G-SA060-002
3. Specifications subject to change without notice.
4. Under normal conditions, the MODULES may experience conditions that produce more
current and/or voltage than reported at Standard Test Conditions. Accordingly, the values of Isc
and Voc marked on UL Listed MODULES should be multiplied by a factor of 125% when
determining component voltage ratings, conductor capacities, fuse sizes and size of controls
connected to the MODULE output. Refer to Article 690-8 of the National Electrical Code for
an additional multiply factor of 125% (80% derating), which may be applicable.
5.
The type of over current protection is described as Series Fuse 7.0A, Bypass Diode 2.0A.