Katherm QK - 

Trench convector with energy-efficient EC tangential fan  

 

1.42

Ready-to-install convector-based trench convectors

Assembly and installation instructions

Description of control, Basic settings

The KaControl version provides the option of controlling the 

Ka

therm

 QK by 

means of a control unit supplied separately or on-site building management 
technology.
A number of different settings and configurations are possible using the DIP 
switches on the PCB and parameters that can be set by the control unit.

This manual provides only a brief overview. Please refer to the 

separate KaControl instruction manual for further setting options.

The KaControl system offers the possibility of grouping, although an 
extension board (CANbus), available as an accessory, then needs to be 
provided.

Lay control lines separately from supply lines. 
Use UNITRONIC® BUS LD 2x2x0.22 or similar as data cables. 
Wire the unit in series: star cabling is not allowed.

Table with rating values

Trench 
length

[mm]

QK 190 / QK 215

Power consumption P [W]

Current consumption l [mA]

at fan speed

20%

40%

60%

80%

100%

P [W]

I [mA]

P [W]

I [mA]

P [W]

I [mA]

P [W]

I [mA]

P [W]

I [mA]

1000

3.6

54

4.1

58

4.5

61

5.2

68

6.3

76

1200

3.8

56

4.5

62

5.2

67

6.1

73

7.7

86

1400

4.2

58

4.8

64

6.0

72

7.4

84

9.2

97

1600

4.4

60

5.2

67

6.7

79

8.6

95

10.9

114

1800

4.5

65

5.4

74

6.8

84

8.7

95

11.5

114

2000

4.5

65

5.4

74

6.8

84

8.7

95

11.5

114

2200

6.1

68

7.0

75

7.8

84

8.8

96

12.1

114

2400

6.3

68

7.3

75

8.3

85

10.5

97

13.6

117

2600

6.5

71

7.5

76

8.8

86

11.3

102

15.0

128

2800

6.6

73

7.7

79

9.9

95

12.9

116

17.4

146

3000

6.7

73

8.0

81

10.5

97

13.8

121

19.4

159

3200

6.8

74

8.2

83

10.8

101

14.6

128

21.1

173

The power and current consumption of the actuators (1 W) is not taken into account.

Содержание Katherm QK

Страница 1: ...Katherm QK Trench convector with EC tangential fan Assembly and installation instructions Keep these instructions in a safe place for future use I605 12 18 EN I SAP No 1334273...

Страница 2: ...lance 17 11 2 Electrical wiring 17 11 3 24 V electromechanical model 18 11 4 230 V electromechanical model 21 11 5 KaControl model 24 11 5 1 Single circuit controls 28 12 Declaration of Conformity 33...

Страница 3: ...ded use is deemed to include observing the installation instructions described in these instructions The installation of this product requires specialist knowledge of heating cooling ventilation and e...

Страница 4: ...uctivity 1 S cm 700 Oxygen content O2 mg l 0 1 Hardness dH 4 8 5 Sulphur ions S not measurable Sodium ions Na mg l 100 Iron ions Fe2 Fe3 mg l 0 1 Manganese ions Mn2 mg l 0 05 Ammonia ions NH4 mg l 0 1...

Страница 5: ...ion Disconnect all parts of the system that are being worked on Ensure that the system cannot be accidentally re connected Before commencing installation maintenance work wait until the fan has come t...

Страница 6: ...r Important Do not remove bracing during installation and operation Arrange the Katherm QK with the convector on the window side Important The height adjustment feet are already fitted to the trench c...

Страница 7: ...g and fixing at the installation site Move the Katherm QK into its final installation position 1 Pay attention to the prescribed spacings to walls and fa ades 2 and 3 on site Align the Katherm QK into...

Страница 8: ...ons Remove the punched pipe opening Screw on the thermostatic valve and return shut off valve without the need for additional sealing to the Eurokonus valve connection on the convector Then fit the fl...

Страница 9: ...d openings of the trench convector are sealed when using screed or other low viscosity floor coverings Important Do not allow screed or the floor to press the floor trench Provide expansion joints if...

Страница 10: ...settable 4 Thermoelectric actuator 24 V type 146906 5 1 2 return shut off valve straight type 145952 6 Unit shown with roll up grille 7 Pipe openings for water connection punched 8 Electrical cable op...

Страница 11: ...ctuator 24 V type 146906 5 1 2 return shut off valve straight type 145952 6 Unit shown with roll up grille 7 Pipe openings for water connection punched 8 Electrical cable openings punched 9 Alternativ...

Страница 12: ...0 2 4 2200 2 4 2400 2 4 2600 2 5 2800 2 5 3000 2 5 3200 2 5 9 Supply air modules Katherm QK Combination of Katherm QK with supply air module 1 Supply air module with supply air spigot 2 Connecting bra...

Страница 13: ...drawing on the left shows 4 different slider positions 100 75 50 and 30 opened They are also shown in the design diagrams below in which the pressure losses sound levels and airflows can be seen Inte...

Страница 14: ...currently in force Regularly maintain and inspect Katherm QK units to ensure their proper function and performance Important Disconnect and de energise all equipment before commencing maintenance work...

Страница 15: ...n the fins impairs the airflow heat transfer and thus also the output of the unit Carefully vacuum the heat exchanger if dirty Do not use water to clean the heat exchanger Caution Fins bend easily 10...

Страница 16: ...rently applicable VDE and EN guidelines as well as Technical Wiring Regulations stipulated by the regional energy supply companies Only connect the unit to fixed cables Only use the room or clock ther...

Страница 17: ...cable cross sections The cable cross sections basically depend on the fuses for the cable length and the wiring capacity of the electric motors on site Lay control lines separately from supply lines U...

Страница 18: ...g diagram supplied with the unit Close the housing of the control box 11 3 24 V electromechanical electrical model Model for complete in situ control of the Katherm QK Product features The operating v...

Страница 19: ...3 5 51 4 4 59 5 8 70 7 7 85 10 5 104 2000 3 5 51 4 4 59 5 8 70 7 7 85 10 5 104 2200 5 1 57 6 0 64 6 8 71 7 8 86 11 1 105 2400 5 3 57 6 3 65 7 3 72 9 5 88 12 6 108 2600 5 5 60 6 5 66 7 8 76 10 3 93 14...

Страница 20: ...ent in manual and automatic operating mode including automatic summer winter changeover and a day or week program Fig Clock thermostat type 30456 Electrical cabling Control via clock thermostat type 3...

Страница 21: ...usly variable parallel control of max 10 Katherm QK 230 V electromechanical models room temperature and fan presetting using dials temperature setting range 5 30 C IP30 rated voltage 230V 50Hz max cur...

Страница 22: ...r supply W2 Control signal for fan and actuator Subject to technical modifications Refer to the control accessory documentation in the event of deviation from the circuit diagrams 3 W1 W2 4 Automation...

Страница 23: ...es W1 power supply W2 Control signal for fan and actuator W3 Operating mode changeover optional Subject to technical modifications Refer to the control accessory documentation in the event of deviatio...

Страница 24: ...l from the on site building management system is alternatively possible Motor protection Any faults with the motor e g overloading are analysed by the electronics within the EC motor This then switche...

Страница 25: ...sory then needs to be provided Lay control lines separately from supply lines Use UNITRONIC BUS LD 2x2x0 22 or similar as data cables Wire the unit in series star cabling is not allowed Table with rat...

Страница 26: ...sory and can be used as a changeover sensor If used set the DIP switch to ON No clip on sensor fitted OFF 4 Heating Cooling External changeover ON ON If the function is activated the operating mode of...

Страница 27: ...bus lines when the unit is fully disconnected DIP switch setting The DIP switches on the rear of the KaController should be set according to the illustration at the side DIP switch no 1 ON DIP switch...

Страница 28: ...control of up to 30 units Subject to technical modifications Refer to the control accessory documentation in the event of deviation from the circuit diagrams Single circuit control of up to 6 units W4...

Страница 29: ...engths with a group of up to 6 individual units Total length of BUS cables between the Katherm QK units max 30 m Total length of BUS cable between the room control unit and master unit max 30 m Total...

Страница 30: ...2 x 2 x 0 22 or of the same value separately from power cables W1 power supply W2 Control signal for fan and actuator Subject to technical modifications Refer to the control accessory documentation i...

Страница 31: ...e with side keys and one without Both control units can be used to call up all functions with the keys offering the possibility of quick access to some functions No Description 1 Display of the operat...

Страница 32: ...re Confirm the entry by pressing the navigator dial Fan speed Change by pressing the side fan button or using the navigator dial Briefly press the navigator dial once Turn the navigator dial to the le...

Страница 33: ...33 37 0 6 0 006 28 28 31 36 39 0 8 0 007 28 28 33 38 41 0 9 0 007 28 29 34 39 43 0 9 0 007 28 29 34 39 43 1 2 0 008 28 30 36 40 44 1 3 0 008 28 31 37 41 45 1 5 0 009 28 32 38 42 45 1 6 0 010 29 33 39...

Страница 34: ...34 1 42 Katherm QK Trench convector with energy efficient EC tangential fan Ready to install convector based trench convectors Assembly and installation instructions...

Страница 35: ...35 Katherm QK Trench convector with energy efficient EC tangential fan 1 42 Ready to install convector based trench convectors Assembly and installation instructions...

Страница 36: ...n eu katherm qk Kampmann co uk katherm qk I605 12 18 EN I SAP No 1334273 Kampmann GmbH Friedrich Ebert Str 128 130 49811 Lingen Ems Germany T 49 591 7108 660 F 49 591 7108 173 E export kampmann de W K...

Отзывы: