Installation and Connection
Installation (general)
Installation (general)
The ceiling cassette can be installed within a suspended ceiling
or under a bare concrete ceiling (without a suspended ceiling
construction). Observe the minimum clearance to the bare ceiling.
Firstly, you need to calculate the cooling or heating load of the
room and select the appropriate ceiling cassette (also from an
acoustic point of view).
After selecting the cassette, determine the optimum position
in the room; observe the throw data (see technical catalogue).
In addition, ensure that draughts are minimised when selecting
the position!
If more than one ceiling cassette is installed in each room, the
cassettes need to be staggered to to avoid them affecting each
other.
The ceiling cassette needs to be installed horizontally. No ob-
jects, such as cupboards, must be located under the ceiling cas-
sette that may minimise the air intake.
Direct radiated heat on the cassette (and temperature sensor)
from lamps or windows must be avoided.
Unit size
Model 1–3
Model 4–6
A
min. 296 mm
min. 329 mm