INHIBITION AND CORROSION PROTECTION 

 

 

 

IMPORTANT 

 
1. The system is now full of fresh, clean water, and in 

line with Building Regulations Part L : 2006, a 
good quality corrosion inhibitor, such as 
SYSTEMSAFE DM, must be added to the system 
water to prevent further corrosion and scaling. 

 

To comply with Benchmark documentation, 
inhibitors must have passed the DWTA  
(Domestic Water Treatment Association) product 
performance standard and can be identified by 
this logo on the pack. 
 

 

 

The inhibitor may be added to the system by 

using the Quantum pump as follows: 

 
2. Briefly open a dump valve to lower the water level 

in the tank to just above the minimum level, close 
the dump valve. Add the SYSTEMSAFE DM 
inhibitor into the tank. Allow circulation through 
the system for ten minutes, isolate the flushing 
pump from the heating system, and switch off. 

 
3. If the system is vented, the residual water in the 

Quantum tank, which will contain a small quantity 
of inhibitor, may be poured into a bucket and 
added to the F&E tank after this has been 
cleaned. 

 

Note: In a pressurised system the inhibitor may 
be injected into the system using an IK6 injector, 
which will avoid wasting any inhibitor left in the 
Quantum tank.   (see page F.5). 

 

 

UPON COMPLETION 

 
1. Restore system to normal, restoring radiator 

balance valves to original settings, removing any 
temporary isolating valves or caps on the 
expansion and cold feed pipes, and restoring non 
return valves to normal operation if necessary. 

 
2. Before re-connecting the feed & expansion tank, it 

should be thoroughly cleaned, removing all traces 
of dirty water and sludge, and then disinfected 
with Kamchlor chlorine release tablets. 

 
 

The Quantum is also a very powerful descaling 

pump, suitable for use when descaling 

combination boiler domestic water heat 

exchangers, any conventional domestic boiler, 

water heaters, direct fired water heaters, thermal 

store type water heaters, showers, and 

calorifiers. 

 

Issue: Mar 2008 

Section B  – Using the Quantum for Power Flushing

 Page 

B.10 

© Kamco

Содержание CLEARFLOW CF90: QUANTUM

Страница 1: ...K a m c o...

Страница 2: ...e safe use of the pump How to connect the pump into the heating system step by step guide to the flushing process and which chemicals are best suited for each application Please take time to carefully...

Страница 3: ...items Regularly check power leads for wear or damage use with a residual circuit breaker When handling chemicals wear suitable protective clothing gloves and goggles Use in a well ventilated area PAT...

Страница 4: ...nto the Quantum if it has been connected connection details are in the next section 7 With vented systems it is necessary to cap off or loop together the expansion and cold feed pipes in order to avoi...

Страница 5: ...connected to the pump body see page F 2 Generally the unit should be located in a room with a suitable drain point and near to a convenient mains water supply such as a bathroom or kitchen The cold wa...

Страница 6: ...pump from the system until power flushing is commenced A pair of 0 5 metre long adapter hoses enabling the Quantum to be connected across the 1 1 2 unions are supplied as standard When used these are...

Страница 7: ...Check all hoses and connections for leaks 5 The Quantum has the ability to dump dirty water when the flow is in either direction Change the Quantum into dumping mode as follows remembering that the fl...

Страница 8: ...d more water if necessary Vent all radiators to ensure that there are no air pockets Use a cloth to absorb any liquid expelled as the system water may be discoloured and likely to stain 8 The flushing...

Страница 9: ...E FX2 IN A SYSTEM HYPER FLUSH Use Hyper Flush when The system contains aluminium radiators or heat exchangers You consider the system to have suffered severe internal corrosion and metal wastage The s...

Страница 10: ...e radiators in turn so that you have flushed every radiator individually including upstairs radiators 12 When you have flushed the last radiator and obtained an even temperature across the surface swi...

Страница 11: ...amples show the same colour Note As an alternative an electronic pH meter may be used see page F 11 22 If you have a TDS meter Total Dissolved Solids it is useful to test the water at this stage The r...

Страница 12: ...e system 10 Open the valves on the next radiator and repeat the procedure 11 Work through the rest of the radiators in turn so that you have flushed every radiator individually including upstairs radi...

Страница 13: ...k which will contain a small quantity of inhibitor may be poured into a bucket and added to the F E tank after this has been cleaned Note In a pressurised system the inhibitor may be injected into the...

Отзывы: