7.4.3 Cabling of Tandem with KaControl (*C1)
Fuse by others
Mains 230 V/50
Hz
Smartboard PCB
PCB PUR-T-
EC01
Unit no. 1
Door air curtain EC
KaControl (C1)
Shut-off valve 230 V
AC type 100913
Speed controller
Type 30510
Type 3250110
(optional)
Room
temperature
sensor
Door air curtain EC (*00)
Unit no. 2
Shut-off valve 230 V
AC type 100913
To further door air
curtains
(Refer to information
for maximum number)
Potential-free
changeover contact
parametrisable
function
(factory-fitted unit
alarm)
Potential-free contact
wired to digital input DI2
(Optional)
Refer to instructions for
possible functions!
Factory setting speed
increase via door contact
Contact closed = door closed
Potential-free contact
wired to digital input DI1
KaController
Type 3210002
(Optional)
Refer to instructions for
possible functions!
Default setting
Remote ON/OFF
Contact closed = OFF
Cabling information:
• Comply with the details on type of cable and cabling taking into consideration VDE 0100.
* Without * NYM-J. The requisite number of wires including fuse is stated on the cable. No cross-section is specified, cable length is involved in calculation of the cross-section.
• With * IY(ST)Y 0.8 mm. Lay separately from high-voltage cables.
• With ** UNITRONIC BUS LD 0.22 mm2. Lay separately from high-voltage cables.
If you are using different cable types they must be at least equivalent to these.
• Length of BUS cable from the KaController to unit 1: max. 30 m. • Maximum number of parallel units: 6 no. The number can be increased to a maximum of 30 using CANBUS cards type 3260701 needed for each unit (see
accessories).
• Cable length of BUS line from unit 1 to the last unit, maximum 30 m. CANBUS cards type 3260701 needed for each unit (see accessories) maximum 300 m.