Chapter 3 Operation Panel
22
Code
Parameter
Function
Explanation
Parameter Value
Factory
Setting
input
Pr.043
Set the rated
speed
for
motor
d0000—d3000
d1500
Pr.044
Set the rated
current
for
motor
d0030—d0120
%
d0100
Pr.045
Set the no
load
current
for motor
d0000—d0099
%
d0040
Pr.046
Torque
compensation
setting
d0000—d0010
d0000
Pr.047
Set the torque
gain
at
accelerating
(whenPr.011=
0)
d0010—d0200
%
d0100
Pr.048
Set the torque
gain
decelerating
((whenPr.011
=0)
d0010—d0200
%
d0100
Pr.049
Set the output
mode
for
multi-function
al relay
d0000
:
get power at faulty, otherwise loss
power
d0001
:
get power at running ,otherwise
loss power d0002
:
get power at specified
frequency ,otherwise loss power
d0003
:
get power at random frequency,
otherwise loss power
d0004
:
get power at specified counter,
otherwise loss power
d0005
:
low voltage attained
d0006
:
over voltage attained
d0007
:
over current attained
d0008
:
non-zero speed attained
d0009
:
DC current braking attained
d0000