13
Electronic continuously variable speed controller
1.96
recirculating air with digital timer and room temperature control, type 30515
Assembly and installation instructions
Important:
After a power failure with the fan, a fault message will
continue to appear for approx. 10 seconds after the power has been
re-established. This can only be acknowledged after this time has
expired. A motor fault is only issued if there is a fault for longer than
1 minute or at least 3 times within a minute.
3 Day mode temperature setting
Setting the required room temperature during the day mode phase.
4 Night mode temperature setting
Setting the required room temperature night setback in heating mode
or night step-up in cooling mode during the night mode phase.
Fig. 6: Indicator light
flashing code
1,0 s
ARRÊT
Appareil arrêté
ou absence de courant
Lumière continue verte,
prêt à l'emploi
Lumière verte clignotant lentement,
pas de validation
Lumière verte clignotant rapidement,
mode ventilation
Lumière verte clignotant,
mode hiver (chauffage)
Lumière verte clignotant très rapidement,
mode été (refroidissement)
Lumière clignotant vert-rouge,
alarme de condensat
Lumière continue rouge,
anomalie du moteur EC
Lumière rouge clignotant,
alarme antigel ou protection
contre le refroidissement ambiant
Lumière rouge clignotant très rapidement,
erreur capteur ambiant ou antigel
OFF
Unit switched off or
no voltage connected
Green – light permanently on,
ready for operation
Green – long flashing,
no activation
Green – short-long flashing,
ventilation mode
Green – flashing,
winter mode (heating)
Green – blinking,
summer mode (cooling)
Green-Red – blinking,
condensation alarm
Red – light permanently on,
EC motor fault
Red – blinking,
frost alarm or room cooling-down protection
Red – blinking,
room or frost sensor fault