4.2.3  Basic function

Weekly disinfect function

Under disinfection unit immediately start to heat water up to 70

 

to kill the potential legionella bacteria inside water of tank

,

      

icon will be lightened on the display screen during disinfection; 

Unit will quit disinfection if water temperature is higher than 70

 

and extinguish       icon.

Vacation function:

Press the

button to select VACATION , Unit will automati-

cally heat water to 15

 for the purpose of energy saving during 

vacation days.

Rmote shutdown function:

Users can connect a switch.If the switch is closed, the unit will be 

stopped forcibly.If switch breaks, the unit can run normally 

according settings.

How is the unit running:
If unit is OFF->press          ->unit will be waken->press
to set target water temperature(38-70

)->press

->unit 

will automatically select heat source and start to heat water to 
target temperature.

Restart After a Long Term Stop

When the unit is restarted after a long term stop(trail running 

included), it is normal that outlet water is unclean. Keep the tap on 

and the water will be clean soon.

Fig.4-4

About TCO and ATCO

The power of compressor and E-heater will be automatically 

shut-off or turn on by TCO and ATCO.
If the temperature is higher than 78

, the ATCO will automati-

cally shut off the power of compressor and E-heater, and turn on 

it if the temperature fall down below 68

If the water temperature is higher than 85

, the TCO will 

automatically shut off the power of compressor and E-heater. 

After that it needs to be reset manually.

1)

2)

3)

4)

4.2.4 Query function

For the convenience of maintenance and debug, query function is 
available by Press 3 buttons together:

+         +                 , 

then system running parameters will be shown one by one with 

following sequence by each pushing of

or            button.

Table

.

4-2

When ambient temp below 2

℃,

heat pump and E-heater will 

take different portions of heating capacity, generally the lower of 

ambient temperature, the lower portion of heat pump will be 

taken as well as the higher portion of E-heater will account for.

More detail please refer to Table.4-1.

0

2

4

6

8

10

12

-7 -5

2

7

20

25

30

32

35

40

45

Ti

m

e(

h)

Ambient temp(°C)

15-45
15-55
15-65
15-70

No.

Hour 

low bit

Min. 

high bit

Min. 

Low bit

unit

Explenation

1

Temp.

T5U

2

Temp.

T5L

3

Temp.

T3

4

Temp.

T4

5

Temp.

TP

6

Temp.

Th

7

8

Last error code

9

Previous 1st error or

protection code

10

Previous 2nd t error or

protection code

Model code: 

01 Europe 190

02Europe 300

03 Australia 190

04 Australia 300

End sign

11

12

13

14

15

16

17

18

19

20

21

Temp.

T7

Temp.

T1

Current

Current value

Current

Electric heating 

current value

Fan

Electronic

expansion

valve 1/8

Electronic

expansion

valve

Warm water 

valve1/32

Warm 

water valve

Compressor 

frequency

Frequency

Host software version

Version

Display board 

software version

Version

0

OFF

1

Low fan

2/3:High fan

NOTE

While the ambient temperature below 

than -7

, heat pump efficiency will 

decrease dramatically, the unit will 

automatically shift to E-heater running.

11

Содержание COMPAK KHP-15/190 ACS2

Страница 1: ...y much for purchasing our product Before using your unit please read this manual carefully and keep it for future reference COMPAK KHP 15 190 ACS2 Type Air source Heat Pump Water Heater OWNER S INSTAL...

Страница 2: ...ole disconnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating not exceeding 30mA shall be incorporated in the fixed wiring according...

Страница 3: ...re of this manual When ordering repair parts please always give the following information 1 Model serial and product number 2 Parts name Front Cover Electronic Control Box Compressor Display Cover Ele...

Страница 4: ...ker must be installed adjacent to the power supply Do not remove cover or deface any permanent instructions lables or the data label from either the outside of the unit or inside of unit panels Ask qu...

Страница 5: ...ngers such as water electricity and gas Before wiring pipes Before installation check whether the user s power supply meets the electrical installation requirements of unit including reliable groundin...

Страница 6: ...strong wind The base surface should be flat surface should be inclined no more than 2 and able to bear the weight of the unit and suitable for installing the unit without increasing noise or vibratio...

Страница 7: ...ir flow As an example a room that has an 2 5 tall ceiling and is 3 meter long by 2 meter wide would contain 15m 2 5 Unit outline dimension unit mm 4 2 3 Maintenance space requirements unit mm Fig 2 1...

Страница 8: ...o not dismantle the PT Valve Do not block off the drainage pipe It will cause explosion and injury if do not comply with the above instruction EXPLOSION Water inlet or outlet pipes The spec of the wat...

Страница 9: ...connects to duct air outlet without duct 2 2 5 5 2 2 5 5 Straight line length m Bent pressure drop Pa Bent s qty Straight line pressure drop Pa m Duct Description Duct Round duct Rectangle duct 160 1...

Страница 10: ...e pay attention to the drainage work we sugest to wrap the thermal insulated layer around ouside of the duct For the case of unit with duct the duct total length should be no more than 5m or the maxim...

Страница 11: ...itch are optional 1 After inserting the weak current connection cable group secure the weak current connection cable group using the two cable ties on the right of the junction box see Fig 3 13 2 The...

Страница 12: ...free of leaks Unit completely filled with water Water temperature limit valve or mixer tap recommanded installed per manufacturer s instructions Condensate Drain Line Installation Must be located wit...

Страница 13: ...stop heat pump activate E heater to continually heat water to the target temperature If manually activate the E heater running when heat pump running E heater and heat pump will work together until th...

Страница 14: ...ure is higher than 85 the TCO will automatically shut off the power of compressor and E heater After that it needs to be reset manually 1 2 3 4 4 2 4 Query function For the convenience of maintenance...

Страница 15: ...htened otherwise will be extinguished E heat will be lightened when E heat is running otherwise will be extinguished Solar will be lightened when the machine is connected to the solar signal or connec...

Страница 16: ...Adjust vacation days 1 360 days Switch to HYBRID mode Use this key to switch mode MODE CLOCK TIMER ON OFF DISINFECT No Icon Description 5 CLOCK CLOCK Press this button to enter the clock setting SET...

Страница 17: ...corresponding value will decrease by pushing When setting temperature press more than 1s temperature value will be decreased continuously When Setting clock timer press more than 1s Clock timer value...

Страница 18: ...con to add home appliance to your Comfort Home account Connected to the network Follow the insturctions in the app to set up the WiFi connection If the network connection fails please refer to the App...

Страница 19: ...s not have electric heating function the heat pump available running ambient range is 7 43 if ambient tempera ture is out of range system will show above mentioned signal to let user notice it Q Why s...

Страница 20: ...ture protection Tp 115 Protection active Tp 90 Protection inactive Maybe because of system blocked air or water or less refrigerant leakage in system after repair water temperature sensor malfunction...

Страница 21: ...time please Shut off the power supply Release all the water in water tank and the pipeline and close all the valves Check the inner components regularly 7 2 Recommended regular maintenance table 7 1 M...

Страница 22: ...d around outside of Aluminum microchannel heat exchanger Hydrophilic aluminum fin inner groove copper tube 28W 560 1787mm 3150W Max operating pressure 1 0MPa Water tank cap Water heating cap 1500W 390...

Страница 23: ...is installed at least every 24 months 2 For equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at le...

Страница 24: ......

Отзывы: