background image

11

Ultra  

1.54

Comfortable indoor climate in high-end interiors

Installation and operating instructions

4. Transport and storage

•  Please note all applicable safety and accident prevention regulations.
• Caution! Risk of sharp edges! Wear gloves, safety shoes and suitable 

protective clothing during transportation!

•  Two people are needed to carry the unit. Caution! Do not carry Ultra unit 

heaters by their louvres! Use suitable means of transport to avoid any 
damage to your health!

•  Please note the information printed on the packaging about storage and 

installing the unit on the ceiling.

Interim storage

Store the units in dry, dust-free and weather-proof rooms without any 
temperature fluctuations.
•  Never stack the units on top of each other to prevent damage to them!
•  Use the original packaging for storage.
•  Store Ultra unit heaters in the position shown on the packaging.

5. Technical data

1)

   Figures in brackets refer when the factory setting is changed to the max. possible speed. This is not suitable for cooling with 

dehumidification!

Technical data • Limits of use for cooling

Series

73

84

85

96

97

Enclosure type

IP 54

IP 54

IP 54

IP 54

IP 54

Water content [l]

1.6 - 2.3

2.0 - 2.9

2.0 – 3.8

2.2 – 4.4

3.3

Weight kg

28 - 30

34 - 43

35 - 45

45 - 55

57

EC model, 230 V series

/

84__33

85__33

96__33

96__34

97__33

AC model, 400 V series

73__36

84__36

85__36

96__36

/

/

AC model, 230 V series

73__16

/

84__16

/

85__16

/

96__16

/

/

/

Nominal speed  
EC model, 230 V rpm

/

1040

980

990

680 (990) 

1)

960

AC model, 400 V rpm

890

680

930

800

820

560

880

680

/

/

/

AC model, 230 V rpm

880

/

940

/

800

/

910

/

/

/

/

Cooling options

EC model, 230 V type

/

843133

853133 
854133

963133 
964133

963134 
964134

973133

AC model, 400 V type

/

843136

853136 
854136

963136 
964136

/

/

AC model, 230 V type

/

843116

/

853116 
854116

/

963116 
964116

/

/

/

Dry cooling

/

yes

yes

yes

yes

yes

yes

yes

yes

yes

Cooling with dehumidification

/

yes

yes

yes

yes

no

yes

yes

yes

yes

Содержание Ultra Series

Страница 1: ...ting instructions Ultra 2 stage three phase motor 1 stage single phase motor EC single phase motor Installation and operating instructions Please retain carefully for future use Read carefully prior t...

Страница 2: ...r optionally also for heating or cooling Ultra series 84 96 for cooling 1 Base cover removable after rotating by 6 2 Cu Al heat exchanger 3 Whisper quiet sickle blade axial fan 4 Whisper quiet sickle...

Страница 3: ...condensation pump 8 2 Safety information 9 3 Scope of delivery 10 4 Transport and storage 11 5 Technical data 11 6 Installation 12 6 1 Installation of the Ultra 12 6 2 Filter assembly 14 6 3 Installa...

Страница 4: ...hanger 37 13 3 Motor 37 13 4 Filter optional accessory 38 13 5 Maintenance of the Ultra for cooling 38 14 Operational faults 41 14 1 All unit heaters 41 14 2 AC single phase motor with motor junction...

Страница 5: ...ve is deemed not to be correct and proper The operator of the unit is solely responsible for any damage arising as a result of this Correct and proper use is also deemed to include compliance with the...

Страница 6: ...ax water temperature C 5 90 Min max air intake temperature C 20 to 40 Min max air humidity 15 75 Max operating pressure bar 16 Min max glycol percentage 25 50 Height when ceiling mounted max approx 4...

Страница 7: ...hnical data To prevent impermissibly severe cooling down of the housing when the fan is at a standstill we would recommend the use of valves e g thermoelectric shut off valve with recirculating mode T...

Страница 8: ...e Note the following limits of use of the condensation pump for the max permitted cooling conditions CHW 6 10 C at entering air temp 27 C 60 rel humidity Ultra series 85 max permitted delivery height...

Страница 9: ...ed to be shorted before working on the electrics The terminals and connectors are still energised even when the unit is switched off Check whether the terminals and connectors are de energised with a...

Страница 10: ...e ruled out despite care during manufacture The operator of the unit is responsible for the EMC conformity of the entire system in accordance with the local applicable standards Modifications to the u...

Страница 11: ...in the position shown on the packaging 5 Technical data 1 Figures in brackets refer when the factory setting is changed to the max possible speed This is not suitable for cooling with dehumidificatio...

Страница 12: ...ermits vibration free suspension consider the use of anti vibration rubber washers for decoupling purposes refer to the table below for the maximum mounting height Maximum mounting height Maximum moun...

Страница 13: ...ew nuts as per the diagram Caution Never lift the unit by the louvres when transporting or installing it Lift the unit under the ceiling and attach it to the brackets by pushing the slots on the brack...

Страница 14: ...ctly onto a solid ceiling and pipes are run under the ceiling the air intake crown cannot be fitted as intended In this case it can optionally either be omitted entirely or adapted on site for instanc...

Страница 15: ...tion The use of flexible pipes such as braided pipe connections spiral or corrugated pipes are recommended in particular when installing the unit under a solid ceiling When used in conjunction with ap...

Страница 16: ...wn in This is drawn off by the condensation pump and discharged along a hose connected on the pressure side Depending on conditions on site the water can be discharged into drainage lines possibly wit...

Страница 17: ...alarm contact are factory wired on the Ultra In the event of an alarm message the KaControl system closes the valve and the fan is switched to stage 1 Ultra for cooling example shows axial fan Conden...

Страница 18: ...he mains voltage Pour water into the condensation tray The pump should switch on automatically and switch itself off again Test the alarm switch add water until the alarm switch is triggered acoustic...

Страница 19: ...cal Wiring Regulations stipulated by the regional energy supply companies Only connect the unit to fixed wiring The operator of the unit is responsible for the EMC conformity of the entire system in a...

Страница 20: ...ver it impermissibly heats up combined with an appropriate protective switch The motor is thus protected against overload operation over and undervoltage unacceptably high ambient temperature and the...

Страница 21: ...relay is energised Contact C NO closed In the event of a fault the relay becomes de energised Contact C NO open There is no fault signal contact in the fans in models 84 and 85 and therefore no fan fa...

Страница 22: ...Ultra Make sure that the motor cable is not pushed through the guard close to the fan Continuously variable power module or KaControl module recirculation air Loosen do not remove the two screws that...

Страница 23: ...left so that the KathermBoard can be removed to the front Electrically wire the unit Install the KathermBoard Position and fix the metal holding strip with the rail for this purpose Commission the un...

Страница 24: ...Several Ultra units even of different sizes can be connected in parallel to a stage switch if the switching power of the stage switch is not exceeded The thermal contacts of all Ultra unit heaters hav...

Страница 25: ...switching units Different switches from our range are available to switch and control the speed of the motors The table at the bottom of page 24 provides an overview of the switching units used their...

Страница 26: ...in parallel to a single phase controller up to the maximum switching power of the single phase controller If several Ultra units are connected to a single phase controller we recommend the use of int...

Страница 27: ...olling the fan motor either via a 0 100 K potentiometer a 0 10 V DC signal or a 0 5 V DC signal The type of control is pre set by a jumper pin To guarantee a reliable start up the fan is operated for...

Страница 28: ...thers the jumper must be connected to 0 5 V on all power units The speed does not behave linear to the control voltage with this setting refer to Fig 3 Input resistance Ri 100 kOhm Fault signal output...

Страница 29: ...e power module are displayed by the LEDs on the power PCB 10 3 2 3 KaControl recirculation air module type 16C1 The KaControl recirculation air module offers the option of controlling the fan motor an...

Страница 30: ...f 100 V AC is factory set The maximum limit can be set as described in Chapter 10 3 2 2 via DIP switches on the power module or alternatively via the KaControl system Maximum permissible cable length...

Страница 31: ...protect personnel when operating the unit with residual current protection devices as well as with frequency converters When power is applied to the unit pulse like capacitor load currents in the int...

Страница 32: ...only for models 96 and 97 In fault mode the relay is energised Contact C NO closed In the event of a fault the relay becomes de energised Contact C NO open There is no fault signal contact in the fans...

Страница 33: ...ns power supply by the master switch 0 10 V DC control signal The 0 10 V DC control signal at input terminals AI2 and GND Ri 20 kOhm on the KathermBoard is interpreted as per Table 9 with regard to sp...

Страница 34: ...rm Board Refer to Table 10 for values Maximum on site fuse 16 A 11 Commissioning 11 1 Pre commissioning checks The base of the Ultra is covered with a transparent film to protect it from damage during...

Страница 35: ...the connecting wires of all thermal contacts individually to check that all thermal contacts are correctly wired If the fan switched off by the thermal contact applies to the 0 100 variable power modu...

Страница 36: ...g maintenance cleaning work 13 1 Housing The Ultra housing is maintenance free Dirt on the housing does not affect the operation of the unit Cleaning is only necessary for aesthetic reasons Opening th...

Страница 37: ...stems assemblies equipment If the defect constitutes an acute danger then do not operate the unit system in its defective state Pay attention to all safety and operating guidelines EN 50 110 IEC 364 w...

Страница 38: ...r and cleaned if necessary produce a maintenance schedule The G3 quality filter is made of plastic and can be beaten to clear off coarse dirt Replace it in the event of more serious dirt The following...

Страница 39: ...e maintenance including cleaning the external pump sump and float switch can be performed without removing the housing cover Simply remove the discharge slats in the discharge field This makes the pum...

Страница 40: ...tion lines if the condensation is seriously contaminated or draining away badly Refer in this respect to the instructions supplied for the condensation pump First loosen the plug in nut to clean to fl...

Страница 41: ...for cooling serious condensation forming outside the condensation tray Fan is not working Room air humidity too high Close the cooling water valve Check the limits of use Fault Possible cause Remedy F...

Страница 42: ...le and control signal 4 V DC Main fuse on the connecting PCB secondary fuse on the connecting PCB fuse on the power PCB and or fuse on the KathermBoard is faulty Check fuses Control voltage poles swit...

Страница 43: ...with a fault signal contact in a group wire contact C NC Fault Possible cause Remedy Fan does not rotate when power is applied to the module and control signal 4 V DC Mechanical blockage Switch off d...

Страница 44: ...Ebert Str 128 130 49811 Lingen Ems Germany T 49 591 7108 660 F 49 591 7108 173 E export kampmann de W Kampmann eu Kampmann UK Ltd Dial House Govett Avenue Shepperton Middlesex TW17 8AG Great Britain T...

Отзывы: