46
1.43
Katherm HK
Ready-to-install trench heaters with EC tangential fan
Assembly and installation instructions
14.8 Timer programs
The KaController provides the option of programming switching on and
off times using a timer program if rooms are only to be air conditioned
during certain times of the day. Unlike with conventional thermostatic
controllers where only one switching on and off time can be selected, two
switching on and off times can be set for each day.
The KaController can manage 2 switch-on and 2 switch-off times per day.
The switching on and off times can be entered as a block or individually
for each day.
The diagram below shows the sequence for setting the timer program.
Steps 1-4 are described in more detail in the next section.
1
ON = SWITCH ON timer program OFF =
SWITCH OFF timer program
2
1 = Timer program no. 1 2 = Timer program
no. 2
3
Clock for switching on/switching off time
4
Weekday
5
If no switch-on or off time is entered in the
timer program matrix, the "Clock" symbol is
hidden in the default view.
Display elements in the "Timer programs"
selection menu
ON1
OFF1
ON2
OFF2
MO
6 : 00
18 : 00 – – : – – – – : – –
TU
6 : 00
18 : 00 – – : – – – – : – –
WE
6 : 00
18 : 00 – – : – – – – : – –
TH
6 : 00
18 : 00 – – : – – – – : – –
FR
6 : 00
18 : 00 – – : – – – – : – –
SA
8 : 00
14 : 00 – – : – – – – : – –
SU
– – : – – – – : – – – – : – – – – : – –
Timer matrix
Example of a weekly timer program
Timer start
screen
Enter day of
the week
Step 1
Step 2
Step 3
Step 3
Step 4
Step 4
Enter timer
program no.
Input timer
program no. 1
switch-on time
Input timer
program no. 2
switch-on time
Input timer
program no. 1
switch-off time
Input timer
program no. 2
switch-off time
1
5
4
3
2
Set the time in the "Time setting" selection menu before
parametrising the switch-on and off times.
If no switch-on or off time is entered in the timer program matrix,
the "Clock" symbol is hidden in the default view.
To exit the "Timer programs" selection menu, press and hold
down the navigator dial for 3 seconds in the timer program start
screen or do not use the KaController for 15 seconds.
The timer program switches the controller on and off in
accordance with the timer entries. After switching off the
controller using the timer program, the user then has the option of
switching the controller on using the ON/OFF key or the navigator
dial.