![K&G GROEP NANO MARINE Скачать руководство пользователя страница 22](http://html2.mh-extra.com/html/kandg-groep/nano-marine/nano-marine_installation-and-operation-manual_3057869022.webp)
Design Installation Operation Manual NANO/MAR/SYSTEM January 1, 2023 | version 1.2 P
22
26
D
EVICES SUPPORTED BY THE
NMS
26.1
DETECTION DEVICE SUPPORT
The detector types below have been evaluated on the NCP and are approved for such
Part no
Type
Brand
ORB-OP-42001-MAR¹
smoke detector
Apollo
ORB-OH-43001-MAR¹
(optical/heat)
smoke/heat detector
Apollo
ORB-HT-41002-MAR¹
heat 61°C detector
Apollo
ORB-HT-41004-MAR¹
heat 73°C detector
Apollo
ORB-HT-41006-MAR¹
heat 90°C detector
Apollo
ORB-MB-00001-MAR
standard detector base
Apollo
26.2
SOUNDER
/
BEACON DEVICE SUPPORT
Part no
Type
Brand
VTB-32EM-DB-RB/RL (VTB²)
sounder beacon
Cranford
Note:
1
Device input voltage 8
–
22 VDC
Note:
2
Device input voltage 18
–
22 VDC
Always check the specification of the devices before installing them on the NCP.
27
E
NCLOSURE SPECIFICATIONS NCP
- outside enclosure
: 120 x 80 x 58,5 mm w x h x d
- protection class
: IP 65
- color of enclosure
: black RAL 9005
- enclosure material : ABS suitable for outdoor use
- cable gland holes
: 7 predrilled holes