12. SETTING STATIC PRESSURE FOR A6 DUCTS
1.When the unit is in standby, press ‘copy’ button for 3s, the unit will enter into temperature
query status, showing T1.
2.Press ‘+’ and ‘-’ button to select on-way resistance test item (shows AF), then press
‘confirm’ to make the unit will enter into on-way resistance test mode, and runs for
3~6mins, then it will get the on-way resistance.
1.When the unit is in standby, press ‘copy’ button for 3s, the unit will enter into temperature
query status, showing T1.
2.Press ‘+’ and ‘-’ button to select ‘SP ‘to enter into parameter selecting interface. Then press
‘confirm’ button to adjust the parameter.
You can choose 0~4.
0: constant airflow function. Unit adjust the airflow volume automatically to be
the same as standard airflow volume, by adjusting the fan speed.
1: non-constant airflow, airflow decreases as on-way resistance increases
2: non-constant airflow, airflow decreases as on-way resistance increases
3: non-constant airflow, airflow decreases as on-way resistance increases
4: non-constant airflow, airflow decreases as on-way resistance increases
From 1 to 4, static pressure increases.