CONTROL OPERATION
Horsepower set
Network address set
●
Network address is set by communication of indoor and
outdoor unit; the address is the same as indoor address, there
is no need to set separately.
●
The central control of indoor units can be done on outdoor unit,
there is no need to control indoor unit separately, for details
●
please refer to V4+ outdoor unit manual.
For previous control of indoor units, the network can be set by
connecting (X,Y,E) terminals, there is no need to set network
address. The network can also be set by outer network module
and main board (CN20).
Fig.10-1
Base on different purposes to setting the switch cords on PC panel
of indoor electrical control box. Once finish the setting, please cut off
the main power, and then input power again, otherwise, setting
function could not work.
Table.10-1
HP set switch ENC1 definition list
Code
Indoor unit capacity value
0
2200W(0.8HP)
2
3600W(1.2HP)
5
7100W(2.5HP)
The system together has 64units (0-63), everyone has only
system address code, If two addresses are the same in one
system, the abnormal operation will occur.
Please switch off the power before setting, otherwise
the unexpected error will occur.
CAUTION
Indoor unit
main control panel
1
2
3
4
5
6
7
8
9
A
B
C
CN
9
CN
1
7
J2
J1
CN
1
9
CN
1
8
CN
2
CN
1
3
CN
3
D
E
F