Ka
ysun Amaz
on Unit
ario T
op Dischar
ge Engineering Da
ta Book
Amazon Unitario Top Discharge
8
3
Combination Ratio
Combination ratio =
Sum of capacity indexes of the indoor units
Capacity index of the outdoor unit
Table 1-4.1: Indoor and outdoor unit combination ratio limitations
Type
Minimum
combination ratio
Maximum combination ratio
Standard indoor units only
Amazon Unitario Top Discharge Series outdoor
units
50%
150%
Notes:
1. When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30%
of the capacity of the outdoor unit and the combination ratio must not exceed 100%.
Table 1-4.2: Combinations of Indoor and outdoor units
Outdoor unit capacit
y
Sum of capacity indexes of
connected indoor units
(standard indoor units only)
Maximum number of connected indoor units
kW
HP
Capacity index
28.0
10
280
140 to 3420
16
33.5
12
335
167.5 to 502.5
20
40.0
14
400
200 to 600
23
45.0
16
450
225 to 675
26
50.0
18
500
250 to 750
29
56.0
20
560
280 to 840
33
59.0
22
590
295 to 885
36
67.0
24
670
335 to 1005
39
73.0
26
730
365 to 1095
43
75.5
28
755
377.5 to 1132.5
46
85.0
30
850
425 to 1275
50
90.0
32
900
450 to 1350
53
Содержание Amazon Unitario Top Discharge
Страница 3: ...Kaysun Amazon Unitario Top DischargeEngineering Data Book Amazon Unitario Top Discharge 2...
Страница 15: ...Kaysun Amazon Unitario Top Discharge Engineering Data Book Amazon Unitario Top Discharge 14...
Страница 184: ...Part 3 System Design and Installation Amazon Unitario Top Discharge 183 Table continued on next page...
Страница 185: ......