Error Messages
(4 of 4)
Error Displayed
Description of Error
The Remote Sensor 2 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem. To clear the error message from the
control, press either the
Menu or Item
button.
REMOTE 2
≠
NONE
The Remote Sensor 3 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem. To clear the error message from the
control, press either the
Menu or Item
button.
REMOTE 3
≠
NONE
This warning message will be displayed if the boiler supply does not increase to the target
temperature within a set time. The time limit is set using the
NO HEAT
item in the Monitor Menu. To
clear this warning, press either the
Menu or Item
button.
This warning message will be displayed if the mixing device operates continuously at full output for a
set time limit. The time limit is set using the
NO HEAT
item in the Monitor Menu. To clear this warning,
press either the
Menu or Item
button.
The Remote Sensor 2 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem. To clear the error message from the
control, press either the
Menu or Item
button.
REMOTE 2
≠
NONE
The Remote Sensor 3 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem. To clear the error message from the
control, press either the
Menu or Item
button.
REMOTE 3
≠
NONE
This warning message will be displayed if the air temperature sensed by an indoor air sensor
exceeds the setting of the
ROOM HOT
item in the Monitor Menu. The control will continue to operate
as normal with this warning. To clear this warning, press either the
Menu or Item
button.
This warning message will be displayed if the air temperature sensed by an indoor air sensor is
below the setting of the
ROOM CLD
item in the Monitor Menu. The control will continue to operate
as normal with this warning. To clear this warning, press either the
Menu or Item
button.