INSTALLATION AND OPERATING INSTRUCTIONS
INSTALLATION AND OPERATING INSTRUCTIONS
1.96
26
Door air curtains
DIP switch no. 1
Dip switch no. 1 must be set to ON to actuate a door air curtain by means of 0…10 V signals
within a building management system provided by others.
The parameter settings required are described in Section 11.3.14.
Factory setting: DIP1=OFF
DIP switch no. 2
It is essential that DIP switch no. 2 is set to OFF.
Factory setting: DIP2 = OFF
DIP switch no. 3
A clip-on sensor can be connected as a frost protection sensor to provide frost protection. In this
case, DIP switch no. 3 has to be set to ON.
Factory setting: DIP3=OFF
DIP switch no. 4
Summer mode / winter mode changeover is set as standard using the KaController.
Alternatively, summer mode / winter mode changeover can also be performed by an external
thermostat or an external switching contact. In this case, DIP switch no. 4 has to be set to ON.
DIP4=ON + External thermostat contact open --> Winter mode
DIP4=ON + External thermostat contact closed --> Summer mode
Factory setting: DIP4=OFF (no external thermostat fitted)
DIP switch no. 5
It is essential that DIP switch no. 5 is set to OFF.
Factory setting: DIP5=OFF
DIP switch no. 6
The room temperature can be detected by the KaController or an external KaControl room
temperature sensor. DIP switch no. 6 has to be set to ON to detect the temperature using the
KaController.
If an external temperature measurement is set and no temperature sensor is fitted, a fault
message will be issued.
Factory setting: DIP6=ON