The function of digital inputs DI1 and DI2 can be configured using
parameters settings.
Parameter P43
Parameter P43 is used to set the function of the digital input DI1.
20.6 Function of digital inputs DI1 and DI2
20.6.1 Function of DI1
Function
Standar
d
Min
Max
Unit
P43 Function of DI1
0 = no function
1 = ON/OFF
(contact open
ON)
2 = Winter/summer
(contact open
heating)
3 = Eco/day mode
(contact open
day)
4 = no function
(contact open
no function)
5 = Condensation alarm
(contact open
no condensation)
6 = General alarm
(contact open
no alarm)
7 = Ext. frost protection monitor (contact open
no frost)
8 = ON/OFF
(contact closed
ON)
9 = Heating/cooling changeover (contact closed
heating)
10 = Eco/Day mode
(contact closed
day)
11 = no function
(contact closed
no function)
12 = Condensation alarm
(contact closed
no condensation)
13 = General alarm
(contact closed
no alarm)
14 = Ext. frost protection monitor (contact closed
no frost)
1
0
14