Airblock FG  

1.50

Slimline air handling unit for decentralized, dynamic air treatment

Installation and Operating Instructions

Cleaning the heat exchanger:

•  Blast the Airblock CU/AL heat exchanger with appropriate compressed 

air or flush the heat exchanger with a suitable medium to remove 
accumulated dust. Proceed extremely carefully as the aluminium fins 
bend very easily and then restrict the air flow! (Bent fins have to be 
straightened with an appropriate tool).

10.5.5 Filter Change (Optional)

Observe the safety information on page 37, sections 10.5.1 and 10.5.2! 
Filter cartridge in a Fiberplast frame 

6

 (optional with the chiller unit).

If your chiller module is fitted with a filter:
•  Check the filter cartridge 

6

 at least once a year (more often if necessary). 

The filter cartridge must be changed if it is dirty.

•  Open the service hatch 

4

 and unlock the safety catches. Pull out the filter 

cartridge downwards. Use a collection bag if necessary to avoid dirt and 
dust dropping down.

•  This filter folds in the middle with model 9 units. This makes it easier to 

remove and it can be folded to save space with disposal so that very little 
dirt can drop out.

•  Push the replacement filter cartridge into the filter opening and lock the 

filter catches. Replacement filter cartridges are available as accessories. 
Filter cartridges cannot be recycled.

• Dispose of the dirty filter. Filter cartridges are metal-free and fully 

incinerable.

Содержание Airblock FG 06

Страница 1: ...C single phase motor Airblock FG modules for heating cooling and ventilating Installation and Operating Instructions Keep these instructions in a safe place for future use Kampmann de installation_man...

Страница 2: ...ning the Fan Modules 23 8 Connecting Airblock Modules 24 9 Heat Recovery Module 25 9 1 Unit Construction 25 9 2 Installation 26 9 3 Control Components 27 9 4 Maintenance 27 9 4 1 Safety Information 28...

Страница 3: ...t Exchanger 38 10 5 5 Filter Change Optional 39 11 Bag Filter Module 40 11 1 Unit Construction 40 11 2 Installation 41 11 3 Control Components 42 11 4 Maintenance 43 11 4 1 Safety Information 43 11 4...

Страница 4: ...tallation Check the application with the manufacturer in case of any doubt Any use other than the use specified above is deemed not to be correct and proper The operator of the unit is solely responsi...

Страница 5: ...between the mains conductor and protective conductor connection after disconnecting the mains supply with the parallel connection of several fans e g model size 7 and 9 Ensure that sufficient protect...

Страница 6: ...FG with attachments can be used for cooling CPW direct evaporator or as an overpressure system with a particle filter class H13 for food stores A bag filter module ISO ePM10 85 in accordance with DIN...

Страница 7: ...e pipe connection unit 4 Standard System Set up Example 1 Mixed air system Installation in a suspended ceiling fresh air intake through the wall horizontal installation of the Airblock FG supply air m...

Страница 8: ...n of the Airblock FG supply air module in a suspended ceiling Fresh air intake via a weather protection grille through the wall Air routing through the heat recovery module for controllable heat recov...

Страница 9: ...option for a droplet separator optional Filter insert ISO Coarse 90 optional can be used as a pre filter in the filter holder of the chiller module Downstream particle filter H13 Air discharge throug...

Страница 10: ...e transmitter optional accessory 5 Supply Air Module incl Heat Exchanger and ISO ePM2 5 65 Filter 5 1 Unit Construction Airblock FG supply air module Fig Securing the suspension brackets The service h...

Страница 11: ...e area heating medium electrical connection 13 14 3 etc Provide rubber pads on site to decouple noises Align the unit in a horizontal position Please note the following The filter 11 can only be remov...

Страница 12: ...technology these must be sensitive to all types of current type B We recommend a tripping current of 300 mA and time delayed tripping super resistant characteristic K for optimum operating safety Fir...

Страница 13: ...protection thermostat 0F0 Model 6 30468 Models 7 8 9 30668 enclosed Filter differential switch for use with supply air module type 300300 chiller module type 302140 heat recovery module type 301700 pa...

Страница 14: ...not stand within the swivel range of the hatch Caution Two people are needed to open the service hatch 4 The hatch weights up to 20 kg depending on the model Never open the service hatch further than...

Страница 15: ...ting instructions for more information Remove the protection securing the system from being switched on after completing the work 5 6 5 Cu Al Heat Exchanger The heat exchanger 12 requires no maintenan...

Страница 16: ...ety catches Pull out the filter cartridge ISO ePM2 5 65 downwards Use a collection bag if necessary to avoid dirt and dust dropping down This filter folds in the middle with model 9 units This makes i...

Страница 17: ...flow 6 Exhaust Air Module 6 1 Unit Construction The service hatch and screw on hinges can be rotated 180 and fitted on site depending on the space requirements the screw in hinges can be fixed to the...

Страница 18: ...on site below and alongside the modules connection side in the case of suspended ceilings or encased units for the installation and maintenance of the Airblock modules 6 3 Electrical Wiring Damage ca...

Страница 19: ...0 or power failure message A fan error message is signalled for models 8 and 9 regardless of the control type Electrical data for EC motor Type Voltage frequency Max current Output 06300300 06300600 2...

Страница 20: ...technical information for technical data on the following accessories delivered separately or fitted at the factory Description of accessory Type suffix for Airblock type Type of accessory spare part...

Страница 21: ...not stand within the swivel range of the hatch Caution Two people are needed to open the service hatch 4 The hatch weights up to 20 kg depending on the model Never open the service hatch further than...

Страница 22: ...block is maintenance free The motor s ball bearings sealed on both sides are greased for life In contrast deposits on the fan and inlet nozzle reduce the air volume and must be removed Unscrew the tur...

Страница 23: ...on on the commissioning of other parts of the system The Airblock can be put into operation after conducting the above checks by switching on the power supply to the motor terminal box switching on th...

Страница 24: ...n steps for a connection point The corners of the housing can be accessed through the service hatch The filter inserts ISO ePM10 70 ISO ePM2 5 65 or H13 must be removed from the module if necessary to...

Страница 25: ...4 Service hatch pre fitted indicated as an opening 5 Housing 6 Bypass flap 7 Screw on hinge for service hatch 2 no pre fitted 8 Connecting strut on air discharge side 9 Connecting strut on air intake...

Страница 26: ...collecting line via the siphon connected to the condensation drain connection Condensation must be able to drain freely Make sure that the condensation drain connection has an appropriate free area L...

Страница 27: ...prescribed by the legislature The intervals are dependent on various factors e g structural conditions level of dirt etc and may therefore differ from the manufacturer s recommendations If an increas...

Страница 28: ...nd within the swivel range of the hatch Caution Two people are needed to open the service hatch 4 The hatch weights up to 20 kg depending on the model Never open the service hatch further than 90 Step...

Страница 29: ...nnection side and remove it in a downward direction Please note that residual water may remain in the condensation tray 3 Remove the counterflow heat exchanger unscrew the wing screws 2 no until the c...

Страница 30: ...30 1 50 Airblock FG Slimline air handling unit for decentralized dynamic air treatment Installation and Operating Instructions Unscrewing the central support Removing the condensation tray details...

Страница 31: ...31 Airblock FG 1 50 Slimline air handling unit for decentralized dynamic air treatment Installation and Operating Instructions X X Removing the condensation tray Removing heat recovery units...

Страница 32: ...are fully opened to the bottom swivel range 1780 mm To do this the slide in rail in which the filter sits can be swivelled 10 The filter can be pulled out easily in a downward direction in a swivelle...

Страница 33: ...ndensation tray 10 Direction of air flow 11 Connecting strut on air discharge side 12 Connecting strut on air intake side 13 Screw on hinge for service hatch 2 no pre fitted 14 Condensation tray The s...

Страница 34: ...pes valves connections all the way to the unit with vapour diffusion tight insulation Only use suitable pipe brackets for cooling mode refrigeration clamps Install safety related components e g expans...

Страница 35: ...g for connecting the heat exchanger Hold the connections on the heat exchanger with a wrench or other suitable tool when connecting the pipework Make sure that there is adequate working space for the...

Страница 36: ...spare part supplied separately Enclosed technical information from manufacturer Frost protection thermostat 0F0 Model 6 30468 Models 7 8 9 30668 enclosed Filter differential pressure switch for use wi...

Страница 37: ...tches are fitted on the top and underside of the units to ensure optimum accessibility for maintenance purposes Stand on a solid surface to carry out maintenance on the Airblock FG e g a lifting platf...

Страница 38: ...rvice hatches 4 on the top and underside 10 5 4 Cu Al Heat Exchanger The heat exchanger 3 requires no maintenance if the system is properly maintained i e if the filter is monitored and changed regula...

Страница 39: ...ional with the chiller unit If your chiller module is fitted with a filter Check the filter cartridge 6 at least once a year more often if necessary The filter cartridge must be changed if it is dirty...

Страница 40: ...hatch and screw on hinges can be rotated 180 and fitted on site depending on the space requirements the screw in hinges can be fixed to the connecting strut on the air discharge side and the connecti...

Страница 41: ...ling tape are included in the delivery Several Airblock filter or chiller modules can be screwed together from the inside using the connection sets included Make sure that there is adequate working sp...

Страница 42: ...of accessory Type suffix for Airblock type Type of accessory spare part supplied separately Enclosed technical information from manufacturer Filter differential pressure switch for use with supply ai...

Страница 43: ...Do not stand within the swivel range of the hatch Caution Two people are needed to open the service hatch 4 The hatch weights up to 20 kg depending on the model Never open the service hatch further th...

Страница 44: ...11 4 4 Filter Change Check the filter cartridge ISO ePM10 85 3 at least once a year more often if necessary The bag filter must be changed if it is dirty To do this open the service hatch 4 of the bag...

Страница 45: ...rticle Filter Module 12 1 Unit Construction Airblock FG particle filter module The service hatch and screw on hinges can be rotated 180 and fitted on site depending on the space requirements the screw...

Страница 46: ...ling tape are included in the delivery Several Airblock filter or chiller modules can be screwed together from the inside using the connection sets included Make sure that there is adequate working sp...

Страница 47: ...of accessory Type suffix for Airblock type Type of accessory spare part supplied separately Enclosed technical information from manufacturer Filter differential pressure switch for use with supply ai...

Страница 48: ...Do not stand within the swivel range of the hatch Caution Two people are needed to open the service hatch 4 The hatch weights up to 20 kg depending on the model Never open the service hatch further th...

Страница 49: ...t once a year and replaced on reaching the filter service life or final pressure drop To do this open the service hatch 4 on the particle filter module Then loosen the clamping rod on the clamping mec...

Страница 50: ...06013250 07013250 08013250 09013250 Replacement filter cartridge ISO ePM2 5 65 for heat recovery supply air and compact filter module in Fiberplast frame 06013270 07013270 08013270 09013270 Descriptio...

Страница 51: ......

Страница 52: ...ngen Ems Germany T 49 591 7108 0 F 49 591 7108 300 E info kampmann de W Kampmann de Kampmann UK Ltd Dial House Govett Avenue Shepperton Middlesex TW17 8AG Great Britain T 44 0 1932 228592 F 44 0 1932...

Отзывы: