KaDeck
Assembly, installation and operating instructions
33
Refer to these points in the following layout plans with electromechanical control:
Comply with the details on cable types and cabling with due consideration of VDE 0100.
Without *: NYM-J. The requisite number of wires, including PE conductor, is stated on the cable. Cross-sections are not
stated, as the cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y, 0.8mm, max. 50 m. Lay separately from high voltage lines.
With ***: J-Y(ST)Y, 0.8 mm, max. 30 m. Lay separately from high voltage lines.
With ***: J-Y(ST)Y, 0.8 mm, max. 10 m. Lay separately from high voltage lines.
With ****: UNITRONIC® BUS LD 2x2x0.22 mm². Lay separately from high voltage lines.
If other types of cables are used, they must be at least equivalent.
The terminals on the unit are suitable for a maximum wire cross-section of 2.5 mm².
All RCCBs used must at least be mixed frequency-sensitive (type F). Refer to the provisions of DIN VDE 0100 Parts 400
and 500 when designing the rated fault current.
Note the electrical data when rating the in-situ mains power supply and fuse (C16 A, max. 10 units).