Tandem door air curtains
Door air curtains with patented Tandem technology
Assembly, installation and operating instructions
53
12
List of KaControl parameters
12.1 List of door air curtain parameters
Parameter
Function
Standard
Min.
Max.
Unit
Door air cur-
tain
2
P000
Software version
24
0
255
-
24
P001
Base setpoint for setpoint entry ± 3K
22
8
32
°C
32
P002
Switching on / off hysteresis for valves
3
0
255
K/10
1
P003
Neutral zone in a 4-pipe system (only in automatic mode)
3
0
255
K/10
3
P004
Cooling without fan assistance (natural convection)
0
0
255
K/10
0
P005
Heating without fan assistance (natural convection)
5
0
255
K/10
5
P006
Fan On/Off hysteresis (only in ventilation mode)
5
0
255
K/10
5
P007
P-band for heating
20
0
100
K/10
20
P008
P-band for cooling
20
0
100
K/10
20
P009
Offset to the base setpoint for setpoint input ± 3K
3
0
10
C
3
P010
Clip-on sensor: Limit temperature to activate fan stages 1
and 2 in heating mode
26
0
255
°C
26
P011
Clip-on sensor: Limit temperature to activate fan stages 3
and 4 in heating mode
28
0
255
°C
28
P012
Clip-on sensor: Limit temperature to activate fan stage 5 in
heating mode
30
0
255
°C
30
P013
Clip-on sensor: Hysteresis for limit temperatures
P010, P011, P012, P014
10
0
255
K/10
10
P014
Clip-on sensor: limit value temperature to activate the fan
stages in cooling mode
18
0
255
°C
18
P015
Function of input AI1
0
0
19
-
0
P016
Function of input AI2
0
0
19
-
0
P017
Function of input AI3
0
0
9
-
0
P018
Raise temperature of cooling setpoint in Eco mode
30
0
255
K/10
30
P019
Lower temperature of heating setpoint in Eco mode
30
0
255
K/10
100
P020
ADC limit coefficient
6
0
15
-
6
P021
ADC average coefficient
6
0
15
-
6
P022
Activation/disabling of sun symbol in Comfort mode
0
0
1
-
0
P023
Difference for compensation during cooling
0
-99
127
K/10
0
P024
Coefficient for compensation during heating
0
-20
20
1/10
0
P025
Difference for compensation during heating
0
-99
127
K/10
0
P026
Coefficient for compensation during heating
0
-20
20
1/10
0
P027
Fan setting: maximum run-time for manual fan mode
0
0
255
min
0
P028
Flushing function: fan stage during the flushing function
2
1
5
-
2
P029
Activation of continuous fan mode
0
0
1
-
0
P030
Ventilate temperature activation
12
0
255
°C
12
P031
Ventilation interval
27
0
255
°C
27
P032
Flushing function: maximum idle time of fan
15
0
255
min
15
P033
Flushing function: duration of flushing function
120
0
255
s
120
P034
Flushing function: activation in operating modes
0
0
3
-
0
2
Parameter key for door air curtain SAP no. 9001162, dated 1.05.2019