Level 2 menu
res
factory data reset
Hold down [+] to restore factory Settings
ou1
Switch 1 signal: (Factory default is HNO)
Hysteresis function: HNO (normally open) /HNC (normally closed)
Window function: FNO (normally open) /FNC (normally closed)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
ou2
Switch 2 signal: (Factory default HNC)
Hysteresis function: HNO (normally open) /HNC (normally closed)
Window function: FNO (normally open) /FNC (normally closed)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
ds1
The opening delay of OUT1. (The factory default is 0s)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
dr1
OUT1 shutdown delay. (The factory default is 0s)
Hold + or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
ds2
OUT2's opening delay. (The factory default is 0s)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
dr2
OUT2 shutdown delay. (The factory default is 0s)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
uni
System standard unit of measurement (display)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
p-n
PNP/NPN switch (Factory default is PNP)
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.
L0
System measurement history minimum.
Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed:
At the press of a button, the value increases; Hold the button down and the value will keep changing.