Coding
Assembly unit
Coding
Assembly unit
1
Outdoor unit
7
Fill valve (field supply)
1.1
Manometer
8
Balance tank (field supply)
1.2
Pressure relief valve
8.1
Air purge valve
1.3
Expansion vessel
8.2
Drain valve
1.4
Plate heat exchanger
9
Expansion vessel (field supply)
1.5
Backup heater
(
Customized model
)
10
P_o: Outside circulation pump (field supply)
1.6
Air purge valve
11
Collector (field supply)
1.7
Flow switch
17
Bypass valve (field supply)
1.8
P_i: Circulate pump in the unit
19
SV2:2-way valve (field supply)
2
Y-shape filter
23
Mixing station (field supply)
3
Stop valve (field supply)
23.1
P_c: mixing pump
4
Wired controller
FHL 1…n Floor heating loop (field supply)
6
Drain valve (field supply)
FCU 1...n Fan coil units (field supply)
1
1.6
1.5
1.4 1.2
1.3
18
1.8
1.7
1.1
FHL1
FHL2
FHLn
----
----
12.3
12.2
12.1
12.1
2 3
6
7
8.1
8.2
8
9
12
13
14
15
16
10
11
27
26
4
17
22
23
NOTE
● The volume of balance tank(8) should be greater than 40L (for 5~9kW unit, greater than 20L) The drain valve (6)
should be installed at the lowest position of the system. An independent backup heater can be selected and installed
in the door.
● As the temperature sensor attached in the user interface is used to detect the room temperature, the user interface
(4) should be placed in the room where floor heating loops and fan coil units is installed and away from the heating
source. Correct configuration should be applied in the user interface (refer to 10.7 field settings/TEMP. TYPE
SETTING). The first setpoint is water temperature which can be set on the main page of user interface, the second
setpoint is calculated from climate related curves, the target outlet water temperature is the higher one of these two
setpoints. The unit will turn off when the room temperature reaches the target temperature.
●
Pump operation and space heating
The pump (1.8) and (10) will operate when there is request for heating from A and/or B. Pump (23.1) will operate when the
room temperature of zone B is lower than the set point which set in the user interface. The outdoor unit will start operating
to achieve the target water flow temperature.
8.8 Application 8
Space heating application and domestic hot water heating with a solar energy kit connected to the system; space heating is
provided by heat pump, domestic hot water heating is provided by heat pump and solar energy kit.