25
Katherm QK -
Trench convector with energy-efficient EC tangential fan
1.42
Ready-to-install convector-based trench convectors
Assembly and installation instructions
Description of control, Basic settings
The KaControl version provides the option of controlling the
Ka
therm
QK by
means of a control unit supplied separately or on-site building management
technology.
A number of different settings and configurations are possible using the DIP
switches on the PCB and parameters that can be set by the control unit.
This manual provides only a brief overview. Please refer to the
separate KaControl instruction manual for further setting options.
The KaControl system offers the possibility of grouping, although an
extension board (CANbus), available as an accessory, then needs to be
provided.
Lay control lines separately from supply lines.
Use UNITRONIC® BUS LD 2x2x0.22 or similar as data cables.
Wire the unit in series: star cabling is not allowed.
Table with rating values
Trench
length
[mm]
QK 190 / QK 215
Power consumption P [W]
Current consumption l [mA]
at fan speed
20%
40%
60%
80%
100%
P [W]
I [mA]
P [W]
I [mA]
P [W]
I [mA]
P [W]
I [mA]
P [W]
I [mA]
1000
3.6
54
4.1
58
4.5
61
5.2
68
6.3
76
1200
3.8
56
4.5
62
5.2
67
6.1
73
7.7
86
1400
4.2
58
4.8
64
6.0
72
7.4
84
9.2
97
1600
4.4
60
5.2
67
6.7
79
8.6
95
10.9
114
1800
4.5
65
5.4
74
6.8
84
8.7
95
11.5
114
2000
4.5
65
5.4
74
6.8
84
8.7
95
11.5
114
2200
6.1
68
7.0
75
7.8
84
8.8
96
12.1
114
2400
6.3
68
7.3
75
8.3
85
10.5
97
13.6
117
2600
6.5
71
7.5
76
8.8
86
11.3
102
15.0
128
2800
6.6
73
7.7
79
9.9
95
12.9
116
17.4
146
3000
6.7
73
8.0
81
10.5
97
13.8
121
19.4
159
3200
6.8
74
8.2
83
10.8
101
14.6
128
21.1
173
The power and current consumption of the actuators (1 W) is not taken into account.