Installation, commissioning and testing quick guide I Jan 1, 2023 | version 1.0 P8
12
C
ONNECTING CABLE TO EXTINGHUISHERS CONNECTOR
The Stat-X KVB extinguisher comes complete with a male socket sub
connector in the top of the extinguisher.
1.
Strip cable jacket of the cable, meant to connected to the NETB
and finish the two wires with insulated crimp bootlace ferrules.
2.
Strip cable jacket at the end of the cable, meant to connected the fire
extinguisher, and finish the two wires with insulated crimp bootlace ferrules.
3.
Follow stricktly the wring specifications of the connetor supplied.
4.
Mount the supplied connector.
5.
Connect the connector to the Stat-X fire extinguisher
6.
Check the connection and measure the resistance from
the other end of the cable (NETB side).
7.
It should be between 1.4 and 2 4 Ohms.
8.
After conducting the point 6 check, connect the cable to the control
electronics NETB CP 10 & CP11 and successively to CP18 & CP 19.
.