Ka
Control
for Door Air Curtains
INSTALLATION AND OPERATING INSTRUCTIONS
INSTALLATION AND OPERATING INSTRUCTIONS
1.96
24
Door air curtains
8.
Addressing
8.1
Single-circuit Controls of up to 6 Units
8.1.1 Maximum 6 door air curtains in one control zone
• Door air curtains in single-circuit controls with a maximum of 6 units
need not be addressed.
• The master unit / slave unit is defined by the connection of the
KaController.
• Connecting a KaController to it automatically converts the respective
door air curtain into the master unit in the control circuit.
• A master unit must not necessarily be arranged at the end of a bus
system.
• Lay all BUS cables in a linear pattern. Star-shaped wiring is not
permitted.
Slave unit
#1
Slave unit
#2
Slave unit
#3
Slave unit
#5
Master unit
#4
Slave unit
#6
2**
2**
2**
2**
2**
3**
Master unit
#1
Slave unit
#2
Slave unit
#3
Slave unit
#5
Slave unit
#4
Slave unit
#6
2**
2**
2**
2**
2**
3**
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1
KaControl
C1