background image

ACD200 Usermanual                                            Functioanl Parameter List 

- 5 - 

Selection 

H0.24 

Starting time of S 

curve 

10.0(%)-50.0(%)

(ACCE and DCCE time ) 

H0.24+H0.25≤90(%) 

0.1(%)  20.0(%) 

○ 

18H 

H0.25 

Risiing time of S 

curve 

10.0(%)-80.0(%)

(ACCE and DCCE time) 

H0.24+H0.25≤90(%) 

0.1(%)  60.0(%) 

○ 

19H 

H0.26 

G/L model set 

  

 

0: model G 
1: model L 

× 

1AH 

H0.27 

Software version  000.0~999.9 

0.1 

Actual 

value 

1BH 

H0.28 

Restore fatory 

settings  

0: no operation  
1: clear fault information 
2: Restore fatory settings (general inverter 
restore factory settings) 

× 

1CH 

H1

H1

H1

H1-

--

- Specified Frequency Function Parametes

 Specified Frequency Function Parametes

 Specified Frequency Function Parametes

 Specified Frequency Function Parametes 

  

 

H1.00 

Analog filter time 

constant 

0.01-30.00s 

0.01s 

0.20s 

○ 

1DH 

H1.05 

Mini. ACI rated 

0.0-H1.07 

0.1% 

0.0% 

○ 

22H 

H1.06 

Mini. ACI rated relative 

frequency 

0.0-Upper Limit Frequency 

0.1 Hz 

0.0Hz 

○ 

23H 

H1.07 

Maxi. ACI rated 

0.0-100.0% 

0.1% 

100.0% 

○ 

24H 

H1.08 

Maxi. ACI rated relative 

frequency 

0.0-Upper Limit Frequency 

0.1 Hz  50.0Hz 

○ 

25H 

H1.09  PULSE maxi. Input pulse 0.1-20.0K 

0.1K 

10.0K 

○ 

26H 

H1.10 

Mini.  PULSE  rated 

0.0-H1.12(Maxi  PULSE  rated) 

0.1K 

0.0K 

○ 

27H 

H1.11 

Mini.  PULSE  rated 

relative frequency 

0.0-Upper Limit Frequency 

0.1 Hz  0.0 Hz 

○ 

28H 

H1.12 

Maxi  PULSE  rated 

H1.10(Mini.    PULSE    rated)  - H1.13(maxi. 
Rated pulse ) 

0.1K 

10.0K 

○ 

29H 

H1.13 

Maxi  PULSE  rated 
relative frequency 

0.0-Upper Limit Frequency 

0.1 Hz  50.0Hz 

○ 

2AH 

H2

H2

H2

H2-

--

-Start,Stop and Brake Parameters

Start,Stop and Brake Parameters

Start,Stop and Brake Parameters

Start,Stop and Brake Parameters 

  

 

H2.00 

Start-up and operation 

mode 

0: star form the staring frequebcy  
1: first brake then star form the staring 
frequebcy 

2: speed tracking start 

× 

2BH 

H2.01 

Starting frequency  0.0-10.0Hz 

0.1Hz 

0.0Hz 

○ 

2CH 

H2.02 

Duration of Starting 

frequency 

0.0-20.0S 

0.1s 

0.0s 

○ 

2DH 

H2.03 

DC brake voltage when 

start 

0-15(%) 

○ 

2EH 

H2.04  DC brake time when start 0.0-20.0S 

0.1s 

0.0s 

○ 

2FH 

H2.05 

Stope mode 

0: stop by DCCE 

× 

30H 

Содержание ACD200 Series

Страница 1: ......

Страница 2: ...lease make sure to cut off the power The electronic components in the inverter are sensitive to static so please do not put anything in the inverter and do not touch the main circuit board After cut o...

Страница 3: ...d Brake Parameters 5 H3 Auxiliary Fuctional Parameters 6 H4 Simple PLC Function Parameters 8 H5 Closed Loop Functional Parameters 9 H6 Termianl FUnction Parameters 10 H7 Specific Traverse Function Par...

Страница 4: ...FWD Forward Runing Order REV Reverse Turn forward and reversely switch value command refer to two wire and three wire control function in H6 08 Optical coupler isolation input Input impedance R 2K MI1...

Страница 5: ...epresent 11 kinds of unit please refer to the parameter description H6 17 the output voltage current is selected by J5 factory setting voltage reference GND Voltage output range 0 10V Carrent output r...

Страница 6: ...dress Address H0 00 Frequency Input Channel Selection 0 operation keypad digital setting 1 terminal UP DOWN adjust and set frequency memorize when power down or stop 2 terminal UP DOWN adjust and set...

Страница 7: ...eed Correction Factor 1 9999 1 100 0EH H0 15 V F Curve Setting 0 conatant torque curve 1 decreasing torque curve 1 2 nd power 2 decreasing torque curve 2 1 7 th power 3 decreasing torque curve 3 1 2th...

Страница 8: ...Maxi ACI rated 0 0 100 0 0 1 100 0 24H H1 08 Maxi ACI rated relative frequency 0 0 Upper Limit Frequency 0 1 Hz 50 0Hz 25H H1 09 PULSE maxi Input pulse 0 1 20 0K 0 1K 10 0K 26H H1 10 Mini PULSE rated...

Страница 9: ...rewquaency compensation 0 150 0 no slip frewquaency compensation 1 0 37H H3 04 Jog operating frequency 0 1 50 0Hz 0 1Hz 5 0Hz 38H H3 05 Jog ACCE time 0 1 60 0s 0 1s 20 0s 39H H3 06 Jog DCCE time 0 1 6...

Страница 10: ...ency Upper limit frequency 0 01Hz 20 0Hz 49H H3 22 Multi frequency 4 Lower limit frequency Upper limit frequency 0 01Hz 30 0Hz 4AH H3 23 Multi frequency 5 Lower limit frequency Upper limit frequency 0...

Страница 11: ...ing time unit 0 second 1 minute 1 000 59H H4 H4 H4 H4 Simple PLC Function Parameters Simple PLC Function Parameters Simple PLC Function Parameters Simple PLC Function Parameters H4 01 Pahse 1 setting...

Страница 12: ...CI analog input 1 1 6AH H5 03 Digital setting of given quantity 0 00 10 00V 0 01 0 00 6BH H5 04 Mini Given quantity 0 0 maxi given quantity relative to percentage of 10 00V 0 1 0 0 6CH H5 05 Mini Give...

Страница 13: ...trol 20 closed loop invalid 21 PLC invalid 22 simple PLC suspension operation control 23 PLC reset when in stop status 24 frequency given channel selection1 25 frequency given channel selection 2 26 f...

Страница 14: ...nter reaches the rated value 19 reaches the set operating time 20 inner timer arrives 1 0 86H H6 12 Fault radiator RA RB RC function selection 0 Inverter is in operating RUN 1 frequency arriving signa...

Страница 15: ...ches given value 0 9999 1 0 95H H6 26 Inner timer timing setting 0 1 6000 0s 0 1 60 0 96H H7 H7 H7 H7 Specific Traverse Function Parameters Specific Traverse Function Parameters Specific Traverse Func...

Страница 16: ...de VF curve 1 0 3200 0Hz 0 01Hz Accordi ng to machine type A2H H8 04 Motor rated speed 1 9999r min 1r min Accordi ng to machine type A3H H8 05 Motor pole number 2 14 2 Accordi ng to machine type A4H H...

Страница 17: ...ion value 0 0 100 0 0 1 0 0 BDH HA 01 Feedback disconnection dealy time 0 0 999 9s 0 1 0 0 BEH HA 02 Remote pressure gauge range 0 00 20 00Mpa 0 01 1 00 BFH HA 03 Sleeping frequency 0 0 99 9Hz 0 1 0 0...

Страница 18: ...al Parameters Secret Code and Manufacturer Functional Parameters Secret Code and Manufacturer Functional Parameters Secret Code and Manufacturer Functional Parameters HE 00 User code 0000 9999 1 0000...

Страница 19: ...ault type ault type P P P Paossible reasons aossible reasons aossible reasons aossible reasons C C C Count ount ount ountermeasures ermeasures ermeasures ermeasures Inverter instantaneous overcurrent...

Страница 20: ...e properly U 05 Inverter accelerate the operating speed and overvoltage Restart the rotating motor Set it as detection restarting function Decceleration time is too short Extend the DCCE time U 06 Inv...

Страница 21: ...d Check the load U 12 Reserved Reserved Reserved U 13 Reserved Reserved Reserved Duct obstrution Clear the duct or improve ventilation The environment tempreture is too high Improve the ventilation lo...

Страница 22: ...es agent for assist U 23 Reserved Reserved Reserved U 25 Disconnection of PID feedback Disconnection of PID feedback Check the feedback wiring PoFF Undervoltage when stop Abnormal input voltage Check...

Страница 23: ...t five times Hd 10 DC bus voltage when the fault happened last time Hd 05 Fault record for the last six times 3 3 Fault Reset 3 3 Fault Reset 3 3 Fault Reset 3 3 Fault Reset When faults happens you ca...