Adjusting Modes
1.
ALTI Mode – Setting the altitude at which you are using the monitor
1.1.
Press Mode until ALTI flashes
1.2.
Press Mode to alter between m (meters) and ft (feet)
1.3.
Press Up/Down to adjust the altitude (Step=100m/500ft)
1.4
Press Enter to save the setting or leave the ALTI Mode, return to
UserMode.
2.
ALARM Mode – Switching On or Off the Audible Alarm
2.1.
Press Mode until ALARM flashes
2.2.
Press Enter until ALARM “speaker icon” flashes
Press Up/Down to turn the ALARM On or Off
2.3.
Press Enter to save the setting and return to UserMode.
3.
OUTSIDE Mode – Setting the outside level of CO
2
if known
**Note: Ventilation Rate
Ventilation rate represents how much air is introduced into the indoor space
from the outside. Low levels indicate low ventilation rates and potentially
poor air quality. High levels indicate excessive ventilation and potential
excessive energy usage.
To obtain an accurate measurement, readings
should be taken 2~3 hours after occupancy has stabilized in a space or
at a peak in daily CO
2
concentrations.
In indoor air quality control, CO
2
value is an indicator of ventilation rate.
400ppm (Parts Per Million) is the default CO
2
concentration outside
(according to ASHRAE: American Society of Heating, Refrigeration and
Air-conditioning Engineers).
3.1.
Press Mode until OUTSIDE flashes
3.2.
Press Enter until OUTSIDE, CO
2
and PPM flash
Press Up/Down to adjust the reading
3.3.
Press Enter to save the setting and return to UserMode
After modification, the VENT Rate will change.