18
FOR THREE-PHASE DIESEL GENERATOR
Three-phase diesel generator load must be distributed on all three phases, and
the load on all phases must be balanced. The load on 1 phase should not exceed
1/3 of the total generator capacity. Maximum permissible imbalance is 20%.
Only 1 or 2 phase load leads to the generator breakage. The total load and total
current on all three phases should not exceed nominal load and current of the
generator.
CONNECTING DEVICES
After starting the engine, make sure the voltmeter readings correspond to
the nominal (at 50 Hz 230V ±10% for single-phase units and 400 ±10% for
threephase).
1. LED display
2. Emergency circuit breaker
3. Sockets
4. Grounding
5. 3 phase / 1 phase mode switch
(position 1 - 400V, position 0 - off,
position 2 - 230V)
6. Direct current sockets 12 V
7. Engine start key
9.3. GENERATOR PANEL FOR MODELS: KS 7000E 1/3, KS 10000E 1/3