the building furniture etc IMPORTANT Water coming from the plastic shroud is an indicator that both condensation drain lines 1 2 may be blocked Immediate action is...

Страница 30: ...t water Do not use flexible pipes for unit connection Indicative plumbing diagram The system components must be defined by Designer and Installer ex expansion tanks vents taps calibration safety valve...

Страница 31: ...e drain 11 Solar circulation unit not supplied 12 Solar panels not supplied A Aqueduct inlet B DHW C DHW recirculation Note Water temperature limiting valve is recommended for mixing the inlet cold wa...

Страница 32: ...ed in a room with a minimum volu me greater than 15m2 The expulsion air flow must be gua ranteed and cannot be blocked It is necessary that the vents be correctly sized Channelling the intake and expu...

Страница 33: ...ections with the special hookings to the circular flanges The duct weight should not lie on the connection flanges Put antivibration joints between ducts and units The connection to the flanges and am...

Страница 34: ...in an area with a low concentration of impurities dust odours exhaust fumes etc Exhaust outlet away from terraces balconies property boundary lines avoid windward zones Unit 190S 1 Unit 300S 3 5 2 4...

Страница 35: ...e duct to prevent water from dropping into internal of the unit In case the water entering to internal components of the unit the component might be damaged or causing physical danger The ducts should...

Страница 36: ...ling at the unit inlet In terms of the unit with duct grid there must be put on the position of duct inlet Provided by the customer The grid must be provided on the intake outlet of the external air o...

Страница 37: ...base EVV Electric expansive valve K3M AC contactor Wiring diagram of tank inside POWER SUPPLY The L N wires which get through the zero phase electricity mutual inductor must keeping the sam direction...

Страница 38: ...er T5L Storage tank temperature sensor Lower TP Discharge temperature sensor TH Suction temperature sensor Item description E Mg Electronic anode CAP1 Fan capacity CN1 40 Terminal base TR Transformer...

Страница 39: ...en wiring the power supply please add additional insulation sheath at the place without rubber insulation layer The unit must be installed with an Creepage Breaker near the power supply and must be ef...

Страница 40: ...ding to the relevant electric technical standards of the State The power cord and the signal cord shall be laid out neatly and properly without mutual interference or contacting the connection pipe or...

Страница 41: ...th this manual the electrical power supply line should be isolated at the beginning the unit isolator is open locked and equipped with the suitable warning make sure no tension is present Warning Afte...

Страница 42: ...n protected from frost 9 DHW safety valve pipe connected and conveyed to an adequate drain protected from frost 10 Water temperature limit valve or mixer tap recommended installed per manufacturer s i...

Страница 43: ...re in the OPEN position Check that no air is present in the circuit if required evacuate using the air bleeding valve placed at the system s high points Aeraulic system Verify that the rooms are clean...

Страница 44: ...n before operation Note Before using this unit please follow the steps below Storage tank water filling If the unit is used for the first time or used again after emptying the storage tank please make...

Страница 45: ...at pump running E heater and heat pump will work together until the water temperature gets to target temperature So if want to heat quickly please manually activate E heater Note E heater will be acti...

Страница 46: ...ion days Weekly disinfect function Under disinfection mode unit immediately start to heat water up to 70 C to kill the potential legionella bacteria inside water of storage tank icon will light on the...

Страница 47: ...can display the normal water temperature the remaining days in vacation mode the temperature set when setting the parameters the unit s setting operation parameters On WiFi connected Off WiFi not con...

Страница 48: ...r water pump Electric heater in operation High temperature alarm Water temperature above 50 C Unit in error protection Unit works in VACATION mode There are 14 default vacation days they can be set in...

Страница 49: ...onding value Pressed for more than 1s the value increases continuously Each button press is only effective when the display is unlocked 10 CONTROL Default HYBRID mode Switches to E heat mode Switches...

Страница 50: ...he button for 3 sec to turn the WiFi on The button is used to cancel all the settings and exit the settings status When the WiFi connection is normal press and hold the Cancel button for more than 8 s...

Страница 51: ...s value and finish setting the first programming segment 1 During the setting process press the TIMER ON OFF button to enter the next ON OFF setting 2 During the setting process press the TIMER ON OFF...

Страница 52: ...the confirmation button the DISINFECT icon and the first two values of 8888 flashthe hour can be changed Press the confirmation button the last two values of 8888 flashthe minutes can be changed After...

Страница 53: ...F abnormal view Current Current value Current Current electric heating value display 0 Fan speed 0 stopped 1 low speed 2 high speed Opening degree Electronic expansion valve displays Opening degree Re...

Страница 54: ...omfort Home App Scan the QR code or search for Comfort Home in Google play Android devices or App Store iOS devices to download the app Register or log in to your account Open the App and create a use...

Страница 55: ...resolved When the self protection happens the will flash and error code will be shown at water temperature indicator Press button for 1sec to stop the will flash but the and error code does not disapp...

Страница 56: ...again the supply plug Setting water temp higher Contact service center No hot water tapped out Public water supply ceased Cold water inlet pressure too low 0 15 Bar 0 015 MPa Cold water inlet valve cl...

Страница 57: ...ssor discharge temperature sensor TP error Maybe the connection between sensor and PCB has released or sensor has been broken Contact a qualified person to service the unit E8 Electric leakage error I...

Страница 58: ...discharge temperature is not so higher than evaporator temperature after compressor running a term Maybe because of compressor broken or bad connection between PCB and compressor P4 Compressor overlo...

Страница 59: ...but there is still a mount of hot water can be tapped A Because the upper water sensor is located on the upper 1 4 storage tank when tapping hot water out it means there is at least 1 4 storage tank o...

Страница 60: ...uitable warning sign make sure no tension is present After switching the power off wait at least 5 minutes before accessing to the electrical panel or any other electrical component Before accessing c...

Страница 61: ...er temperature to decrease the heat release prevent scale and save energy if the outlet water volume is sufficient Standby mode In some cold areas under 0 C if the system will be stopped for a long ti...

Страница 62: ...nthly It is advisable to start with frequent checks and to adjust the frequency based on how much dirt is discovered In terms of the filter set in air inlet directly namely air inlet without connect w...

Страница 63: ...move power supply Remove frontal cover A Unscrew the screws and remove the cover cap B Turn off the water inlet valve C Open hot water tap for decrease the pressure of the storage tank Open tap D Empt...

Страница 64: ...w freely when operating the handle replace safety valve with a new one Nota Please beware of burn beware of the hot water from the val ve To clean the valve Manually open the valve Turn the knob as in...

Страница 65: ...ea surrounding the area occur could cause explo sions or fires Carefully check the positioning of the unit The installation of the unit in a place unsuited to support its weight and or guarantee adequ...

Страница 66: ...cks burns and electrocution Open and padlock the general isolator prior to removing the guards and signal work in progress with the appropriate shield Contact with parts that could be under voltage du...

Страница 67: ...t must be disposed of together with all of its parts To dispose of household electrical and electronic equipment the manufacturer recommends you contact an authorised dealer or an authorised ecologica...

Страница 68: ...y authorised per sonnel at existing collection centres Dismantling and disposal THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL When dismantling the unit the fan the mo...

Страница 69: ...ter recirculation 3 Unit keypad 8 Water inlet 3 4 F 13 Probe sump for solar 4 Electric line input 9 Water outlet 3 4 F R Air inlet 5 Condensate drain 10 Solar inlet 3 4 F M Air supply Size 190S Operat...

Страница 70: ...ter recirculation 3 Unit keypad 8 Water inlet 3 4 F 13 Probe sump for solar 4 Electric line input 9 Water outlet 3 4 F R Air inlet 5 Condensate drain 10 Solar inlet 3 4 F M Air supply Size 300S Operat...

Страница 71: ...6 Daily consumption kWh 4 22 6 34 COP EN 16147 2 76 3 01 Clima Warmer Heat pumps Water Heater 3 Domestic hot water profile L XL wh 125 143 Annual consumption AEC kWh 819 1173 Daily consumption kWh 3 8...

Страница 72: ...elegated Regulation N 814 2013 Colder Climate Heat Pump Water Heater 5 Data referred to completely ducted unit 6 Maximum temperature that can be reached during Anti legionella mode Dinsifect It contai...

Страница 73: ...imate conditions 7 Water heating energy efficiency in rounded to the nearest integer and calculated in accordance with point 3 of Annex VIII whereby for solar water heaters and heat pump water heaters...

Страница 74: ...limate conditions 7 Water heating energy efficiency in rounded to the nearest integer and calculated in accordance with point 3 of Annex VIII whereby for solar water heaters and heat pump water heater...

Страница 75: ...cocompatibile Ecodesign co conception Ecodise o 2011 65 UE 2015 863 UE RoHs Unit manufactured and tested according to the followings Standards Unit costruita e collaudata in conformit alle seguenti No...

Страница 76: ...Solar pump control 220 240 Operating logic Note solar pump must be controlled through AC contactor The CN6 is not allowed to drive the pump directly T5U Storage tank temp sensor Upper Unit CN32 in CN6...

Страница 77: ...ough AC contactor The CN6 is not allowed to drive the pump directly T5U Storage tank temp sensor Upper Unit CN32 in CN6 out SOLAR PUMP CN29 60 C Disabled 220 240 220 240 ON ON 65 C 0 0 OFF Enabled OFF...

Страница 78: ...Ethernet cable 5m long For details see instructions ELFOControl3 EVO manual Ethernet 485 converter TERMINATION JUMPER Termination No Yes UNIT Modbus connection Baud rate 9600 Lenght 8 Parity none Stop...

Страница 79: ...it F Setting range 100 158 F Send value actual value 3 Comand Functions BIT15 Reserved BIT14 Reserved BIT13 Reserved BIT12 Reserved BIT11 Reserved BIT10 Reserved BIT9 Reserved BIT8 Reserved BIT7 Reser...

Страница 80: ...Tp Exhaust gas temperature Compressor exhaust temperature Tp unit C Send value actual value unit F Send value actual value C 106 Th temperature Suction Temp Th unit C Send value actual value 2 30 unit...

Страница 81: ...Send value actual value 114 Remaining hot water Segment 0 4 Reserved 115 Auxiliary Status bit 1 BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8 BIT7 BIT6 BIT5 BIT4 BIT3 Wifi Connection Status 1 Connect...

Страница 82: ...temperature Compressor exhaust temperature Tp unit C Send value actual value unit F Send value actual value C 106 Th temperature Suction Temp Th unit C Send value actual value 2 30 unit F Send value...

Страница 83: ...F Send value actual value 114 Remaining hot water Segment 0 4 Reserved 115 Auxiliary Status bit 1 BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8 BIT7 BIT6 BIT5 BIT4 BIT3 Wifi Connection Status 1 Connec...

Страница 84: ......

Отзывы: